Plan Review Details - Permit 11040299
Plan Review Stops For Permit 11040299
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-07-26 Cont ID  
Sent By jwitmer Date 2011-07-26 Time 09:58 Rev Time 0.55
Received By jwitmer Date 2011-07-26 Time 09:58 Sent To  
Notes
2011-07-26 10:02:32BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 1A) ROOFING APPROVALS BOTH FLAT AND SLOPED TILE
  
 ROOFING ZONE POSITIVE // NEGATIVE
  
 ROOF ZONE 1 19.015 -46.744
 ROOF ZONE 2 19.015 -78.435
 ROOF ZONE 3 19.015 -118.049
 WALL ZONE 5
 DOORS 40.754 -52.986
 WALL ZONE 4
 WINDOW 24 SF 40.389 -43.954
 WALL ZONE 5
 WINDOW 24 SF 40.389 -52.256
 WALL ZONE 4
 WINDOW 10 SF 42.675 -46.241
 WALL ZONE 5
 WINDOW 10 S F 42.675 -56.829
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-14 Cont ID  
Sent By jwitmer Date 2011-06-14 Time 13:50 Rev Time 2.20
Received By jwitmer Date 2011-06-14 Time 12:04 Sent To  
Notes
2011-06-14 13:14:23 
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 1A) ROOFING APPROVALS BOTH FLAT AND SLOPED TILE
  
 ROOFING ZONE POSITIVE // NEGATIVE
  
 ROOF ZONE 1 19.015 -46.744
 ROOF ZONE 2 19.015 -78.435
 ROOF ZONE 3 19.015 -118.049
 WALL ZONE 5
 DOORS 40.754 -52.986
 WALL ZONE 4
 WINDOW 24 SF 40.389 -43.954
 WALL ZONE 5
 WINDOW 24 SF 40.389 -52.256
 WALL ZONE 4
 WINDOW 10 SF 42.675 -46.241
 WALL ZONE 5
 WINDOW 10 S F 42.675 -56.829
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-20 Cont ID  
Sent By jwitmer Date 2011-04-20 Time 12:23 Rev Time 4.00
Received By jwitmer Date 2011-04-19 Time 08:08 Sent To  
Notes
2011-04-20 12:16:09BUILDING PLAN REVIEW
 PERMIT: 11040299
 ADD: 2431 S DIXIE HWY
 CONT: TBD
 TEL: (954)557-1300
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A102:
 1A) DOOR # 4 VERSES THE DRINKING FOUNTAIN. THE OUT
 SWING OF DOOR # 4 DOES NOT HAVE THE REQUIRED 18 INCHES
 ON THE LATCH SIDE. PLEASE REVIEW 11-4.13.6.
  
 1B) THE SECOND ISSUE WITH DOORWAYS BOTH DOORWAYS 5 &6
 ARE ILLUSTRATERD AS A PAIR OF DOUBLE DOORS. THE DOOR
 SCHEDULEFOR DOOR # 5 INDICATES A 3'-0" DOOR NOT A PAIR
 OF DOORS.
  
 1C) THE DOOR SCHEDULE ALSO DOESN'T INDICATE TYPE OF
 HARDWARE, PLEASE INDICATE COMPLIANCE WITH 11-4.13.4.
  
 1D) DOOR # 5 VERSES THE DRINKING FOUNTAIN MAY BECOME
 MORE OF AN ISSUE IF IT IS MOVED DOWN TTHE WALL TO
 COMPLY WITH DOOR # 4.
  
 2) DOOR # 1 & 17, WILL BE RAISED APPROXIMATELY ONE FOOT
 WITH THE NEW FLOOR LEVEL. I DIDN'T SEE ANY CUT SECTIONS
 THROUGH THE PLANS INDICATING HOW THE NEW ELEVATIONS ARE
 GOING TO EFFECT THE EXISTING LINTELS AND OR BEAM. SHEET
 S-3 DETAIL # 1 DOES HAVE A NOTE TO VEREIFY EXISTING
 BEAM CONDITION.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A) WINDOWS FIXED GLASS
 3B) EXTERIO DOORS
 3C)ROOFING APPROVALS BOTH FLAT AND TILE
 3D) ROOF TOP EXHAUST FANS
  
 PLANS SUBMITTED ARE TO BE DETERMINED, SINCE THE
 PRESSURES ON THE BUILDING ARE CORRECT THIS PERMIT CAN
 BE ISSUED WITH THE PRODUCT APPROVALS COMING IN AT A
 LATER DATE AFTER ISSUANCE. NOTE IN DOING SO THIS WILL
 CONSTITUTE A REVISION REQUIRING SEPERATE REVIEWS AND
 ASSOCIATED FEES!!! FOR EACH PRODUCT APPROVAL TO BE
 SUBMITTED. PLEASE NOTE IN MANY CASES THERE ARE WITHIN
 THE PRODUCT APPROVAL THERE ARE EITHER SUB-SYSTEMS OR
 DIFFERENT TYPES OF GLAZING WITH DIFFERENT PRESSURES,
 PLEASE CIRCLE WHICH SYSTEM TO BE INSTALLED UNDER THIS
 PERMIT.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) AT THE REAR OF THE BUILDING THERE IS A DOWN SPOUT
 NEAR DOOR # 17, THIS DOWN SPOUT IS ALSO LOCATED ON A105
 PLEASE PROVIDE WHERE THIS DOWN SPOUT IS GOING TO DRAIN.
 2007 FBC-B 1503.6.
  
