Plan Review Details - Permit 11040457
Plan Review Stops For Permit 11040457
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-21 Cont ID  
Sent By rlecky Date 2011-04-21 Time 14:58 Rev Time 0.00
Received By rlecky Date 2011-04-21 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-04-19 Cont ID  
Sent By ddaniels Date 2011-04-19 Time 16:11 Rev Time 0.00
Received By ddaniels Date 2011-04-19 Time 16:09 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-21 Cont ID  
Sent By rlecky Date 2011-04-21 Time 14:58 Rev Time 0.00
Received By rlecky Date 2011-04-19 Time 08:31 Sent To  
Notes
2011-04-19 08:31:18TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-20 Cont ID  
Sent By hmoser Date 2011-04-20 Time 11:30 Rev Time 0.00
Received By hmoser Date 2011-04-20 Time 10:55 Sent To  
Notes
2011-04-20 11:45:56PASS PROVISO
 REFER TO SECTION 602.2.1 2007 FBC (M) DUCT DETECTORS .
 SHALL BE INSTALLED IN THE SUPPLY DUCT.
 REFER TO SECTION 606.3 INSTALLATION. 2007 FBC (M) THE
 REQUIRED DUCT DETECTOR SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIR FLOW CONVEYED BY THE SYSTEM.
 REFER TO NFPA 90-A ACCESS TO DUCT DETECTORS .ACCESS
 DOORS IN DUCT SHALL BE TIGHT FITTING AND SUITABLE
 FOR THE REQUIRED DUCT CONSTRUCTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  