Plan Review Details - Permit 11040302
Plan Review Stops For Permit 11040302
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-19 Cont ID  
Sent By jwitmer Date 2011-05-19 Time 15:54 Rev Time 0.77
Received By jwitmer Date 2011-05-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-10 Cont ID  
Sent By jwitmer Date 2011-05-10 Time 08:51 Rev Time 0.77
Received By jwitmer Date 2011-05-10 Time 08:50 Sent To  
Notes
2011-05-10 11:19:29BUILDING PLAN REVIEW
 PERMIT: 11040302
 ADD: 332 EVERNIA ST
 CONT: VILLA FRANCA
 TEL: (561)722-7588
 2007 / 09 FLORIDA BUILDING CODE W/ SUPPLEMENTS* WEST
 PALM BEACH ADMINISTATIVE AMENDMENTS CHAPTER 1
  
 2007/ 09 FLORIDA EXISTING BUILDING CODE
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
  
 1A) THE PLANS DO NOT INDICATE CLEARLY THE CODES THIS
 PROJECT WAS DESIGNED TOO, INCLUDING THE EXISTING
 BUILDING CODE, THIS IS A CHANGE OF OCCUPANCY FROM THE
 LAST KNOWN USAGE INCATING THE 2007/ 09 FLORIDA BUILDING
 CODE CHAPTER 9 CHANGE OF OCCUPANCY. PROVIDE TYPE OF
 OCCUPANCY.
  
  
  
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. WHERE THE
 OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE
 PROVISIONS OF SECTIONS 902 THROUGH 912 SHALL APPLY.
 THIS INCLUDES A CHANGE OF OCCUPANCY CLASSIFICATION
 WITHIN A GROUP AS WELL AS A CHANGE OF OCCUPANCY
 CLASSIFICATION FROM ONE GROUP TO A DIFFERENT GROUP.
  
 903.1 GENERAL. BUILDING ELEMENTS AND MATERIALS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.
  
 1B) 2007/09 EXISTING BUILDING CODE SECTION 906
 ACCESSIBILITY 906.1 GENERAL. ACCESSIBILITY IN PORTIONS
 OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING .
 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS
 THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 WHEN REMODELING A BUILDING THE ACCESSIBILITY CODE
 REQUIES AN ADDITIONAL 20% ( $65,000 X .20= $13,000.00)
 DISPROPORTIONATE COST TO BRING THE BUILDING UP TO THE
 CURRENT CODE FOR ACCESSIBILITY, 2007/09 FBC-B 11-4.1.6
 (2) INDICATES HOW THESE MONIES ARE TO BE SPENT SO THE
 BUILDING WILL MEET THE ACCESSIBILITY CODE THROUGH A
 SERIES OF ALTERATIONS.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
 (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
 (IV) ACCESSIBLE TELEPHONES;
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 PLEASE SEE THE ENTRANCE INDICATES A RAMP WITH NO BOTTOM
 LANDING. 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARENCE.
  
 1C) PLANS DO NOT PROVIDE DETAILS FOR THE BREAK ROOM
 SINK, SHALL COMPLY WITH:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 1D) THE PLANS DO NOT INDICATE WHAT YPE OF HARDWARE IS
 TO BE INSTALLED ON THE FRONT DOUBLE DOORS. PLEASE BE A
 WARE OF :
 1008.1.8.4 BOLT LOCKS. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE NOT PERMITTED. ALL HARDWARE MUST BE
 DIRECT ACTING REQUIRING NO MORE THAN ONE OPERATION.
 DOUBLE CYLINDER DEAD BOLTS, REQUIRING A KEY FOR
 OPERATION ON BOTH SIDES, ARE PROHIBITED ON REQUIRED
 MEANS OF EGRESS DOORS UNLESS THE LOCKING DEVICE IS
 PROVIDED WITH A KEY WHICH CANNOT BE REMOVED WHEN THE
 DOOR IS LOCKED FROM THE INSIDE. ONLY ONE LOCKING OR
 LATCHING DEVICE SHALL BE PERMITTED ON A DOOR OR ON ONE
 LEAF OF A PAIR OF DOORS.
  
 2) SHEET A-2.
  
 2A) 907.2 WIND LOADS. BUILDINGS AND STRUCTURES SUBJECT
 TO A CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE
 NATURE OF OCCUPANCY RESULTS IN HIGHER WIND IMPORTANCE
 FACTORS BASED ON THE FLORIDA BUILDING CODE, BUILDING
 TABLE 1604.5, (HIGH -VELOCITY HURRICANE ZONES SHALL
 COMPLY WITH TABLE 1615.2) SHALL BE ANALYZED AND SHALL
 COMPLY WITH THE APPLICABLE WIND LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING .
 NOTE NEW BUILDING ELEMENTS WINDOWS AND DOORS WILL NEED
 TO MEET TTHE WIND DESIGN CRITERIA OF FBC-B 1609,
 EXPOSURE "C" THE DESIGN PRESSURES
 WILL NEED TO REFLECT THE HEIGHT MULTIPLIERS FOR A "C"
 EXPOSURE, IT APPEAR THE PRESSURES ARE FOR A "B"
 EXPOSURE.
  
 2B) THE PLANS INDICATE A NEW FOORING AND KNEE WALL BUT
 DO NOT REFLECT INTO WHAT TYPE OF FRAMING THE TOP TRACK
 WILL ANCHOR. 2007/09 FBC-B
 1609 COMPONENTS AND CLADDING.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-23 Cont ID  
Sent By rlecky Date 2011-05-23 Time 15:08 Rev Time 0.00
Received By rlecky Date 2011-05-23 Time 15:08 Sent To  
Notes
2011-05-23 15:21:04FOR STAMPA

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-19 Cont ID  
Sent By rlecky Date 2011-04-19 Time 11:17 Rev Time 0.00
Received By rlecky Date 2011-04-19 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-05-19 Cont ID  
Sent By mcarsill Date 2011-05-19 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2011-05-19 Time 13:26 Sent To  
Notes
2011-05-19 13:38:55332 EVERNIA STREET
 PERMIT NUMBER 11040302
 "INTERIOR RENOVATIONS"
  
  
 1. REVISION CLOUD ON SHEET A-1 FOR HARDWARE NOTES IS
 INCORRECT AND MISLEADING. DOORS SUBJECT TO AN OCCUPANT
 LOAD OF 100 OR MORE MUST BE EQUIPPED WITH PANIC
 HARDWARE WITH NO OTHER LOCKS OR LATCHES. IN REVIEW OF
 SECTION 12.2.2.2.4 (2) NEW ASSEMBLY OCCUPANCIES "ANY
 LATCHING DEVICES ON SUCH DOORS FROM AN ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED BY PANIC HARDWARE OR FIRE EXIT HARDWARE". ON
 MAY 19, 2011, THIS WRITER SPOKE TO ARCHITECT JEFFREY
 GASPSTUR BY TELEPHONE REGARDING THIS MATTER.
  
 2. BATHROOM DOORS CANNOT SWING TOO FAR INTO EXIT ACCESS
 CORRIDOR. THIS INFORMATION WAS PREVIOUSLY PROVIDED BY
 THE FIRE PLAN REVIEWER.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-05-03 Cont ID  
Sent By wjolin Date 2011-05-03 Time 12:18 Rev Time 0.00
Received By wjolin Date 2011-05-03 Time 09:43 Sent To  
Notes
2011-05-03 10:14:47332 EVERNIA STREET
 PERMIT #11040302
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES NO CHANGE IN OCCUPANCY
 (ASSEMBLY). RECORDS INDICATE THIS LOCATION WAS
 PREVIOUSLY A FURNITURE STORE (MERCANTILE).
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 & NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 PROVIDE EXISTING EGRESS DOOR LOCK INFORMATION. NOTE: IF
 DOORS ARE EQUIPPED WITH A LATCH, ASSEMBLY OCCUPANCIES
 WITH AN OCCUPANT LOAD EXCEEDING 100 PERSONS SHALL HAVE
 EGRESS DOOR LATCHES RELEASED BY PANIC HARDWARE.
  
