| Plan Review Stops For Permit 11040584 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-06-29 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-06-29 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-06-29 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-04-22 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-22 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-22 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2011-04-22 09:11:10 | PROVIDE A ONE LINE DIAGRAM SHOWING THE EXISTING | | | SERVICE, MAIN DISCONNECTS, VOLTAGE, SERVICE GROUNDING | | | AND FEEDERS. NEC 215.5, 215.6. | | | PROVIDE SPECIFICATION ON THE NEW DISCONNECT SHOWING THE | | | EQUIPMENT IS SUFFICIENT TO INTERRUPT THE AVAILABLE | | | FAULT CURRENT. NEC 110.9 | | | PROVIDE A FAULT CURRENT CALCULATION TO SUPPORT THE | | | EQUIPMENT SELECTION. NEC 110.10 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-06-29 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-06-29 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-06-29 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-04-22 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-22 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-21 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
|