Plan Review Details - Permit 11040492
Plan Review Stops For Permit 11040492
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-08-19 Cont ID  
Sent By jgomez Date 2011-08-19 Time 11:15 Rev Time 0.00
Received By jgomez Date 2011-08-19 Time 11:15 Sent To  
Notes
2011-08-19 13:06:20BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENERGY CALCULATIONS SUBMITTED: A) SHOW PTAC UNIT FOR
 HEATING AND COOLING. PLANS SUBMITTED SHOW SPLIT A/C
 UNIT. REVISE PLANS AS REQUIRED. PTAC UNIT FOR HEATING
 MUST BE HARD WIRED AND A/C PERMIT IS REQUIRED (PROVIDE
 COMPLETE INFORMATION FOR A/C UNDER A SEPARATE PERMIT) .
 SEE SEC R303.8.
 B) REVISE MATERIAL OF DOOR TO BE USED. IT ISN'T WOOD.
 SEE NOA SUBMITTED.
 C) PROVIDE CORRECT BUILDER'S NAME.
  
 2- ENTRY DOOR NOA SUBMITTED IS FOR A NON-IMPACT
 DOOR/SIDELITE. PROVIDE COMPLETE SHUTTERS INFORMATION.
 PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE.
 ARCHITECT TO REVIEW PRODUCT APPROVAL PRIOR TO
 SUBMITTAL. SEC. 106.3.3 CITY AMENDMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-07-26 Cont ID  
Sent By jgomez Date 2011-07-26 Time 10:33 Rev Time 0.00
Received By jgomez Date 2011-07-26 Time 10:23 Sent To  
Notes
2011-07-26 11:24:02RESIDENTIAL (R3) ALTERATION BUILDING REVIEW THIRD
 CHECKLIST.
 2007 EXISTING BUILDING CODE, 2007 FLORIDA RESIDENTIAL
 CODE WITH 2009 REVSIONS.
  
  
 1- NEW CALCULATED DESIGN PRESSURES FOR WINDOWS AND
 DOORS LOCATED ON THE END ZONE ARE TOO LOW (IT MAY BE
 THAT CALCULATIONS WERE DONE USING EXPOSURE "B" INSTEAD
 OF EXPOSURE "C") . AND THEY ARE ALMOST THE SAME AS THE
 ONES LOCATED ON THE INTERIOR ZONE. PROVIDE CALCULATIONS
 SHOWING HOW THESE DESIGN PRESSURES WERE OBTAINED. SEC.
 R301.2.1.4.3.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
 (REPEAT COMMENT). A BUILDING PERMIT CAN'T BE USED IF
 THESE FORMS ARE NOT SUBMITTED SHOWING COMPLIANCE WITH
 THE ENERGY CODE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS. (REPEAT COMMENT).
  
 B) REVISE RAS 117 CALCULATIONS FOR FLAT ROOF NOA
 08-0924.14 SUBMITTED. CALCULATIONS WERE DONE USING
 DESIGN PRESSURES WITH EXPOSURE "B". NEED TO USE
 CALCULATIONS FOR EXPOSURE "C. SEC. R301.2.1.4.3.
 *** AND, PROVIDE 2 COPIES OF CALCULATIONS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 481 WHEN
 SUBMITTING INFORMATION FOR PUBLIC RECORDS. ONLY ONE
 ORIGINAL WAS SUBMITTED. THE SECOND WAS A COPY. COPY IS
 NOT ALLOWED.
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS. NEED ENTRY DOOR
 WITH SIDELITE ASSEMBLY AT GUEST HOUSE AS SHOWN ON PLANS
 AND NEED DOOR AT STORAGE ENTRY. (REPEAT COMMENT. GUEST
 HOUSE NOA 08-0312.09 SUBMITTED EXPIRED ON MAY 25, 2011.
 NEED CURRENT NOA WITH DOOR INCLUDING THE SIDELITE AS
 SHOWN ON PLANS. AND, PRODUCT APPROVAL FOR STORAGE ROOM
 WAS NOT SUBMITTED).
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY
 OR ARCHITECT TO SPECIFY CURRENT PRODUCT APPROVAL NUMBER
 ON PLANS. ALL OTHER PRODUCT APPROVALS REQUIRE FULL
 REPORT. (REPEAT COMMENT).
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT).
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 6- PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE
 OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3. (REPEAT
 COMMENT).
  
