Plan Review Details - Permit 11040607
Plan Review Stops For Permit 11040607
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-16 Cont ID  
Sent By jwitmer Date 2011-05-16 Time 15:02 Rev Time 2.20
Received By jwitmer Date 2011-05-16 Time 15:02 Sent To  
Notes
2011-05-16 16:58:41BUILDING PLAN REVIEW
 PERMIT: 11040607
 ADD: 4317 NORTHSHORE DR SUITE # 4211
 CONT: TO BE DETERMINED
 CONTACT: FANTASIA SIMS
 TEL: (561)577-6874
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS*
 WEST PALM BEACH AMENDMENTS
 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC
 SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATOR'S
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIROMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.THIS REVIEW WILL BE CONDUCTED FOR AN I-2
 OCCUPANCY WITH THE FOLOWING PARAMETERS:
 A) CHILD CARE WILL BE PROVIDED ON A 24 HOUR BASIS
 B) THE CHILD CARE FACILITY WILL HOUSE MORE THAN 5
 CHILDREN WHO ARE 2 1/2 YEARS OLD AND YOUNGER.
 C) IT IS ALSO ASSUMED THAT MEDICAL SUPERVISION IS
 PRESENT IN GROUP I-2 FACILITIES.
 2007 FBC-B 308.3.1.
  
 1) PLEASE REVIEW THE 2007/ 09 FL EXISTING BLDG CODE
 901.3.1 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY. PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
 1A) THE MINIMUM BUILDING TYPE OF CONSTRUCTION. FBC-B
 TABLE 503 SQ FT AREA / HEIGHT OF BUILDING
  
 1B) IF PLEASE PROVIDE IF THE BUILDING IS FIRE
 SPRINKLERED PER FBC-B 504.2 OR 903.
  
 1C) IF THE DESIGNER OF RECORD HAS DESIGNED THIS TENANT
 SPACE PER EXISTING BLDG CODE 912.1.1.1 WITHOUT
 SEPERATION OR 912.1.1.2 WITH SEPERATION.
 2007 FBC-B TABLE 508.3.3 & 106.3.5 (4).
  
 1D) PLANS INDICATING THE FLOOR PLAN OF THE HAIR SALON
 TO SEE WHAT SYSTEMS THAT WILL BE CHANGED. 2007 FBC-B
 106.3.5 & 106.1.2.
  
 2) EXISTING BLDG CODE 912.1.2 FIRE PROTECTION AND
 INTERIOR FINISH. THE PROVISIONS OF SECTIONS 912.2 AND
 912.3 FOR FIRE PROTECTION AND INTERIOR FINISH,
 RESPECTIVELY, SHALL APPLY TO ALL BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 2A) EX BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A
 CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES
 AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 2007 FBC-B F] 903.2.5 GROUP I. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT BUILDINGS WITH A
 GROUP I FIRE AREA.
  
 2B) EX BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 FBC-B [F] 907.2.6 GROUP I. A MANUAL FIRE ALARM SYSTEM
 SHALL BE INSTALLED IN GROUP I OCCUPANCIES. AN
 ELECTRICALLY SUPERVISED, AUTOMATIC SMOKE DETECTION
 SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 907.2.6.1 AND 907.2.6.2.
  
 EXCEPTION: MANUAL FIRE ALARM BOXES IN RESIDENT OR
 PATIENT SLEEPING AREAS OF GROUP I-1 AND I-2 OCCUPANCIES
 SHALL NOT BE REQUIRED AT EXITS IF LOCATED AT ALL
 NURSES' CONTROL STATIONS OR OTHER CONSTANTLY ATTENDED
 STAFF LOCATIONS, PROVIDED SUCH STATIONS ARE VISIBLE AND
 CONTINUOUSLY ACCESSIBLE AND THAT TRAVEL DISTANCES
 REQUIRED IN SECTION 907.3.1 ARE NOT EXCEEDED.
  
 [F] 907.2.6.2 GROUP I-2. CORRIDORS IN NURSING HOMES
 (BOTH INTERMEDIATE CARE AND SKILLED NURSING
 FACILITIES), DETOXIFICATION FACILITIES AND SPACES
 PERMITTED TO BE OPEN TO THE CORRIDORS BY SECTION 407.2
 SHALL BE EQUIPPED WITH AN AUTOMATIC FIRE DETECTION
 SYSTEM. HOSPITALS SHALL BE EQUIPPED WITH SMOKE
 DETECTION AS REQUIRED IN SECTION 407.2.
  
