| 2011-05-26 11:30:12 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ENGINEER OF RECORD NEEDS TO UPDATE HIS LICENSE WITH |
| | THE FLORIDA DEPARTMENT OF BUSINESS & PROFESSIONAL |
| | REGULATION (DBPR). HIS STATUS IS DELINQUENT. ENGINEER |
| | TO CONTACT THE DBPR TO UPDATE HIS LICENSE STATUS. |
| | |
| | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4- ENGINEER TO REVISE THE BUILDING EXPOSURE. ACCORDING |
| | TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NO "B". REVISE BUILDING |
| | EXPOSURE AND ALL DESIGN PRESSURES ACCORDINGLY. REVISE |
| | DESIGN CRITERIA ON SHEET #2 AND SHEET # T-1. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. 2 DIFFERENT PRODUCT APPROVALS |
| | WERE SUBMITTED. FLORIDA PRODUCT APPROVAL FL239-R12 |
| | SUBMITTED FOR PGT WINDOWS IS MISSING THE DRAWINGS |
| | SHOWING THE WINDOWS SPECS. IN ADDITION NOA 09-0316.10 |
| | SUBMITTED FOR AWP WINDOWS IS SUPERSEDED BY MIAMI-DADE. |
| | VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. |
| | PLEASE SELECT ONLY ONE WINDOW COMPANY AND CORRESPONDING |
| | PRODUCT APPROVAL. |
| | |
| | B) SHINGLES NOA 08-1110.11 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD |
| | CURRENT NOA. NOTE: DOWNLOAD CURRENT NOA 10-11222.08. |
| | |
| | C) STORM PANELS. FLORIDA PRODUCT APPROVAL FL7030 |
| | SUBMITTED IS FOR 2004 CODE. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR 2007 CODE VERSION. |
| | ****ALSO: PROVIDE SHUTTERS COMPLETE INSTALLATION |
| | SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS |
| | SPECIFIC SHUTTERS MOUNTING CONDITIONS AND ANCHOR TYPE |
| | AND SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. NOTE: PROVIDE ONLY THE PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | OR, ENGINEER TO SPECIFY STRUCTURAL CONNECTOR PRODUCT |
| | APPROVAL NUMBER ON DRAWINGS. |
| | |
| | E) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 7- SHEET T-1: ENGINEER TO REVISE ROOF SHEATHING NAILING |
| | NOTE. NEED TO SPECIFY 8D RING SHANK NAILS AT 4"O.C. IN |
| | ROOF ZONE #3 AS REQUIRED BY SEC. R803.2.3.1. ALSO, ROOF |
| | PERIMETER AND CORNER AREAS NEED TO BE SPECIFIED AS |
| | 4'-0" MIN. SEE FIGURE R301.2(7). |
| | |
| | 8- SURVEY SUBMITTED: A) PROPERTY IS LOCATED ON FLOOD |
| | ZONE "B" NO "C". REVISE AS REQUIRED. |
| | |
| | B) SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPER 472 FLORIDA STATUTE WHEN SUBMITTING SURVEYS FOR |
| | PUBLIC RECORDS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |