| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2011-04-19 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-04-19 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-04-19 |
Time |
12:15 |
Sent To |
E |
|
| Notes |
| 2011-04-19 12:42:32 | 4215 UP THE GROVE LANE | | | PERMIT #11040389 | | | MASTER #10120325 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER LOCAL POLICY, DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM CONDITION. | | | | | | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE | | | INSTRUCTING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED, | | | LOCATE THE NEAREST EXIT AND EXIT THE BUILDING | | | IMMEDIATELY. | | | | | | ALL MANUAL PULL STATIONS ARE ASSIGNED IDENTICAL | | | ADDRESSES ON THE RISER DETAIL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|