| 2011-05-17 15:45:51 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PLANS SPECIFY NEW COVERED PORCH. THIS IS NOT A |
| | PORCH. PORCH IS AN EXTERIOR AREA. PLANS SHOW A COMPLETE |
| | ENCLOSED ROOM. THIS IS A NEW INTERIOR ROOM. SEE |
| | DEFINITION OF PORCH AND REVISE NAME ON PLANS AS |
| | REQUIRED. SEC. 106.1.1 CITY AMENDMENTS TO FBC |
| | |
| | 2- INDICATE ON PLANS THE NAMES OF THE ROOMS ADJACENT TO |
| | THIS NEW INTERIOR ROOM TO VERIFY COMPLIANCE WITH THE |
| | BEDROOM EGRESS REQUIREMENTS OF SEC. R310. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | REQUIRED. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS. PLEASE MAKE SURE |
| | CORRECT REVISED FORM IS USED. SEC. N1100.3 OF 2007 |
| | FLORIDA RESIDENTIAL CODE CHAPTER 11. |
| | |
| | 5- SHEET #1: SPECIFY SIZE OF NEW EXTERIOR DOOR. SEC. |
| | 106.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | 6- SHEET #2: WHAT'S A SIMPSON TA30R CONNECTOR SPECIFIED |
| | ON WALL SECTION ON THE EXISTING MASONRY WALL END. I AM |
| | UNABLE TO FIND THIS STRUCTURAL CONNECTOR ON THE SIMPSON |
| | CATALOG. REVISE AS REQUIRED. ALSO, REVISE ROOF FRAMING |
| | PLAN ON SHEET #3. SEC. 106.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | 7- SHEET #5: A) REVISE STRUCTURAL NOTE #6. ACCORDING |
| | 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". |
| | |
| | B) REVISE VALUES FOR WIND ANALYSIS & DESIGN TABLE. * |
| | THE CODE TO BE USED FOR ONE & TWO FAMILY DWELLINGS IS |
| | THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS |
| | NOT THE FBC. ** ASCE 7 EDITION TO BE USED IS THE 2005 |
| | EDITION NOT THE 2002. *** THE WIND EXPOSURE IS "C" NOT |
| | "B". **** SPECIFY THE DOOR AND WINDOWS DESIGN |
| | PRESSURES. SEC. R301. NOTE: CONSIDER EXPOSURE "C". |
| | REVISE ALL THE SECTIONS AND TABLES THAT REFER TO THE |
| | FBC AND REFERENCE CORRESPONDING SECTION AND TABLE FROM |
| | THE 2007 FLORIDA RESIDENTIAL CODE. SEC. R101.2. |
| | |
| | C) UPDATE THE FLORIDA PRODUCT APPROVAL NUMBER SPECIFIED |
| | ON THE TYPICAL LINTEL AT WINDOWS & DOORS SPECIFICATION |
| | AT BOTTOM OF THE SHEET. NEED TO SPECIFY A PRODUCT |
| | APPROVAL APPROVED FOR THE 2007 BUILDING CODE. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. NOA 09-0316.10 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. GO TO THE MIAMI-DADE WEBSITE |
| | AND DOWNLOAD CURRENT NOA. |
| | |
| | B) STORMS PANELS. PROVIDE COMPLETE INFORMATION. NEED TO |
| | MARK ON NOA SUBMITTED SPECIFIC MOUNTING CONDITIONS AND |
| | ANCHOR TYPE AND SPACING TO BE USED. AND, NEED TO |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED BY |
| | THE CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS |
| | IMPACT PROTECTION. |
| | |
| | C) FLAT ROOF NOA 07-0730.03 WAS SUPERSEDED BY |
| | MIAMI-DADE. NEED CURRENT NOA. ALSO, NEED TO PROVIDE RAS |
| | 117 CALCULATIONS FOR THE NAIL ENHANCING AT PERIMETER |
| | AND CORNER AREAS AS REQUIRED BY THE GENERAL LIMITATION |
| | #7. NOTE: IF THE NOA PROVIDED REQUIRES SIGNED AND |
| | SEALED RAS 117, THEN PROVIDE SIGNED AND SEALED |
| | CALCULATIONS. |
| | |
| | D) EXTERIOR SWING DOOR. NOA 07-0618.06 SUBMITTED IS FOR |
| | 8'-0" HIGH DOORS. NEED NOA FOR 6'-8" HIGH DOORS. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND |
| | PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | F) ALL PRECAST LINTELS SPECIFIED ON PLANS. |
| | |
| | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 10- SPECIFY VENTILATION ON NEW ROOF AS REQUIRED BY SEC. |
| | R806. |
| | |
| | 11- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. |
| | 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 12- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| | BY 2009 REVISIONS SEC. R313.4 |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |