| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****APPROVED WITH PROVISIONS***** |
| | |
| | SHEET LS1.0 THE DELAYED EGRESS FEATURE ON THE ELEVATOR |
| | LOBBY DOOR SHALL NOT RELOCK AUTOMATICALLY. AFTER THE |
| | LOCK HAS BEEN RELEASED, RELOCKING SHALL BE BY MANUAL |
| | MEANS ONLY PER NOTE 4D OF SECTION 7.2.1.6.1. VERIFY THE |
| | SWING OF THIS DOOR AS IT IS NOTED PULL TO OPEN; |
| | HOWEVER, THE DOOR APPEARS TO REQUIRE A PUSHING MOTION |
| | TO OPEN ON THE PLAN. |
| | |
| | SHEET A1.0 DOORS ARE REQUIRED TO SWING IN THE DIRECTION |
| | OF TRAVEL WHEN THE ROOM SERVES 50 OR PERSONS SUCH AS |
| | CONFERENCE ROOM 1. |
| | |
| | SHEET A2.0 ELIMINATE STORAGE WITHIN 18 INCHES OF |
| | CEILINGS AND SPRINKLER DEFLECTORS. |
| | |
| | SHEET FA0.1 ACTIVATION OF A DUCT SMOKE DETECTOR SHALL |
| | INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | SHEET FA2.1 PROVIDE NOTIFICATION APPLIANCE IN ROOM/AREA |
| | 405, 439, 440, 441 AND 443. |
| | |
| | SHEET FS2.1 SHOP DRAWINGS AND HYDRAULIC CALCULATIONS |
| | SHALL NOT BE SEALED BY THE CONTRACTOR AS THE ENGINEER |
| | OF RECORD IS ALREADY ESTABLISHED BY THE CONSTRUCTION |
| | DOCUMENTS. PER FLORIDA ADMINISTRATIVE CODE, CHAPTER |
| | 61G15-32.002, THE FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER WHO DEVELOPS THE FIRE PROTECTION SYSTEM DESIGN |
| | CRITERIA AND SEALS THE CONSTRUCTION DOCUMENTS IS DEEMED |
| | THE ENGINEER OF RECORD. |
| | |