Plan Review Details - Permit 11040525
Plan Review Stops For Permit 11040525
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-22 Cont ID  
Sent By rmcdouga Date 2011-04-22 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2011-04-22 Time 08:11 Sent To  
Notes
2011-04-22 08:14:072007 FBC WITH 2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION. NOTE: IF FORM 1100B-08 IS USED R-13
 INSULATION IS REQUIRED IN THE EXTERIOR FRAME WALLS.
  
 2) PRODUCT APPROVALS WERE SUBMITTED FOR A FIXED IMPACT
 RATED WINDOW. THIS TYPE WINDOW WAS NOT INDICATED ON THE
 PLANS. PLEASE CLARIFY.
  
 3) THE PRODUCT APPROVALS FOR THE DOUBLE HUNG AND FIXED
 IMPACT RATED WINDOWS SPECIFY DESIGN PRESSURES OF +55
 AND -65 PSF. THE PLANS SPECIFY THE COMPONENT AND
 CLADDING PRESSURES AS +49.42, -66.08 PSF IN WALL ZONE
 5. THEREFORE, THE NEGATIVE PRESSURES OF THE PRODUCTS
 ARE TOO LOW FOR USE IN WALL ZONE 5.
  
 4) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND
 DESIGN PRESSURE FROM THE GAF ROOFING PRODUCT APPROVAL
 THAT WILL BE USED. SUBMIT TWO SETS OF SIGNED AND SEALED
 RAS CALCULATIONS FOR THE ENHANCED FASTENING OF THE BASE
 SHEET AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE 19 OF
 THE PRODUCT APPROVAL.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-22 Cont ID  
Sent By rmcdouga Date 2011-04-22 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2011-04-22 Time 08:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-04-20 Cont ID  
Sent By jpapa Date 2011-04-20 Time 10:46 Rev Time 0.00
Received By jpapa Date 2011-04-20 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-22 Cont ID  
Sent By rmcdouga Date 2011-04-22 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2011-04-20 Time 13:50 Sent To  
Notes
2011-04-20 13:52:01****************EXPEDITED****************
 R--5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-04-22 Cont ID  
Sent By rmcdouga Date 2011-04-22 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2011-04-22 Time 08:09 Sent To  
Notes
2011-04-22 08:10:59BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-22 Cont ID  
Sent By rmcdouga Date 2011-04-22 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2011-04-22 Time 08:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-20 Cont ID  
Sent By jpapa Date 2011-04-20 Time 10:46 Rev Time 0.00
Received By jpapa Date 2011-04-20 Time 10:46 Sent To  
Notes
***NONE***