 6) SHEET A104 THE PLANS HAVE A STATEMENT THAT THE
 ROOFING INSULATION SHALL BE RIGID INSULATION A AVERAGE
 R-20.
 INFORMAL BOAF INTERPRETATION
 DATE: TUE NOV 13 2007
 REPORT #: 5438
 CODE: BUILDING
 SECTION: 404.1.A
 QUESTION:
 IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL
 HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO
 MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19
 AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE
 SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE
 R-19,
 NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB
 ACCORDINGLY. THANK YOU
 ANSWER:
 A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, A
 MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE MINIMUM
 R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING
 PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF
 THE VALUE.
 COMMENTARY:
 THIS QUESTION ACTUALLY REFERS TO SECTION 13-404.1 (A)
 PRESCRIPTIVE REQUIREMENTS SPECIFIC TO METHOD A. THIS
 SECTION MANDATES COMPLIANCE WITH FLA/COM METHOD A,
 HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF AN R-19 FOR
 MULTIFAMILY RESIDENTIAL ROOF/CEILING ASSEMBLY. AS SPACE
 PERMITS, MAY RELATE TO THE AREA OF THE EAVES WHERE THE
 R- 19 INSULATION WOULD HAVE TO BE COMPRESSED TO FIT IN
 THE SPACE AVAILABLE. HOWEVER, THE PETITIONER ALLUDES TO
 THE ROOFER INSTALLING THE INSULATION. THERE ARE NO
 SPACE CONSTRAINTS FOR INSULATION APPLIED TO A ROOF
 DECK; IT SHOULD BE R-19 MINIMUM. IF THE BUILT-UP ROOF
 IS SLOPING TO A DRAIN IN A MANNER WHERE SOME PARTS OF
 THE ROOF HAVE MORE THAN R-19 AND SOME HAVE LESS, THEN
 THE RESIDENT WHOSE APARTMENT/CONDO IS UNDER THE ROOF
 SECTION WITH LESS THAN R- 19 WOULD BE PENALIZED WITH
 HIGHER HEAT LOADS AND HIGHER ENERGY COSTS THAN THEIR
 NEIGHBOR.
  
 7) SHEET A104 & A104A BOTH INDICATE NEW ROOF TOP A/C
 CURBS BUT THE PLANS DO NOT INDICATE HOW THEY ARE TO BE
 ATTACHED TO THE ROOF FRAMING (BAR JOIST SYSTEM? NO
 INFORMATION IS PROVIDED FOR THIS DETAIL IN TTHE
 STRUCTURAL PLANS EITHER.
  
 8) PLANS ARE NOT CLEAR AS TO THE EXTERIOR WALLS AND
 TYPE OF INSULATION TO BE USED AND WHAT POINT THE
 INSULATION WILL END IN RELATION TO THE ROOFING
 ASSEMBLY? FBC-B 2603.4 & FBC-M 602.1.5.1.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-06-22 Cont ID  
Sent By rlecky Date 2011-06-22 Time 13:13 Rev Time 0.00
Received By rlecky Date 2011-06-22 Time 13:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-25 Cont ID  
Sent By rlecky Date 2011-04-25 Time 11:47 Rev Time 0.00
Received By rlecky Date 2011-04-25 Time 10:23 Sent To  
Notes
2011-04-25 11:28:14NOTE:
  
 A SEPERATE ELECTRIC PERMIT IS REQUIRED FOR DATA AND
 PHONES.
 A SEPERATE ELECTRIC PERMIT IS REQUIRED FOR SECURITY
 A SEPERATE ELECTRIC PERMIT IS REQUIRED FOR SITE
 LIGHTING.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-07-12 Cont ID  
Sent By mgonzale Date 2011-07-12 Time   Rev Time 1.00
Received By mgonzale Date 2011-07-12 Time   Sent To  
Notes
2011-07-12 09:29:18PASSED
  
 CIVIL SUBMITTAL IS ACCEPTABLE.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-05-09 Cont ID  
Sent By mgonzale Date 2011-05-09 Time   Rev Time 2.00
Received By mgonzale Date 2011-05-09 Time   Sent To  
Notes
2011-05-09 17:16:23FAILED:
 YOUR PAVING AND DRAINGE PLAN IS DEFFICIENT AND A
 SEPARATE SUBMITTAL WILL NEED TO BE MADE DIRECTLY TO
 ENGINEERING SERVICES DEPARTMENT.
 GO TO
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 GO TO
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/UPLOADS/2010-10-20
 -16-37-34-DEVELOPMENTPERMITPACKAGE2011.PDF
 PRINT AND SUBMIT:
 #1 DEVELOPMENT APPLICATION COVER
 #2 STANDARD APPLICATION FOR DEVELOPMENT PERMIT FORM
 ALONG WITH
 1. ENGINEERING PLANS - SIX (6) SETS OF SIGNED AND
 SEALED PLANS IN THE ORDER LISTED BELOW, ALONG WITH A
 LETTER DESCRIBING THE SUBMITTAL.
 A. COVER SHEET
 B. PAVING, GRADING, AND DRAINAGE PLANS
 C. PAVING, GRADING, AND DRAINAGE DETAILS
 F. OFFSITE IMPROVEMENTS (DRIVEWAY APRONS, SIDEWALKS,
 SERVICE RELOCATION/MODIFICATIONS, ETC)
 G. STORMWATER POLLUTION PROTECTION PLAN
 2. DRAINAGE CALCULATIONS - 2 COPIES SIGNED AND SEALED
 (INCLUDE SURFACE WATER MANAGEMENT CALCULATIONS IN ACRES
 AND S.F.)
 A.IDENTIFY LOCATION ON OUTFALL OR CITY CONNECTION. IF
 NOT IN USE CITY WILL HAVE DEVELOPER/OWNER CAP AND
 ELIMINATE SUCH SERVICE.
 3. ENGINEER'S COST ESTIMATE.
  
 TO: ENGINEERING SERVICES DEPARTMENT
 ATTENTION: MR. BRIAN MOREE,
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
  
 SITE SPECIFIC COMMENTS:
  
 #1 EXISTING DRAINAGE WILL CONFLICT WITH NEW FOUNDATION.
 COMPARE C-1 AND S-3.
  
 #2 SITE DESIGN MUST RETAIN 1ST INCH OF RAINFALL BEFORE
 DISCHARGE AT A CONTROL ELEVATION.
  
 #3 SITE DOMESTIC WATER METER WILL REQUIRE A BACKFLOW.
 SITE POSES A CHALLENGE AS THE DOMESTIC METER GOES
 DIRECTLY INTO NORTH BUILDING WALL WITH NO GREEN AREA. A
 NEW TAP LOCATED WHERE BACKFLOW WILL BE JUST INSIDE THE
 PROPERTY FOLLOWING THE CITY METER MAY BE NEEDED.
  
 #4 SITE PAVING AND DRAINAGE DESIGN WILL NEED SPOT
 ELEVATION OF EXISTING AND PROPOSED SO THAT WATER IS
 RETAINED ON-SITE PRIOR TO DISCHARGE.
  
 #5 ANY PROPOSED STRUCTURE OR CATCH BASIN TOP MUST BE
 SHOWN IN DETAIL.
  
 #6 EXISTING 8" CAST IRON PIPE WILL BE ALLOWED IF
 CLEAN-OUTS AREA PROVIDED AT BENDS AND IF RE-ROUTED FROM
 UNDER THE BUILDING.
  
 #7 PROVIDE SIGNED AND SEALED DRAINAGE CALCULATIONS
 SUMMARY.
  
 #8 C-1 TRENCH DRAIN SHOWN ON SHEET C-1 CAN BE REMOVED
 IF LOCATED ON PRIVATE PROPERTY; OTHERWISE YOU WILL NEED
 AN FDOT UTILITY PERMIT TO REMOVE AND/OR MODIFY.
  
 #9 FLOOR PLAN PLUMBING PLAN P-1 SHOWS THE SEWER COMING
 OUT THE NORTH WALL, ASBUILTS IN OUR OFFICE REFLECT A
 SEWER LATERAL OFF S DIXIE HWY. (FIELD VERIFY).
  
 #10 SHOW CONNECTION OF ROOF DRAIN INTO STORM. ON THE
 PLANS IT DOES NOT CONNECT TO ANYTHING.
  
 # 11 PARKING LOT LAY-OUT DESIGN SHALL BE IN ACCORDANCE
 WITH THE ZONING ORDINANCE. PARKING STALLS AND AISLE
 DIMENSIONS MUST BE SHOWN ON DEVELOPMENT PLANS. ALL
 PARKING LOTS REGARDLESS OF SIZE SHALL PROVIDE FOR
 PROPER DRAINAGE. THE MINIMUM LONGITUDINAL GRADIENT
 (SLOPE) SHALL BE 0.4 PER CENT IN BOTH DIRECTIONS. ALL
 RUNOFF SHALL BE COLLECTED ON SITE, FOR PROVISIONS OF
 WATER QUALITY AND QUANTITY CONTROL, PRIOR TO DISCHARGE
 TO THE CITY'S DRAINAGE FACILITIES.
  
 # 12 WATER QUALITY RETENTION VOLUME CALCULATION:
 RETENTION OF THE 1ST INCH OVER THE PROJECT AREA OR 2.5
 TIMES THE PERCENTAGE OF IMPERVIOUS AREA WILL NEED TO BE
 DOCUMENTED FOR WATER QUALITY PURPOSES.
  
 # 13 REVISE SHEET C-1 NOTES CALL OUT CITY OF MIAMI
 BEACH PUBLIC WORKS (NOTE 10) AND IT REFERENCES CITY OF
 WPB PUBLIC WORKS MANUAL. (NO SUCH THING) REFERE TO
 ENGINEERING SERVICES DEPARTMENT STANDARDS.
  
 *******************************************************
 **********
 GENERAL COMMENTS:
 EXISTING DEVELOPMENTS THAT PROPOSE ADDITIONAL
 STRUCTURES AND/OR PARKING FACILITIES FOR APPROVAL MUST
 PROVIDE STORMWATER MANAGEMENT AS REQUIRED ABOVE FOR THE
 NEW FACILITIES ONLY. HOWEVER, IT WILL BE THE
 RESPONSIBILITY AND A REQUIREMENT OF THE DEVELOPER'S
 ENGINEER TO DETERMINE AND CERTIFY THAT PROPOSED AND
 EXISTING FACILITIES TOGETHER WILL NOT ADVERSELY AFFECT
 THE SITE DRAINAGE, STATE AND/OR FEDERAL REGULATIONS AS
 A WHOLE OR THE EXISTING AND FUTURE WATER QUALITY
 RESULTING FROM ANY INCREASES TO THE EXISTING IMPERVIOUS
 AREAS OF THE SITE.
  
 EXISTING BUILDINGS WHICH HAVE PLUMBING DRAIN OUTLETS AT
 AN ELEVATION 12? OR LESS ABOVE THE GROUND SURFACE OF
 THE NEXT UPSTREAM MANHOLE, WHERE THE ELEVATION OF ANY
 FLOOR IS AT OR BELOW THE INVERT OF THE ADJACENT CITY
 SANITARY SEWER MAIN OR
 IS LESS THAN 12?ABOVE THE GROUND SURFACE OF THE NEXT
 UPSTREAM MANHOLE, OR WHERE A CONDITION EXISTS WHERE A
 PLUG IN THE CITY SANITARY SEWER MAIN WILL CAUSE THE
 HYDRAULIC GRADIENT TO RISE ABOVE THE LOWEST FLOOR
 LEVEL.
  
 CITY ORDINANCE 3132-98, SECTION 32-18(A): "...IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY
 DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE
 PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM
 WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED
 ENTIRELY OF STORM WATER." AND, SECTION 32-18(C): "NO
 PERSON MAY MAINTAIN, USE OR ESTABLISH ANY DIRECT OR
 INDIRECT CONNECTION TO THE STORM WATER SYSTEM THAT
 RESULTS IN ANY DISCHARGE IN VIOLATION OF THIS
 ORDINANCE. THIS PROHIBITION IS RETROACTIVE AND APPLIES
 TO CONNECTIONS MADE IN THE PAST, REGARDLESS OF WHETHER
 MADE UNDER A PERMIT, OR OTHER AUTHORIZATION, OR WHETHER
 PERMISSIBLE UNDER LAWS OR PRACTICES APPLICABLE OR
 PREVAILING AT THE TIME THE CONNECTION WAS MADE."
  
 EXFILTRATION TRENCHES ARE DISCOURAGED BECAUSE THE
 EXFILTRATION THAT THEY PROVIDE ARE FOUND TO DECREASE
 WITH AGE, IF THEY ARE NOT PROPERLY MAINTAINED OR
 REPLACED WHEN THEY DO NOT PROVIDE THE SERVICES INTENDED
 BY THE DESIGN. HOWEVER, IF THE DEVELOPER'S ENGINEER,
 DEVELOPER AND/OR OWNER DETERMINES THAT EXFILTRATION
 TRENCHES ARE TO BE PROVIDED FOR WATER QUALITY OR
 QUANTITY, THEIR DESIGN MUST CONFORM TO THE METHODOLOGY
 OF SFWMD. SITE'S HYDRAULIC CONDUCTIVITY TEST REPORTS AT
 THE LOCATION OF THE PROPOSED TRENCH SHALL BE SUBMITTED
 TO THE CITY ENGINEER TOGETHER WITH THE CALCULATIONS;
 SITE DEVELOPMENTS THAT USE EXFILTRATION TRENCHES FOR
 BOTH, WATER QUALITY AND QUANTITY WITHOUT OVERFLOW
 CAPABILITIES MUST PROVIDE ENOUGH TRENCH CAPACITY TO
 HANDLE THE DIFFERENCE BETWEEN THE POST-DEVELOPMENT AND
 PRE-DEVELOPMENT RUNOFF.
  
