Plan Review Details - Permit 11040291
Plan Review Stops For Permit 11040291
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-26 Cont ID  
Sent By lmartine Date 2011-04-26 Time 09:51 Rev Time 0.00
Received By lmartine Date 2011-04-26 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-21 Cont ID  
Sent By shill Date 2011-04-21 Time 14:07 Rev Time 0.00
Received By shill Date 2011-04-21 Time 14:07 Sent To  
Notes
2011-04-21 14:09:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET, FLORIDA ADMINISTRATIVE CODE 9N-3,
 WWW.FLORIDABUILDING.ORG.
  
 2. PROVIDE A FLOOR PLAN WHICH SHOWS THE LOCATION OF THE
 PROPOSED DOOR, SWING (INSWING OR OUTSWING) AND ALSO
 PROVIDE ANY OTHER INFORMATION REQUIRED TO SHOW THAT
 WATER INFILTRATION RESISTANCE IS NOT REQUIRED. SEE THE
 PRODUCT APPROVAL, POSITIVE DESIGN PRESSURES FOR INSWING
 DOORS THAT REQUIRE WATER INFILTRATION ARE LOWER THAN
 REQUIRED BY FBC R 301. PROVIDE ENOUGH INFORMATION TO
 SHOW COMPLIANCE, SUCH AS ANY CONDITIONS WHICH WOULD
 MAKE WATER INFILTRATION UNNECESSARY (SUCH AS A COVERED
 PORCH). IN OTHER WORDS, SHOW HOW WATER WILL BE
 PREVENTED FROM ENTERING THE BUILDING THROUGH THE DOOR,
 ESPECIALLY IF IT IS AN INSWING DOOR.
  
 3. PROVIDE BUILDING HEIGHT, LOCATION IN THE BUILDING
 (DISTANCE TO CORNER), AND DOOR SIZE SO DESIGN PRESSURES
 CAN BE DETERMINED FBC R301.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-21 Cont ID  
Sent By shill Date 2011-04-21 Time 14:09 Rev Time 0.00
Received By shill Date 2011-04-12 Time 08:32 Sent To  
Notes
2011-04-13 08:32:41TO MISC 1