 THE LAVATORY DOORS OBSTRUCT THE CORRIDOR. DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL NOT LEAVE
 LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF A CORRIDOR
 UNOBSTRUCTED AND SHALL NOT PROJECT MORE THAN 7 INCHES
 INTO THE REQUIRED WIDTH OF A CORRIDOR WHEN THE DOOR IS
 FULLY OPEN.
  
 PROVIDE RAMP AND HANDRAIL DETAILS. RAMP IS REQUIRED TO
 HAVE A LANDING AT THE BOTTOM PER SECTION 7.2.5.3.2.1 OF
 THE FLORIDA FIRE PREVENTION CODE (NFPA 101). HANDRAILS
 ARE REQUIRED WITHIN 30 INCHES OF ALL PORTIONS OF RAMP
 EGRESS WIDTH.
  
 PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS HAVING EXIT
 SIGNS.
  
 POST BUILDING OCCUPANT LOAD NEAR FRONT ENTRANCE DESK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2011-04-28 Cont ID  
Sent By wjolin Date 2011-04-28 Time 10:53 Rev Time 0.00
Received By wjolin Date 2011-04-21 Time 12:40 Sent To  
Notes
2011-04-28 10:55:024/21 PLANS NOT LOCATED IN BOX C7; ONLY DOOR AND WINDOW
 INFORMATION. PLANS NOT REVIEWED. WJ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-23 Cont ID  
Sent By rlecky Date 2011-05-19 Time 15:21 Rev Time 0.00
Received By rlecky Date 2011-05-13 Time 16:22 Sent To  
Notes
2011-05-13 16:30:54**********************EXPEDITED***********************
 C--9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-11 Cont ID  
Sent By hmoser Date 2011-05-11 Time 08:52 Rev Time 0.00
Received By hmoser Date 2011-04-12 Time 09:18 Sent To  
Notes
2011-04-13 09:18:52C7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-05-26 Cont ID  
Sent By lmartine Date 2011-05-26 Time 17:47 Rev Time 0.00
Received By lmartine Date 2011-05-26 Time 17:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-05-10 Cont ID  
Sent By jwitmer Date 2011-05-10 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2011-05-10 Time 08:49 Sent To  
Notes
2011-05-10 08:50:12BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-05-11 Cont ID  
Sent By hmoser Date 2011-05-11 Time 08:51 Rev Time 0.00
Received By hmoser Date 2011-05-11 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-23 Cont ID  
Sent By lwagner Date 2011-05-23 Time 13:39 Rev Time 0.00
Received By lwagner Date 2011-05-23 Time 13:39 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-04-19 Cont ID  
Sent By lwagner Date 2011-04-19 Time 09:41 Rev Time 0.00
Received By lwagner Date 2011-04-19 Time 09:23 Sent To  
Notes
2011-04-19 09:39:08FBC PLUMBING 2007 REVIEW #1
 DENNIED:
  
 1. FBC 106.3.5.1.3 PLUMBING MINIMUM REVIEW CRITERIA-
 HOT AND COLD WATER DIAGRAM AND WATER HEATER REQUIRED ON
 PLAN.
  
 2. DRINKING FOUNTAINS ARE NOT SHOWN ON RISER DIAGRAM.
  
 3. THE WATER CLOSET SHOWN ATTACHED TO THE BUILDING
 DRAIN IS NOT VENTED.
  
 4. 1002.4 TRAP PRIMERS ARE REQUIRED FOR FLOOR DRAINS.
  
 **** NOTE ****
 PLUMBING NOTE #7 AIR CHAMBERS ARE NO LONGER PART OF
 PLUMBING CODE. WATER HAMMER ARRESTORS ARE TO BE
 INSTALLED WHERE REQUIRED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By aaponte Date 2011-04-28 Time 15:45 Rev Time 0.50
Received By aaponte Date 2011-04-28 Time 15:44 Sent To  
Notes
2011-04-28 15:45:58PROVISO: PLANT MATERIAL ON PLANTER ALONG FRONTAGE SHALL
 BE RESTORED AND IRRIGATION SHALL BE FUNCTIONAL.