 CHAPTER 62.302, F.A.C. EFFECTIVELY STATES THAT THE SITE
 IS NOT ALLOWED TO DISCHARGE ANY QUANTITY OF WATER THAT
 VIOLATES STATE WATER QUALITY STANDARDS. CITY ORDINANCE
 3132-98, SECTION 32-18(A) STATES THAT IT IS A VIOLATION
 TO DISCHARGE ANYTHING EXCEPT STORM WATER INTO THE
 CITY'S MS4. THE CITY HAS THE AUTHORITY AND OBLIGATION
 TO ENFORCE THESE RESTRICTIONS. IF THE APPLICANT'S
 PROPOSED SYSTEM IS NOT PROVIDING SUFFICIENT WATER
 QUALITY TREATMENT (SO THAT ANY DISCHARGE IS FREE OF ALL
 BUT STORM WATER RUN-OFF), THEN APPLICANT MUST RE-DESIGN
 THE SYSTEM.
  
 *******************************************************
 **********
 MANUEL JULIAN GONZALEZ
 CONSTRUCTION SERVICE DEPARTMENT ENGINEERING REVIEW
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-06-27 Cont ID  
Sent By wjolin Date 2011-06-27 Time 09:55 Rev Time 0.00
Received By wjolin Date 2011-06-27 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-21 Cont ID  
Sent By wjolin Date 2011-04-21 Time 11:55 Rev Time 0.00
Received By wjolin Date 2011-04-21 Time 10:24 Sent To  
Notes
2011-04-21 10:35:032431 SOUTH DIXIE HIGHWAY
 PERMIT #11040299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 COVER SHEET POST NUMERICAL ADDRESS ON THE BUILDING.
 NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND PER SECTION 10.12.1.2 OF
 NFPA 1 FLORIDA EDITION.
  
 SHEET A100 A CURB OR BARRIER SHALL BE PROVIDED THAT
 PREVENTS THE PASSAGE OF A 4 INCH DIAMETER SPHERE WHERE
 ANY PORTION OF THE SPHERE IS WITHIN 4 INCHES OF THE
 FLOOR OR GROUND SURFACE PER SECTION 7.2.5.4.1.2 OF NFPA
 101 FLORIDA EDITION.
  
 SHEET A101 DEMOLITION WORK SHALL COMPLY WITH NFPA 241.
  
 SHEET A102
 PROVIDE LIFE SAFETY PLAN INDICATING TRAVEL DISTANCES,
 FIRE EXTINGUISHERS ETC. EXTINGUISHERS SHALL HAVE A
 MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A
 LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO
 EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 38.3.2.1 (FFPC) THE STORAGE ROOM IS
 REQUIRED TO BE PROTECTED WITH A ONE HOUR FIRE RATED
 BARRIER WITHOUT WINDOWS OR AN AUTOMATIC SPRINKLER
 SYSTEM. DOORS WILL BE REQUIRED TO BE FIRE RATED AND
 SELF CLOSING.
  
 INDICATE WHAT TYPE OF MATERIALS, MEDICAL GAS CYLINDERS,
 ETC. WILL BE STORED IN THE STORAGE ROOM.
  
 PROVIDE STAIR DETAILS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2011-07-22 Time 10:51 Sent To  
Notes
2011-07-22 10:51:44C2
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-30 Cont ID  
Sent By lmartine Date 2011-06-30 Time 09:01 Rev Time 0.00
Received By lmartine Date 2011-06-08 Time 16:44 Sent To  
Notes
2011-06-08 16:44:57C2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-13 Cont ID  
Sent By lmartine Date 2011-05-09 Time 09:59 Rev Time 0.00
Received By lmartine Date 2011-04-12 Time 09:28 Sent To  
Notes
2011-04-13 09:28:38C2

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2011-07-25 Cont ID  
Sent By eschneid Date 2011-07-25 Time 14:10 Rev Time 0.00
Received By eschneid Date 2011-07-25 Time 14:10 Sent To  
Notes
2011-07-25 14:11:21LANDSCAPE PERMIT NO. 11070489

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2011-06-21 Cont ID  
Sent By rkussner Date 2011-06-21 Time 16:31 Rev Time 0.00
Received By rkussner Date 2011-06-21 Time 16:31 Sent To  
Notes
2011-06-21 17:04:55***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE
 PERMIT. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT
 TWO COPIES OF THE SIGNED AND SEALED LANDSCAPE PLAN.
 PLEASE INCLUDE A CERTIFIED COST ESTIMATE THAT INCLUDES
 THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR,
 BROKEN DOWN INTO UNIT COST.
  
 2 REPEAT COMMENT: . PLEASE APPLY FOR AN IRRIGATION
 PERMIT AND SUBMIT TWO SETS OF IRRIGATION PLANS.
  
 3. REPEAT COMMENT: PLEASE DEMONSTRATE (IN TABULAR FORM)
 HOW YOU COMPLY WITH THE XERISCAPE REQUIREMENTS.
  
 4. THE USE OF CAR AND CURBING AT THE HEAD OF THE
 PARKING STALLS IS NOT REQUIRED. IF CAR STOPS ARE USED
 THE CURB CAN BE DELETED. IF THE CURB IS USED, CAR STOPS
 ARE NOT REQUIRED AND THE LENGTH OF THE PARKING STALLS
 CAN BE SHORTENED BY TWO FEET WITH THE OVERHANG AREA
 OVER A GREEN SPACE. IF THE VEHICLES OVERHANG INTO A
 GREEN AREA, NO SHRUBS, STREET LIGHTS OR OTHER ITEMS CAN
 BE WITHIN THE OVERHANG AREA EXCEPT FOR MULCH OR SOD.
  
 5. PURSUANT TO SECTION 94-444 (B), GARBAGE OR TRASH
 RECEPTACLES AND MECHANICAL EQUIPMENT SHALL NOT BE
 PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 PLEASE PROVIDE THE LOCATION OF YOUR GARBAGE AREA AND
 OTHER MECHANICAL EQUIPMENT AND THE MANNER IN WHICH
 THESE ITEMS WILL BE SCREENED.
  
 IF YOU HAVE ANY QUESTIONS OR WOULD LIKE TO DISCUSS THE
 COMMENTS, PLEASE CONTACT ROBERT KUSSNER @ (5610
 822-1462.
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-05-02 Cont ID  
Sent By rkussner Date 2011-05-02 Time 14:07 Rev Time 0.00
Received By rkussner Date 2011-05-02 Time 14:06 Sent To  
Notes
2011-05-02 17:26:24***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE APPLY
 FOR A LANDSCAPE PERMIT AND SUBMIT TWO COPIES OF THE
 SIGNED AND SEALED LANDSCAPE PLAN. PLEASE INCLUDE A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIRALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. PURSUANT TO SECTION 94-443 (C) (5) (A) LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NON-MOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS "TYPE D".
  
 3. PLEASE APPLY FOR AN IRRIGATION PERMIT AND SUBMIT TWO
 SETS OF IRRIGATION PLANS.
  
 4. PLEASE DEMONSTATE (IN TABULAR FORM) HOW YOU COMPLY
 WITH THE XERISCAPE REQUIREMENTS.
  
 5. PURSUANT TO SECTION 94-442 (B) (2) (B) (1), AT LEAST
 ONE SHADE TREE SHALL BE PLANTED FOR EACH 1,600 SQUARE
 FEET OF OPEN SPACE OR PROTION THEREOF. AT LEAST ONE
 FLOWERING TREE SHALL BE PLANTED FOR EACH 6,400 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF. THE OPEN SPACE
 IS CALCULATED BY TAKING 40% OF THE TOTAL LOT AREA,
 WHICH IN THIS CASE COMES TO 4,737 SQUARE FEET. THAT
 REQUIRES THREE SHADE TREES AND ONE FLOWERING TREE. THE
 CALCULATIONS PROVIDED ARE INCORRECT.
  
 6. PURSUANT TO SECTION 94-443 (C) (2), A HEDGE SHALL BE
 PLANTED ALONG THE INSIDE PERIMETER OF THE LANDSCAPE
 BUFFER, ADJJACENT TO DIXIE HIGHWAY.
  
 7. ALL PLANS SHALL BE CONSISTANT. THE HANDICAP
 MANEUVERING AREA/RAMP IS SHOWN DIFFERENTLY ON THE SITE
 PLAN AS COMPARED TO THE LANDSCAPE PLAN.
  
 8. THE DRIVE AISLE IN THE LOCATION WHERE IT TUNS TO THE
 SOUTH SHALL BE MODIFIED. THE LANDSCAPE AREA ON THE
 NORTH SIDE SHALL BE EXPANDED TO FOLLOW THE TURN RADIUS
 ON THE SOUTH SIDE. AN ADDITIONAL TREE SHALL BE PLANTED
 IN THAT EXPANDED LANDSCAPE AREA WITHIN THE LANDSCAPE
 STRIP.
  
 9. THE EXISITNG HEDGE ALONG THE WEST PERIMETER APPEARS
 TO BE ON THE NEIGHBORING PROPERTY. PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS OR WOULD LIKE TO DISCUSS THE
 COMMENTS, PLEASE CONTACT ROBERT KUSSNER @ (5610
 822-1462.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-06-29 Cont ID  
Sent By hmoser Date 2011-06-29 Time 08:41 Rev Time 0.00
Received By hmoser Date 2011-06-29 Time 07:00 Sent To  
Notes
2011-06-29 08:51:54PASS PROVISO
 PROVIDE A LETTER FROM THE ENGINEER FOR THE TIE DOWN OF
 THE CURB TO THE ROOF
 AT THE FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-26 Cont ID  
Sent By hmoser Date 2011-04-26 Time 16:10 Rev Time 0.00
Received By hmoser Date 2011-04-26 Time 13:08 Sent To  
Notes
2011-04-26 16:13:59PASS PROVISO
 PROVIDE A LETTER FROM THE ENGINEER ON THE TIE DOWN OF
 THE A/C CURB TO THE ROOF
 SECTION 301.12 FBC (M) 2007
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-06-20 Cont ID  
Sent By lwagner Date 2011-06-20 Time 11:25 Rev Time 0.00
Received By lwagner Date 2011-06-20 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-18 Cont ID  
Sent By lwagner Date 2011-04-18 Time 13:16 Rev Time 0.00
Received By lwagner Date 2011-04-15 Time 13:26 Sent To  
Notes
2011-04-18 10:28:51*****PROVISO******
  
 1.SEPARATE MED GAS APPLICATION, PERMIT, AND FEES
 REQUIRED
  
 2. 713.7 CENTRAL VACUUM OR DISPOSAL SYSTEMS. WHERE THE
 WASTE FROM A CENTRAL VACUUM (FLUID SUCTION) SYSTEM OF
 THE BAROMETRIC-LAG, COLLECTION-TANK OR BOTTLE-DISPOSAL
 TYPE IS CONNECTED TO THE DRAINAGE SYSTEM, THE WASTE
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM THROUGH A TRAPPED WASTE.
  
 3. 301.12 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 ROOF MOUNTED MECHANICAL UNITS AND SUPPORTS SHALL BE
 SECURED TO THE STRUCTURE. THE USE OF WOOD "SLEEPERS"
 SHALL NOT BE PERMITTED.
  
 4.307.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL
 COOLING COILS AND EVAPORATORS SHALL BE CONVEYED FROM
 THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL.
 CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-07-25 Cont ID  
Sent By eschneid Date 2011-07-25 Time 13:02 Rev Time 1.25
Received By eschneid Date 2011-07-25 Time 13:02 Sent To  
Notes
2011-07-25 14:10:13SEPARATE PERMITS REQUIRED FOR AWNING AND SIGNS.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2011-06-17 Cont ID  
Sent By eschneid Date 2011-06-10 Time 14:20 Rev Time 2.00
Received By eschneid Date 2011-06-10 Time 14:20 Sent To  
Notes
2011-06-10 15:15:22FAILED
  
 PLEASE RESPOND IN WRITING. NOTE THAT ADDITIONAL
 COMMENTS MAY BE GENERATED WHEN PLANS ARE REVISED.
  
 1 ) REPEAT COMMENT - PLEASE SEE THE LIST BELOW FOR
 SEPARATE PERMITS REQUIRED. THE SITE WORK/PARKING PERMIT
 AND THE LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR TO
 ZONING APPROVAL OF THIS PERMIT.
  
 A. SITE WORK INCLUDING PARKING LOT STRIPING PERMIT. -
 NOTE THE FOLLOWING ITEMS WHICH ARE STILL SHOWN
 INCORRECTLY - STRIPING DETAIL FOR THE PARKING SPACES
 (THE STRIPES ARE TO BE 12 INCHES APART). PLEASE CONTACT
 ZONING FOR A COPY OF THE STANDARD CITY DETAIL.
  
 B. LANDSCAPE PERMIT. HEDGE MATERIAL SHALL BE PROVIDED
 ON THE EAST SIDE OF THE TRASH ENCLOSURE.
  
 C. AWNING PERMIT. THE PERMIT SHALL INCLUDE DETAILS OF
 THE PROPOSED CANVAS CANOPY.
  
 D. SIGN PERMIT. ALL NEW EXTERIOR SIGNAGE.
  
 E. IRRIGATION.
  
 F. WALL. THE TRASH CAN ENCLOSURE SHALL HAVE AN OPAQUE
 GATE. PLEASE PROVIDE A COPY OF THE SANITATION APPROVAL
 OF THE USE OF TRASH CANS AS PART OF THE RESUBMITTAL.
 (THE LETTER FROM THE SANITATION DEPARTMENT IS REQUIRED
 PRIOR TO ZONING APPROVAL OF THIS PERMIT).
  
 2) PARKING AISLE WIDTH IS REQUIRED TO BE 18 FEET FOR 60
 DEGREE PARKING. THE LANDSCAPE AND CIVIL PLANS SHOW THE
 WIDTH AT 17.5 FEET.
  
 3) THE PLANS SHOW D-CURBING TO PROTECT THE LANDSCAPE AT
 THE HEAD OF THE PARKING SPACES. IF THIS IS THE CASE,
 THEN THE SPACE SHALL MEASURE 16 FEET DEEP AND NO WHEEL
 STOPS SHALL BE PROVIDED. THIS IS DONE TO PROVIDE EXTRA
 LANDSCAPE AREA. PLEASE CONTACT ZONING FOR A COPY OF THE
 STANDARD CITY DETAIL.
  
 4) REPEAT COMMENT - THE BUILDING SITS ON THE PROPERTY
 LINE SO ANY FACADE APPLICATIONS WILL ENCROACH THE
 RIGHT-OF-WAY; THEREFORE, PROVIDE A LETTER FROM FDOT
 APPROVING THE MOLDING WHICH OVERHANGS SOUTH DIXIE
 HIGHWAY AND FROM THE CITY'S ENGINEERING SERVICES
 DEPARTMENT FOR THE MOLDING WHICH OVERHANGS SUNSET ROAD.
  
