Plan Review Details - Permit 11040215
Plan Review Stops For Permit 11040215
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-04-15 Cont ID  
Sent By jwitmer Date 2011-04-15 Time 15:21 Rev Time 0.77
Received By jwitmer Date 2011-04-15 Time 15:15 Sent To  
Notes
2011-04-15 15:47:11 
  
  
  
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 2007/2009 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM
 WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH
 OF NOT LESS THAN 32 INCHES (813 MM). CLEAR OPENINGS OF
 DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN
 90 DEGREES

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-12 Cont ID  
Sent By rlecky Date 2011-04-12 Time 09:07 Rev Time 0.00
Received By rlecky Date 2011-04-12 Time 08:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-04-08 Cont ID  
Sent By wjolin Date 2011-04-08 Time 13:57 Rev Time 0.00
Received By wjolin Date 2011-04-08 Time 13:24 Sent To  
Notes
2011-04-08 13:56:58501 SOUTH FLAGLER DRIVE, SUITE #502
 PERMIT #11040215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 DEMOLITION WORK TO COMPLY WITH THE REQUIREMENTS OF NFPA
 241. DEBRIS SHALL BE REMOVED DAILY.
  
 THE NEW SIDE LIGHT GLAZING SHOWN ADJACENT TO THE SUITE
 ENTRY DOOR APPEARS TO BE LOCATED IN A FIRE RATED
 CORRIDOR WALL. VERIFY GLAZING IS FIRE RATED.
  
 NEW WALLS AND CEILING CONFIGURATION WILL AFFECT FIRE
 SPRINKLER AND FIRE ALARM LAYOUT. SEPARATE PLANS AND
 PERMITS ARE REQUIRED FOR THE INSTALLATION/MODIFICATION
 OF THESE SYSTEMS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-28 Cont ID  
Sent By lmartine Date 2011-04-19 Time 17:25 Rev Time 0.00
Received By lmartine Date 2011-04-08 Time 10:55 Sent To  
Notes
2011-04-08 10:57:47B--13

Review Stop Z ZONING
Rev No 1 Status N Date 2011-04-19 Cont ID  
Sent By aaponte Date 2011-04-19 Time 09:14 Rev Time 0.25
Received By aaponte Date 2011-04-19 Time 09:14 Sent To  
Notes
2011-04-19 09:15:48INTERIOR IMPROVEMENTS ONLY FOR OFFICE SPACE.