Plan Review Details - Permit 11040544
Plan Review Stops For Permit 11040544
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-10 Cont ID  
Sent By jwitmer Date 2011-05-10 Time 12:39 Rev Time 0.55
Received By jwitmer Date 2011-05-10 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-21 Cont ID  
Sent By jwitmer Date 2011-04-21 Time 13:18 Rev Time 0.25
Received By jwitmer Date 2011-04-21 Time 13:17 Sent To  
Notes
2011-04-21 13:23:58 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 11040544
 ADD: 1258 PALM BEACH LAKES
 CONT: OCEAN BUILDERS
 TEL: (772)341-6636
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. THERE HAS BEEN NO PLANS SUBMITTED ONLY A
 SURVEY. HAND WRITTEN IS SCOPE OF WORK TO BE COMPLETED
 UNDER THIS PERMIT INCLUDING REPLACEMENT OF EQUIPMENT.
 WITHOUT THIS INFORMATION IT IS NOT POSSIBLE FOR THE
 TRADES TO MAKE COMMENTS! 106.1.2 ADDITIONAL INFORMATION
 REQUIED. PLEASE PROVIDE A FLOOR PLAN AND A LIFE SAFETY
 PLAN.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-08-08 Cont ID  
Sent By rlecky Date 2011-08-08 Time 11:22 Rev Time 0.00
Received By rlecky Date 2011-08-08 Time 11:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-05-04 Cont ID  
Sent By rlecky Date 2011-05-04 Time 12:01 Rev Time 0.00
Received By rlecky Date 2011-05-04 Time 12:01 Sent To  
Notes
2011-05-04 12:01:55PREVIOUS ELECTRIC REVIEW COMMENTS WERE NOT ADDRESSED.
  
 REQUIRES A SEPARATE ELECTRIC PERMIT AND PLAN.
 SHOW EXISTING SERVICE LOCATION WITH SAFETY CLEARANCES,
 POWER PLAN AND RISER.
 SHOW EXIT SIGNS AND EMERGENCY LIGHTING.
 SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-25 Cont ID  
Sent By rlecky Date 2011-04-25 Time 08:03 Rev Time 0.00
Received By rlecky Date 2011-04-25 Time 07:56 Sent To  
Notes
2011-04-25 08:02:48REQUIRES A SEPARATE ELECTRIC PERMIT AND PLAN.
 SHOW EXISTING SERVICE LOCATION WITH SAFETY CLEARANCES,
 POWER PLAN AND RISER.
 SHOW EXIT SIGNS AND EMERGENCY LIGHTING.
 SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-07-28 Cont ID  
Sent By wjolin Date 2011-07-28 Time 11:39 Rev Time 0.00
Received By wjolin Date 2011-07-28 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-05-05 Cont ID  
Sent By wjolin Date 2011-05-05 Time 13:15 Rev Time 0.00
Received By wjolin Date 2011-05-05 Time 12:51 Sent To  
Notes
2011-05-05 13:14:061258 PALM BEACH LAKES BOULEVARD
 PERMIT #11040544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 RESTROOM DOOR SWING AND FREEZER DOOR SWING OBSTRUCTS
 EGRESS.
  
 AN 8 INCH STEEL BAFFLE IS REQUIRED BETWEEN FRYER GREASE
 AND SURFACE FLAMES OF ADJACENT COOKING EQUIPMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-26 Cont ID  
Sent By wjolin Date 2011-04-26 Time 12:10 Rev Time 0.00
Received By wjolin Date 2011-04-26 Time 11:51 Sent To  
Notes
2011-04-26 12:10:291258 PALM BEACH LAKES BOULEVARD
 PERMIT #11040544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LIFE SAFETY PLAN SHOWING EXIT DOORS, DOOR
 LOCKS, TRAVEL DISTANCE TO EXITS, EXIT SIGNS, PORTABLE
 FIRE EXTINGUISHER LOCATIONS, SEATING CONFIGURATION ETC.
  
 POST NUMERICAL ADDRESS ON THE BUILDING. NUMBERS SHALL
 BE AT LEAST SIX INCHES TALL AND SHALL CONTRAST THE
 BACKGROUND COLOR.
  