 5) THE CITY DOES NOT PERMIT THE WAVE BICYCLE RACK AS
 SHOWN. PLEASE PROVIDE A DIFFERENT TYPE SUCH AS AN
 INVERTED U, AN A, OR A POST AND LOOP STYLE.
 ADDITIONALLY, THE PAD IS SIZED FOR 2 BICYCLE RACKS. IF
 ONLY ONE RACK (PARKS 2 BIKES) IS USED, THEN THE PAD
 SHALL BE REDUCED TO 5 FEET WIDE ALONG S. DIXIE. PLEASE
 NOTE THAT CARE SHALL BE TAKEN TO SECURE THE RACK INTO A
 PAVER BASE. STAFF IS NOT OPPOSED TO A CONCRETE PAD.
 PLEASE CONTACT ZONING FOR A COPY OF THE STANDARD CITY
 BICYCLE RACK DETAILS.
  
 6) THE SITE AND CIVIL PLANS SHALL SHOW DIMENSIONS
 ACROSS BOTH THE PARKING AND LANDSCAPE AREAS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-05-02 Cont ID  
Sent By eschneid Date 2011-05-02 Time 11:22 Rev Time 1.50
Received By eschneid Date 2011-05-02 Time 11:22 Sent To  
Notes
2011-05-02 12:05:12FAILED
  
 PLEASE RESPOND IN WRITING. NOTE THAT ADDITIONAL
 COMMENTS MAY BE GENERATED WHEN PLANS ARE CHANGED.
  
 1) THE ZONING BOARD OF APPEALS SHALL APPROVE THE FRONT
 SETBACK VARIANCE PRIOR TO ZONING APPROVAL OF THE
 PERMIT.
  
 2) PLEASE SEE THE LIST BELOW FOR SEPARATE PERMITS
 REQUIRED. THE SITE WORK/PARKING PERMIT AND THE
 LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR TO ZONING
 APPROVAL OF THIS PERMIT.
  
 A. SITE WORK INCLUDING PARKING LOT STRIPING PERMIT. THE
 PLANS SHALL INCLUDE THE BICYCLE RACK DETAILS, THE
 LOCATION OF THE TRASH CAN ENCLOSURE, THE CORRECT
 STRIPING DETAIL FOR THE PARKING SPACES (THE STRIPES ARE
 TO BE 12 INCHES APART), THE ANGLE OF THE PARKING SPACES
 (APPEARS THAT 60 DEGREE IS BEING USED), SHOW THE
 LOCATION AND DETAILS FOR THE TYPE D CURBS TO PROTECT
 THE LANDSCAPE AREAS, AND PROVIDE A COPY OF THE LETTER
 FROM THE WESTERN NEIGHBOR WHICH WAIVES THE PARKING LOT
 WALL REQUIREMENT.
  
 B. LANDSCAPE PERMIT. THE PLANS SHALL INCLUDE DIMENSIONS
 ACROSS THE SITE (SIMILAR TO THE SITE PLAN), THE
 LOCATIONS OF UTILITY POLES, OVERHEAD LINES AND LIGHTING
 (THERE SHALL BE NO CONFLICTS WITH LANDSCAPE), CURBING,
 AND SCREENING OF THE TRASH ENCLOSURE.
  
 C. AWNING PERMIT. THE PERMIT SHALL INCLUDE DETAILS OF
 THE PROPOSED AWNING.
  
 D. SIGN PERMIT. ALL NEW EXTERIOR SIGNAGE.
  
 E. IRRIGATION.
  
 F. FENCING. THE TRASH CANS SHALL BE SCREENED BY AN
 ENCLOSURE. PLEASE PROVIDE A COPY OF THE SANITATION
 APPROVAL OF THE USE OF TRASH CANS AS PART OF THE
 RESUBMITTAL.
  
 PLEASE CHECK WITH THE CONSTRUCTION SERVICES DEPARTMENT
 TO SEE IF THE SUBMITTED PLANS, SUBJECT TO ANY
 CORRECTIONS BASED ON COMMENTS ABOVE AND OTHER REVIEWERS
 MAY BE USED.
  
 3) SHOW ALL OF THE NEW ROOFTOP MECHANICAL EQUIPMENT,
 ETC. ON THE ELEVATIONS. THIS EQUIPMENT SHALL BE
 SCREENED FROM VIEW. IF IT IS NOT, THEN ALTERNATIVE
 SCREENING IS REQUIRED.
  
 4) PROVIDE A LETTER FROM FDOT APPROVING THE MOLDING
 WHICH OVERHANGS SOUTH DIXIE HIGHWAY AND FROM THE CITY?S
 ENGINEERING SERVICES DEPARTMENT FOR THE MOLDING WHICH
 OVERHANGS SUNSET ROAD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  