Plan Review Details - Permit 11040462
Plan Review Stops For Permit 11040462
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-15 Cont ID  
Sent By jgomez Date 2011-06-15 Time 16:12 Rev Time 0.00
Received By jgomez Date 2011-06-15 Time 16:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-15 Cont ID  
Sent By jgomez Date 2011-06-15 Time 10:55 Rev Time 0.00
Received By jgomez Date 2011-06-15 Time 10:55 Sent To  
Notes
2011-06-15 13:13:31RESIDENTIAL (R3) ALTERATION/REPAIR BUILDING REVIEW
 SECOND CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
  
 A) EXTERIOR DOORS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED AT ALL).
  
 B) HURRICANE SHUTTERS IF DOORS TO BE INSTALLED DON'T
 HAVE IMPACT GLASS. AND, CLEARLY MARK ON PRODUCT
 APPROVAL DRAWINGS SPECIFIC SHUTTERS MOUNTING CONDITIONS
 AND SPECIFIC ANCHOR TYPE AND SPACING TO BE USED. ALSO,
 PROVIDE A COMPLETE INSTALLATION SCHEDULE AS REQUIRED BY
 THE CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS
 IMPACT PROTECTION. (REPEAT COMMENT).
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-18 Cont ID  
Sent By jgomez Date 2011-05-18 Time 15:42 Rev Time 0.00
Received By jgomez Date 2011-05-18 Time 15:42 Sent To PC
Notes
2011-05-18 15:59:10RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. 2007
 FBC-EXISTING.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
  
 A) WINDOWS AS SPECIFIED ON PLANS.
  
 B) HURRICANE SHUTTERS IF WINDOWS AND DOORS TO BE
 INSTALLED DON'T HAVE IMPACT GLASS. AND, CLEARLY MARK ON
 PRODUCT APPROVAL DRAWINGS SPECIFIC SHUTTERS MOUNTING
 CONDITIONS AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED. ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY THE CITY IMPLEMENTATION STANDARD FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION.
  
 C) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- SHEET A-1:
 A) SPECIFY SAFETY GLASS ON WINDOW ADJACENT TO THE DOOR
 IN THE FAMILY ROOM AREA AND WINDOW BY THE BATH TUB
 AREA. SEC. R308.4.
  
 B) ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES FOR THE
 EXTERIOR DOORS ARE SO LOW. PROVIDE CALCULATIONS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
  
 C) ENGINEER TO SPECIFY THE BUILDING CONSTRUCTION TYPE
 ON THE CODE INFORMATION TABLE. THIS ITEM WAS LEFT BLANK
 ON DRAWING SUBMITTED. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 D) AREA CALCULATIONS TABLE INDICATES "ADDITION".
 ENGINEER TO CLARIFY WHERE IS THE ADDITION. CALCULATIONS
 SAYS EVERYTHING IS EXISTING. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By rlecky Date 2011-04-28 Time 12:01 Rev Time 0.00
Received By rlecky Date 2011-04-28 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-06-15 Cont ID  
Sent By jgomez Date 2011-06-15 Time 14:09 Rev Time 0.00
Received By jgomez Date 2011-06-15 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2011-05-11 Time 14:00 Sent To  
Notes
2011-05-24 14:19:21SUBMITTED SURVEYS SENT TO ZONING PREMATURELY ON THE
 11TH.
 SURVEYS REROUTED TO ZONING WITH COMPLETE APPLICATION
 PACKAGE 5/24.
  
  
 LM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-18 Cont ID  
Sent By jgomez Date 2011-05-18 Time 16:02 Rev Time 0.00
Received By jgomez Date 2011-04-19 Time 11:16 Sent To  
Notes
2011-04-19 11:16:50R7
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-18 Cont ID  
Sent By jgomez Date 2011-05-18 Time 16:03 Rev Time 0.00
Received By jgomez Date 2011-05-18 Time 16:03 Sent To  
Notes
2011-05-18 16:03:51PLUMBING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2011-06-03 Cont ID  
Sent By lfranco Date 2011-06-03 Time 11:17 Rev Time 0.50
Received By lfranco Date 2011-06-03 Time 11:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-05-06 Cont ID  
Sent By lfranco Date 2011-05-06 Time 15:59 Rev Time 0.00
Received By lfranco Date 2011-05-06 Time 15:59 Sent To  
Notes
2011-05-06 16:07:51PLANNING AND ZONING: **** FAILED *****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
 PROVIDE DIMENSIONS FROM STRUCTURE TO ALL PROPERTY
 LINES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]