 IF APPLICABLE, STRUCTURES WITH LIGHT FRAME ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 GREASE COOKING EQUIPMENT SHALL BE PROVIDED WITH A TYPE
 K EXTINGUISHER.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR ANY COOKING
 EQUIPMENT FIRE SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-09 Cont ID  
Sent By lmartine Date 2011-08-09 Time 14:36 Rev Time 0.00
Received By lmartine Date 2011-07-25 Time 11:33 Sent To  
Notes
2011-07-25 11:40:00SENT TO B15 FOR ALL TRADES REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-09 Cont ID  
Sent By lmartine Date 2011-05-17 Time 14:36 Rev Time 0.00
Received By lmartine Date 2011-05-02 Time 16:36 Sent To  
Notes
2011-05-02 16:37:02B3
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-09 Cont ID  
Sent By lmartine Date 2011-05-04 Time 14:35 Rev Time 0.00
Received By lmartine Date 2011-04-20 Time 08:16 Sent To  
Notes
2011-04-21 08:36:03B3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-08-08 Cont ID  
Sent By hmoser Date 2011-08-08 Time 12:09 Rev Time 0.00
Received By hmoser Date 2011-08-08 Time 12:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-05-17 Cont ID  
Sent By hmoser Date 2011-05-17 Time 07:56 Rev Time 0.00
Received By hmoser Date 2011-05-17 Time 07:56 Sent To  
Notes
2011-05-17 08:08:07DENIED
 NO PLANS SUBMITTED
 REFER TO SECTION 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
 REFER TO SECTION 106.3.4 SITE DRAWINGS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-04-26 Cont ID  
Sent By hmoser Date 2011-04-26 Time 07:13 Rev Time 0.00
Received By hmoser Date 2011-04-26 Time 07:13 Sent To  
Notes
2011-04-26 07:16:08PLANS DENIED
 NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-07-27 Cont ID  
Sent By lwagner Date 2011-07-27 Time 10:58 Rev Time 0.00
Received By lwagner Date 2011-07-27 Time 10:44 Sent To  
Notes
2011-07-27 10:58:18GAS APPLICATION, DRAWING, AND PERMIT BASED ON VALUE
 WILL BE REQUIRED FOR ANY GAS PIPE, NEW CONNECTIONS, OR
 NEW GAS APPLIANCES TO BE INSTALLED.
  
 DBPR DIVISION OF HOTELS AND RESTAURANTS (H&R) LICENSES
 WILL REQUIRE A MOP SINK THAT IS NOT IN THE FOOD
 HANDLING AREA IF ONE IS NOT EXISTING.
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/INDEX.HTML

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-06 Cont ID  
Sent By lwagner Date 2011-05-06 Time 14:10 Rev Time 0.00
Received By lwagner Date 2011-05-06 Time 13:27 Sent To  
Notes
2011-05-06 13:55:01GAS APPLICATION, DRAWING, AND PERMIT BASED ON VALUE
 WILL BE REQUIRED FOR ANY GAS PIPE, NEW CONNECTIONS, OR
 NEW GAS APPLIANCES TO BE INSTALLED.
  
 DBPR DIVISION OF HOTELS AND RESTAURANTS (H&R) LICENSES
 WILL REQUIRE A MOP SINK THAT IS NOT IN THE FOOD
 HANDLING AREA IF ONE IS NOT EXISTING.
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/INDEX.HTML

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-04-22 Cont ID  
Sent By lwagner Date 2011-04-22 Time 13:59 Rev Time 0.00
Received By lwagner Date 2011-04-21 Time 13:32 Sent To  
Notes
2011-04-22 12:49:16FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 PLEASE REFER TO BUILDING PLAN REVIEW COMMENT #1.
  
 PLUMBING 403.2 SEPERATE RESTROOM FACILITIES FOR EACH
 SEX WILL BE REQUIRED FOR MORE THAN TEN SEATS.
  
 A SEPERATE GAS APPLICATION, DRAWING, AND PERMIT WILL BE
 REQUIRED IF CHANGING ANY GAS EQUIPMENT/ PIPING/ ETC.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-08-09 Cont ID  
Sent By astelly Date 2011-08-09 Time 09:15 Rev Time 0.00
Received By astelly Date 2011-08-09 Time 09:15 Sent To  
Notes
2011-08-09 09:17:00AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/PROVISO
 SEPARATE PAVING AND LANDSCAPING PERMITS ARE REQUIRED
 FOR THE REQUIRED RE-STRIPING AND LANDSCAPING OF THE
 PARKING LOT.
 THE TERMINAL AND INTERIOR ISLANDS SHOWN ON THE PLAN
 MUST BE CURBED AND LANDSCAPED PER SEC. 94-443(C)(3).

Review Stop Z ZONING
Rev No 1 Status F Date 2011-05-04 Cont ID  
Sent By astelly Date 2011-05-04 Time 10:11 Rev Time 0.00
Received By astelly Date 2011-05-04 Time 10:11 Sent To  
Notes
2011-05-04 10:32:32AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE SUBMIT A SITE PLAN SHOWING THE DUMPSTER LOCATION
 AND ALL PARKING AND LANDSCAPING. THE PARKING
 REQUIREMENTS CAN BE FOUND IN ARTICLE XV OF THE ZONING
 CODE. THE REQUIREMENTS FOR LANDSCAPING ARE CONTAINED IN
 ARTICLE XIV.
  
 ADDITIONAL COMMENT (5/16):
 DURING THE WEEK OF MAY 16, 2011, CODE ENFORCEMENT NOTED
 THAT THE CONTENT OF THE SIGN HAD BEEN CHANGED WITHOUT
 OBTAINING A PERMIT. PERMITS ARE REQUIRED FOR ALL FACE
 CHANGES TO SIGNAGE. PLEASE PULL THE APPROPRIATE PERMITS
 FOR THIS SCOPE OF WORK.
  
 YOUR RESUBMISSION MAY GENERATE ADDITIONAL COMMENTS.