 B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED
 IS NOT CORRECT. (REPEAT COMMENT).
  
 C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FBC-EXISTING. (REPEAT COMMENT).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-07-21 Cont ID  
Sent By jgomez Date 2011-07-21 Time 09:44 Rev Time 0.00
Received By jgomez Date 2011-07-21 Time 09:44 Sent To  
Notes
2011-07-21 09:50:39RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007
 FBC-EXISTING BUILDING.
  
 1- A) ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3
 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
 ARCHITECT TO REVISE THE BUILDING EXPOSURE ON PROJECT
 INFORMATION TABLE ON SHEET A-1.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 B) REVISE THE DOORS/WINDOWS DESIGN PRESSURES ON SHEET
 A-1 AND A-2 TO CORRESPOND TO EXPOSURE "C". SEE ITEM
 1(A) ABOVE. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 B) FLAT ROOF AS SHOWN ON PLANS. AND, MARK /IDENTIFY
 WHICH APPROVED ROOFING ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. IF GENERAL LIMITATION #7 REQUIRES SIGNED
 AND SEALED CALCULATIONS, THEN PROVIDE THEM SIGNED AND
 SEALED. (REPEAT COMMENT. CERTAINTEED INFORMATION
 SUBMITTED IS NOT A PRODUCT APPROVAL. CERTAINTEED
 PRODUCT REQUIRES SIGNED AND SEALED RAS 117
 CALCULATIONS. PRODUCT APPROVAL LIMITATIONS).
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE ASSEMBLY AT GUEST HOUSE AND DOOR AT STORAGE
 ENTRY. (REPEAT COMMENT. GUEST HOUSE NOA 08-0312.09
 SUBMITTED EXPIRED ON MAY 25, 2011. NEED CURRENT NOA.
 AND, PRODUCT APPROVAL FOR STORAGE ROOM WAS NOT
 SUBMITTED).
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
 ALL OTHER PRODUCT APPROVALS REQUIRE FULL REPORT.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 F) HARDI-PLAN SIDING AS SPECIFIED ON SHEET A-3 TYPICAL
 BEARING WALL DETAIL AND EXTERIOR ELEVATIONS. NOTE:
 HISTORIC NEEDS TO APPROVE IT ALSO. WOOD SIDING DOESN'T
 REQUIRE PRODUCT APPROVAL, BUT STILL NEED TO COORDINATE
 WITH HISTORIC APPROVAL. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 G) HURRICANE SHUTTERS IF DOORS AND WINDOWS PROVIDED
 DON'T HAVE IMPACT GLASS. CLEARLY IDENTIFY ON PRODUCT
 APPROVAL SPECIFIC SHUTTERS MOUNTING CONDITIONS AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 H) SIDELITE WINDOW AT GUEST HOUSE ENTRY DOOR.
 COORDINATE WITH ITEM #3(D) ABOVE. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- ARCHITECT TO SIGN AND SEAL BOTH SETS OF PLANS. ONLY
 ONE WAS SIGNED AND SEALED. CHAPTER 481 FLORIDA STATUTE.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 6- ARCHITECT TO PROVIDE IN THE TITLE BLOCK ALL THE
 INFORMATION REQUIRED BY SEC. 61G1-16004 OF THE FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
 MISSING THE ARCHITECT'S AND FIRM LICENSE NUMBER AND
 DATE WHEN DRAWINGS WHERE PREPARED. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. ROOF
 ZONE #3 REQUIRES 8D RING SHANK NAILS AT 4"O.C. ALSO.
 REVISE ROOF NAILING PATTERN ON SHEET A-1 PROJECT
 INFORMATION TABLE, ON SHEET A-2 SECTION AND ON SHEET
 A-3 TYPICAL BEARING WALL DETAIL. SEC. R803.2.3.1.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 9 - PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE
 OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED
 IS NOT CORRECT. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FBC-EXISTING. (REPEAT COMMENT. NOT ADDRESSED).
  
 10- SHEET A-2: A) ROOF PROFILE SHOWN ON FRONT
 ELEVATION, REAR ELEVATION AND LEFT ELEVATION DOESN'T
 MATCH ROOF FRAMING PLAN LAYOUT SHOWN ON SHEET A-1.
 REVISE AS REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) REAR ELEVATION IS MISSING THE WINDOW ON THE STORAGE
 ROOM AS SHOWN ON FLOOR PLAN ON SHEET A-1. REVISE AS
 REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 11- BRING ALL REVISED PLANS AND PRODUCT APPROVALS FOR
 HISTORIC APPROVAL PRIOR TO SUBMITTING TO THIS OFFICE TO
 AVOID CONFLICTS OR DELAYS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-19 Cont ID  
Sent By jgomez Date 2011-05-19 Time 13:08 Rev Time 0.00
Received By jgomez Date 2011-05-19 Time 13:08 Sent To PC
Notes
2011-05-19 13:30:09RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007
 FBC-EXISTING.
  
 1- A) ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3
 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
 ARCHITECT TO REVISE THE BUILDING EXPOSURE ON PROJECT
 INFORMATION TABLE ON SHEET A-1.
  
 B) REVISE THE DOORS/WINDOWS DESIGN PRESSURES ON SHEET
 A-1 AND A-2 TO CORRESPOND TO EXPOSURE "C". SEE ITEM
 1(A) ABOVE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS.
  
 B) FLAT ROOF AS SHOWN ON PLANS. AND, MARK /IDENTIFY
 WHICH APPROVED ROOFING ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. IF GENERAL LIMITATION #7 REQUIRES SIGNED
 AND SEALED CALCULATIONS, THEN PROVIDE THEM SIGNED AND
 SEALED.
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE ASSEMBLY AT GUEST HOUSE AND DOOR AT STORAGE
 ENTRY.
  
 D) WINDOWS AS SHOWN ON PLANS.
  
 E) WINDOW MULLIONS AS SHOWN ON PLANS. COORDINATE WITH
 ITEMS #3(C) AND #3(I).
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
 ALL OTHER PRODUCT APPROVALS REQUIRE FULL REPORT.
  
 G) HARDI-PLAN SIDING AS SPECIFIED ON SHEET A-3 TYPICAL
 BEARING WALL DETAIL. NOTE: HISTORIC NEEDS TO APPROVE IT
 ALSO. WOOD SIDING DOESN'T REQUIRE PRODUCT APPROVAL, BUT
 STILL NEED TO COORDINATE WITH HISTORIC APPROVAL.
  
 H) HURRICANE SHUTTERS IF DOORS AND WINDOWS PROVIDED
 DON'T HAVE IMPACT GLASS. CLEARLY IDENTIFY ON PRODUCT
 APPROVAL SPECIFIC SHUTTERS MOUNTING CONDITIONS AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 I) SIDELITE WINDOW AT GUEST HOUSE ENTRY DOOR.
 COORDINATE WITH ITEM #3(C) ABOVE.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO SIGN AND SEAL BOTH SETS OF PLANS. ONLY
 ONE WAS SIGNED AND SEALED. CHAPTER 481 FLORIDA STATUTE.
  
 6- ARCHITECT TO PROVIDE IN THE TITLE BLOCK ALL THE
 INFORMATION REQUIRED BY SEC. 61G1-16004 OF THE FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
 MISSING THE ARCHITECT'S AND FIRM LICENSE NUMBER AND
 DATE WHEN DRAWINGS WHERE PREPARED.
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. ROOF
 ZONE #3 REQUIRES 8D RING SHANK NAILS AT 4"O.C. ALSO.
 REVISE ROOF NAILING PATTERN ON SHEET A-1 PROJECT
 INFORMATION TABLE, ON SHEET A-2 SECTION AND ON SHEET
 A-3 TYPICAL BEARING WALL DETAIL. SEC. R803.2.3.1.
  
 9- PROJECT INFORMATION TABLE ON SHEET A-1: A) REVISE
 OCCUPANCY CLASS. THIS IS NOT R1. THIS IS R3.
  
 B) SPECIFY TYPE OF CONSTRUCTION. INFORMATION SUBMITTED
 IS NOT CORRECT.
  
 C) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FBC-EXISTING.
  
 10- SHEET A-2: A) ROOF PROFILE SHOWN ON FRONT
 ELEVATION, REAR ELEVATION AND LEFT ELEVATION DOESN'T
 MATCH ROOF FRAMING PLAN LAYOUT SHOWN ON SHEET A-1.
 REVISE AS REQUIRED.
  
 B) REAR ELEVATION IS MISSING THE WINDOW ON THE STORAGE
 ROOM AS SHOWN ON FLOOR PLAN ON SHEET A-1. REVISE AS
 REQUIRED.
  