 EXCEPTIONS:
  
 1. CORRIDOR SMOKE DETECTION IS NOT REQUIRED IN SMOKE
 COMPARTMENTS THAT CONTAIN PATIENT SLEEPING UNITS WHERE
 PATIENT SLEEPING UNITS ARE PROVIDED WITH SMOKE
 DETECTORS THAT COMPLY WITH UL 268. SUCH DETECTORS SHALL
 PROVIDE A VISUAL DISPLAY ON THE CORRIDOR SIDE OF EACH
 PATIENT SLEEPING UNIT AND AN AUDIBLE AND VISUAL ALARM
 AT THE NURSING STATION ATTENDING EACH UNIT.
  
 2. CORRIDOR SMOKE DETECTION IS NOT REQUIRED IN SMOKE
 COMPARTMENTS THAT CONTAIN PATIENT SLEEPING UNITS WHERE
 PATIENT SLEEPING UNIT DOORS ARE EQUIPPED WITH AUTOMATIC
 DOOR-CLOSING DEVICES WITH INTEGRAL SMOKE DETECTORS ON
 THE UNIT SIDES INSTALLED IN ACCORDANCE WITH THEIR
 LISTING, PROVIDED THAT THE INTEGRAL DETECTORS PERFORM
 THE REQUIRED ALERTING FUNCTION.
  
  
 2C) FBC-B 912.3 INTERIOR FINISH. IN AREAS OF THE
 BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 2C) INTERIOR FINISHES 2007 EX BLDG CODE 912.3 INTERIOR
 FINISH. IN AREAS OF THE BUILDING UNDERGOING THE CHANGE
 OF OCCUPANCY CLASSIFICATION, THE INTERIOR FINISH OF
 WALLS AND CEILINGS SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING , FOR THE NEW
 OCCUPANCY CLASSIFICATION.
  
 2007 FBC-B 806.1 GENERAL REQUIREMENTS. IN OCCUPANCIES
 IN GROUPS A, E, I AND R-1 AND DORMITORIES IN GROUP R-2,
 CURTAINS, DRAPERIES, HANGINGS AND OTHER DECORATIVE
 MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET
 THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 IN ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
  
 IN GROUPS I-1 AND I-2, COMBUSTIBLE DECORATIVE MATERIALS
 SHALL MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701
 UNLESS THE DECORATIVE MATERIALS, INCLUDING, BUT NOT
 LIMITED TO, PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH
 LIMITED QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR
 SPREAD IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE
 DECORATIVE MATERIALS ARE PROHIBITED.
  
 FIXED OR MOVABLE WALLS AND PARTITIONS, PANELING, WALL
 PADS AND CRASH PADS APPLIED STRUCTURALLY OR FOR
 DECORATION, ACOUSTICAL CORRECTION, SURFACE INSULATION
 OR OTHER PURPOSES SHALL BE CONSIDERED INTERIOR FINISH
 IF THEY COVER 10 PERCENT OR MORE OF THE WALL OR OF THE
 CEILING AREA, AND SHALL NOT BE CONSIDERED DECORATIVE
 MATERIALS OR FURNISHINGS.
  
 3) 2007 EX BLDG CODE 912.1.4 ACCESSIBILITY. ALL
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8.
 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS
 THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2007/09 FBC-B 11-4.1.62) ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION. IN ADDITION TO THE
 REQUIREMENTS OF SECTION 11-4.1.6(1), AN ALTERATION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO
 AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE
 PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA, ARE READILY ACCESSIBLE TO AND USABLE BY
 INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS
 ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN
 TERMS OF COST AND SCOPE.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
  
  
 4) 2007 EX BLDG CODE 912.4 MEANS OF EGRESS, GENERAL.
 HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND MEANS OF
 EGRESS SHALL BE IN ACCORDANCE WITH TABLE 912.4.
 I-2 INSTITUTIONAL 2
 HAIR SALON: BUSINESS 4
  
 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 2007 FBC-B PLEASE PROVIDE THE OCCUPANT LOAD ACCORDING
 TO 2007 TABLE 1004.1.1 FBC-B FOR I-2 OCCUPANCY, IF
 DAYCARE OCCUPANCY THIS WILL BE FORE LESS THAN 24 HR
 STAY THE PLANS AND PERMIT APPLICATION WILL NEED TO
 REFLECT THIS CHANGE OF OCCUPANCY.
  
 IF THIS IS A I-2 OCCUPANCY WHERE THE OCCUPANTS WILL BE
 HERE MORE THAN 24 HRS, THIS IS DIFFERENT FROM BEING
 OPEN 24 HOURS, PLEASE REVIEW THE REQUIREMENTS FOR
 PATIENT SLEEPING ROOMS AND SMOKE BARRIERS AND REFUGE
 AREAS.
  
