Plan Review Details - Permit 11040584
Plan Review Stops For Permit 11040584
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-06-29 Cont ID  
Sent By rlecky Date 2011-06-29 Time 08:36 Rev Time 0.00
Received By rlecky Date 2011-06-29 Time 08:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-22 Cont ID  
Sent By rlecky Date 2011-04-22 Time 09:13 Rev Time 0.00
Received By rlecky Date 2011-04-22 Time 09:04 Sent To  
Notes
2011-04-22 09:11:10PROVIDE A ONE LINE DIAGRAM SHOWING THE EXISTING
 SERVICE, MAIN DISCONNECTS, VOLTAGE, SERVICE GROUNDING
 AND FEEDERS. NEC 215.5, 215.6.
 PROVIDE SPECIFICATION ON THE NEW DISCONNECT SHOWING THE
 EQUIPMENT IS SUFFICIENT TO INTERRUPT THE AVAILABLE
 FAULT CURRENT. NEC 110.9
 PROVIDE A FAULT CURRENT CALCULATION TO SUPPORT THE
 EQUIPMENT SELECTION. NEC 110.10
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  