 11- BRING ALL REVISED PLANS AND PRODUCT APPROVALS FOR
 HISTORIC APPROVAL PRIOR TO SUBMITTING TO THIS OFFICE TO
 AVOID CONFLICTS OR DELAYS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-05-02 Cont ID  
Sent By rlecky Date 2011-05-02 Time 10:25 Rev Time 0.00
Received By rlecky Date 2011-05-02 Time 09:57 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-06-09 Cont ID  
Sent By fmittner Date 2011-06-09 Time 14:57 Rev Time 0.00
Received By fmittner Date 2011-06-09 Time 14:57 Sent To  
Notes
2011-06-09 14:58:06REVISED PERMIT INTERIOR DEMO ONLY - APPROVED

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By jpapa Date 2011-04-28 Time 14:48 Rev Time 0.00
Received By jpapa Date 2011-04-28 Time 14:48 Sent To  
Notes
2011-04-28 15:24:24**PROVISOS**
  
 1. THE EXTERIOR FINISH SHALL FEATURE WOOD HORIZONTAL
 SIDING, CONSISTENT THROUGHOUT THE STRUCTURE, WITH A
 WIDTH OF APPROXIMATELY 6" TO MATCH THE EXISTING,
 HISTORIC FEATURE.
  
 2. PRODUCT SPECIFICATIONS FOR PROPOSED WINDOWS, DOORS
 SHALL BE SUBMITTED FOR HISTORIC PRESERVATION DIVISION
 REVIEW PRIOR TO INSTALLATION.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER, AT 561-822-1454.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-08-19 Cont ID  
Sent By jgomez Date 2011-08-19 Time 15:38 Rev Time 0.00
Received By jgomez Date 2011-08-18 Time 11:07 Sent To  
Notes
2011-08-18 11:07:31SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-07-26 Cont ID  
Sent By jgomez Date 2011-07-26 Time 10:23 Rev Time 0.00
Received By jgomez Date 2011-07-26 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-21 Cont ID  
Sent By jgomez Date 2011-07-21 Time 14:25 Rev Time 0.00
Received By jgomez Date 2011-07-20 Time 11:44 Sent To  
Notes
2011-07-20 11:44:19GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-19 Cont ID  
Sent By jgomez Date 2011-05-19 Time 13:30 Rev Time 0.00
Received By jgomez Date 2011-04-19 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-08-19 Cont ID  
Sent By jgomez Date 2011-08-19 Time 15:39 Rev Time 0.00
Received By jgomez Date 2011-08-19 Time 15:39 Sent To  
Notes
2011-08-19 15:41:371- ENERGY CALCULATIONS SUBMITTED SHOW PTAC UNIT.
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE A/C
 PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-05-19 Cont ID  
Sent By jgomez Date 2011-05-19 Time 13:07 Rev Time 0.00
Received By jgomez Date 2011-05-19 Time 13:07 Sent To  
Notes
2011-05-19 13:08:19NO INFORMATION GIVEN. PROVIDE COMPLETE INFORMATION
 UNDER A SEPARATE PERMIT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-19 Cont ID  
Sent By jgomez Date 2011-08-19 Time 15:47 Rev Time 0.00
Received By jgomez Date 2011-08-19 Time 15:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-19 Cont ID  
Sent By jgomez Date 2011-05-19 Time 13:07 Rev Time 0.00
Received By jgomez Date 2011-05-19 Time 13:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2011-08-25 Cont ID  
Sent By fmittner Date 2011-08-25 Time 13:47 Rev Time 0.00
Received By fmittner Date 2011-08-25 Time 13:47 Sent To  
Notes
2011-08-25 13:48:14NEW SURVEY SUBMITTED SHOWING 5 FOOT SETBACKS.

Review Stop Z ZONING
Rev No 2 Status F Date 2011-08-22 Cont ID  
Sent By fmittner Date 2011-08-22 Time 15:29 Rev Time 0.00
Received By fmittner Date 2011-08-22 Time 15:29 Sent To  
Notes
2011-08-22 15:30:48SINCE NEW FOOTER BEING POURED, MUST SUBMIT SITE PLAN
 SHOWING EXACT LOCATION OF PROPOSED STRUCTURE.
  
 CONTACT: FRIEDERIKE MITTNER 822-1457

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By jpapa Date 2011-04-28 Time 14:31 Rev Time 0.00
Received By jpapa Date 2011-04-28 Time 14:31 Sent To  
Notes
***NONE***