 PLEASE SEE REQUIREMENTS FOR I-2 OCCUPANCY EXIST BLDG
 CODE 705.4.1.2.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-19 Cont ID  
Sent By rlecky Date 2011-05-19 Time 10:11 Rev Time 0.00
Received By rlecky Date 2011-05-19 Time 09:11 Sent To  
Notes
2011-05-19 10:13:01PROVIDE AN ELECTRICAL PLAN FOR THE FACILITY
 PROVIDE A LIGHTING PLAN
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT.
 RECEPTACLES IN BATHROOMS AND KITCHEN AREAS SHALL BE
 GFCI PROTECTED
 INTERCONNECTED SMOKE ALARMS WITH BATTERY BACK UP ARE
 REQUIRED IN EACH SLEEPING AREA AND OUTSIDE EACH
 SLEEPING AREA
 SEPERATE ELECTRIC PERMIT IS REQUIRED FOR ELECTRIC
 CHANGES NEEDED
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-26 Cont ID  
Sent By wjolin Date 2011-04-26 Time 13:36 Rev Time 0.00
Received By wjolin Date 2011-04-26 Time 12:47 Sent To  
Notes
2011-04-26 13:13:514317 NORTHSHORE DRIVE, SUITE #4211
 PERMIT #11040607
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN AND OPERATION OF THE DAY-CARE OCCUPANCY SHALL
 COMPLY WITH THE FLORIDA FIRE PREVENTION CODE 2007
 EDITION; SPECIFICALLY CHAPTER 16 TITLED NEW DAY-CARE
 OCCUPANCIES.
  
 DAY-CARE OCCUPANCY SHALL BE SEPARATED FROM ADJACENT
 OCCUPANCIES BY AT LEAST A ONE HOUR FIRE RATED BARRIER.
  
 IDENTIFY THE OCCUPANCY TYPE OF THE TWO ADJACENT TENANT
 SPACES.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 TWO EXITS ARE REQUIRED FROM THE BUILDING. CURRENTLY THE
 REAR EXIT DISCHARGES INTO THE PROPOSED FENCE ENCLOSURE.
  
 PROVIDE EMERGENCY LIGHTING.
  
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B.
  
 PROVIDE A MONITORED FIRE ALARM SYSTEM INTEGRATED WITH
 SMOKE DETECTORS. SYSTEM SHALL INITIATE BY MANUAL MEANS
 AND SMOKE DETECTORS.
  
 PROVIDE AN EMERGENCY PLAN.
  
 FIRE DRILLS SHALL BE CONDUCTED MONTHLY AND ALL
 OCCUPANTS SHALL PARTICIPATE IN THE DRILL.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF. A COPY OF THE
 LATEST INSPECTION REPORT SHALL BE POSTED IN A
 CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
  
 STAFF MEMBERS SHALL INSPECT ALL EXIT FACILITIES DAILY
 TO ENSURE ALL DOORS AND EXIT PATHS ARE UNLOCKED AND
 UNOBSTRUCTED.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 ARE LIMITED TO 20 PERCENT OF THE WALL AREA OF BUILDINGS
 NOT PROTECTED BY AUTOMATIC SPRINKLERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-19 Cont ID  
Sent By lmartine Date 2011-05-19 Time 10:53 Rev Time 0.00
Received By lmartine Date 2011-04-25 Time 14:43 Sent To  
Notes
2011-04-25 14:43:43SENT TO B7.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-05-17 Cont ID  
Sent By jwitmer Date 2011-05-17 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2011-05-17 Time 11:37 Sent To  
Notes
2011-05-17 11:37:39BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-05-18 Cont ID  
Sent By lwagner Date 2011-05-18 Time 14:19 Rev Time 0.00
Received By lwagner Date 2011-05-18 Time 13:35 Sent To  
Notes
2011-05-18 14:07:47FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. A SERVICE SINK WILL BE REQUIRED PLUMBING 403.1
  
 2. FBC PLUMBING 403.2 SEPERATE FACILITIES
 PLEASE SEE BUILDING REVIEW ITEM #3 REGARDING
 ACCESSIBILITY ISSUES.
 ...SECTION 11-4.1.6(1), AN ALTERATION THAT
 AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO
 AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE
 PATH OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA, ARE READILY ACCESSIBLE TO AND USABLE BY
 INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS
 ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN
 TERMS OF COST AND SCOPE......
  
 PLEASE CHECK WITH HEALTH DEPT. FOR CHILD CARE
 REQUIREMENTS FOR LICENSE OR CERTIFICATE
 PALM BEACH COUNTY HEALTH DEPARTMENT
 800 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 837-5900
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-05-04 Cont ID  
Sent By astelly Date 2011-05-04 Time 10:37 Rev Time 0.00
Received By astelly Date 2011-05-04 Time 10:41 Sent To  
Notes
2011-05-04 10:44:17AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/ PROVISO
  
 FENCE PERMIT SHALL BE REVISED TO COMPLY WITH THE FIRE
 MARSHALL'S COMMENTS REGARDING DISCHARGE. ALL SIGNAGE
 SHALL REQUIRE A SEPARATE PERMIT.