Plan Review Details - Permit 11040263
Plan Review Stops For Permit 11040263
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-04-15 Cont ID  
Sent By jwitmer Date 2011-04-15 Time 13:58 Rev Time 1.55
Received By jwitmer Date 2011-04-15 Time 11:43 Sent To  
Notes
2011-04-15 14:26:12BUILDING PROVISO:
 NOTE ELEVATOR LOBBY IS EXISTING DOOR # 400 A NOTE 6
 INDICATES WORK BEING COMPLETED ON ELECTRIC LOCKS AND
 CARD READER, TO COMPLY WITH FBC-B
 707.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS
 OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE.
 PLEASE PROVIDE LITERATURE FOR ELECTRIC LOCKING
 MECHANISM AND FAIL SAFE IN CASE OF LOSS OF POWER.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-18 Cont ID  
Sent By rlecky Date 2011-04-18 Time 11:01 Rev Time 0.00
Received By rlecky Date 2011-04-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-04-15 Cont ID  
Sent By wjolin Date 2011-04-15 Time 09:32 Rev Time 0.00
Received By wjolin Date 2011-04-14 Time 08:54 Sent To  
Notes
2011-04-15 09:32:021 NORTH CLEMATIS STREET, 4TH FLOOR
 PERMIT #11040263
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 SHEET LS1.0 THE DELAYED EGRESS FEATURE ON THE ELEVATOR
 LOBBY DOOR SHALL NOT RELOCK AUTOMATICALLY. AFTER THE
 LOCK HAS BEEN RELEASED, RELOCKING SHALL BE BY MANUAL
 MEANS ONLY PER NOTE 4D OF SECTION 7.2.1.6.1. VERIFY THE
 SWING OF THIS DOOR AS IT IS NOTED PULL TO OPEN;
 HOWEVER, THE DOOR APPEARS TO REQUIRE A PUSHING MOTION
 TO OPEN ON THE PLAN.
  
 SHEET A1.0 DOORS ARE REQUIRED TO SWING IN THE DIRECTION
 OF TRAVEL WHEN THE ROOM SERVES 50 OR PERSONS SUCH AS
 CONFERENCE ROOM 1.
  
 SHEET A2.0 ELIMINATE STORAGE WITHIN 18 INCHES OF
 CEILINGS AND SPRINKLER DEFLECTORS.
  
 SHEET FA0.1 ACTIVATION OF A DUCT SMOKE DETECTOR SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 SHEET FA2.1 PROVIDE NOTIFICATION APPLIANCE IN ROOM/AREA
 405, 439, 440, 441 AND 443.
  
 SHEET FS2.1 SHOP DRAWINGS AND HYDRAULIC CALCULATIONS
 SHALL NOT BE SEALED BY THE CONTRACTOR AS THE ENGINEER
 OF RECORD IS ALREADY ESTABLISHED BY THE CONSTRUCTION
 DOCUMENTS. PER FLORIDA ADMINISTRATIVE CODE, CHAPTER
 61G15-32.002, THE FLORIDA REGISTERED PROFESSIONAL
 ENGINEER WHO DEVELOPS THE FIRE PROTECTION SYSTEM DESIGN
 CRITERIA AND SEALS THE CONSTRUCTION DOCUMENTS IS DEEMED
 THE ENGINEER OF RECORD.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-25 Cont ID  
Sent By rregueir Date 2011-04-25 Time 15:54 Rev Time 0.00
Received By rregueir Date 2011-04-14 Time 15:44 Sent To  
Notes
2011-04-14 15:44:48**DIGITAL PLANS** SEE PROJECTDOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-22 Cont ID  
Sent By rregueir Date 2011-04-22 Time 16:58 Rev Time 0.00
Received By rregueir Date 2011-04-22 Time 09:04 Sent To  
Notes
2011-04-22 13:55:27**PROVISO**
  
 1. SOME ROOMS WITH FULL-HEIGHT PARTITIONS DO NOT HAVE
 TRANSFER DUCTS OR OTHER MEANS BY WHICH RETURN AIR CAN
 GET BACK TO THE CENTAR AIR HANDLER. EXAMPLE: COFFEE
 ROOM 405. THIS IS JUST AN EXAMPLE. CHECK ALL AREAS AND
 PROVIDE BALANCED RETURN PER FBC-M 601.4. REVISION
 REQUIRED.
  
 2. SEVERAL ROOMS HAVE TRANSFER DUCTS WHICH ARE NOT
 SIZED TO MEET THE BALANCED RETURN EXCEPTIONS UNDER
 FBC-M 601.4. EXAMPLES: ROOMS 409 AND 453. PLEASE CHECK
 ALL AREAS AND PROVIDE BALANCED RETURN PER FBC-M 601.4.
 REVISION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-15 Cont ID  
Sent By lwagner Date 2011-04-15 Time 12:59 Rev Time 0.00
Received By lwagner Date 2011-04-15 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-04-25 Cont ID  
Sent By rregueir Date 2011-04-25 Time 15:54 Rev Time 0.00
Received By rregueir Date 2011-04-25 Time 15:54 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy