| Plan Review Stops For Permit 11040478 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-04-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-27 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-27 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-04-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-20 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-20 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2011-04-20 11:11:20 | PROVIDE A LOAD CALCULATION FOR THE UNDERSIZED NEUTRALS | | | (GROUNDED CONDUCTORS) OR PROVIDE FULL SIZED NEUTRALS. | | | NEC 215.2, 220.61, 230.42 | | | PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR. NEC 250.110, | | | 250.118 | | | PROVIDE A ONE LINE DIAGRAM SHOWING THE EXISTING | | | SERVICE, VOLTAGE, SERVICE GROUNDING AND FEEDERS. NEC | | | 215.5, 215.6. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-04-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-27 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-27 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-04-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-20 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-19 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2011-04-19 16:07:46 | INCOMING SENT TO ELECTRIC BOX. JW |
|
|
|