| Plan Review Stops For Permit 11040205 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-06-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-06-09 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-06-09 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2011-06-09 14:17:41 | BUILDING REVIEW APPROVED WITH PROVISO | | | | | | 1- A) REVISE SURVEY TO STATE FLOOD ZONE "A". | | | B) PROVIDE SURVEY WITH ORIGINAL SIGNATURE. CHAPTER 472 | | | FLORIDA STATUTES. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR: A) DECORATIVE SHUTTERS | | | SHOWN ON EXTERIOR ELEVATIONS. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. | | | B) SINGLE HUNG WINDOWS THAT MEET THE CALCULATED DESIGN | | | PRESSURES. SEE SHEET S1. | | | | | | ***NOTE: ARCHITECT TO REVIEW ALL PRODUCT APPROVALS. | | | | | | 3- CLEARLY SPECIFY ATTIC LIVE LOAD. SEE TABLE R301.5. | | | | | | 4- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING. | | | SEC. R312. | | | | | | 5- ENERGY CALCULATIONS CALL FOR UNVENTED ATTIC. SHEET | | | S3 SHOW ATTIC VENTILATION CALCULATIONS. REVISE AS | | | REQUIRED TO MATCH AND PROVIDE REQUIRED SPECIFICATIONS. | | | | | | 6- REVISE ELEVATION CERTIFICATES. FLOOD ZONE A NOT B. | | | AND NEED ORIGINAL SIGNATURES. GIVE THEM TO INSPECTOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-05-13 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-05-13 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2011-05-13 16:08:50 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF CHAPTER | | | 13 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- PER CONVERSATION WITH BUILDING OFFICIAL (DOUG WISE) | | | THE PROPERTY IS LOCATED IN FLOOD ZONE A5 WITH A FLOOD | | | BASE ELEVATION OF 7'-0". PROVIDE SURVEY SHOWING THE | | | HOUSE FINISH FLOOR ELEVATION. IF THE HOUSE FINISH FLOOR | | | ELEVATION IS LESS THAN 7'-6", THEN THE HOUSE WILL NEED | | | TO BE RAISED. SEC. 94-541 CITY FLOOD PLAIN MANAGEMENT | | | POLICY. | | | | | | 3- SHEET A1: CLARIFY HOW DO YOU ENTER THE SITTING ROOM. | | | THERE ARE NO DOORS. SEC. 106.1.1 CITY AMENDMENTS TO | | | FBC. | | | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) DECORATIVE SHUTTERS SHOWN ON EXTERIOR ELEVATIONS. | | | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | | | | B) COPPER CLADDING OVER ENTRY ROOF. SEE DETAIL 7/A5 ON | | | SHEET A5. | | | | | | C) MODIFIED BITUMEN MEMBRANE ON SECOND FLOOR BALCONY. * | | | THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED. | | | PROVIDE ONLY ONE PRODUCT APPROVAL AND MAKE SURE PRODUCT | | | APPROVAL IS FOR MODIFIED BITUMEN TO RECEIVE TILE AS | | | SPECIFIED ON FLOOR PLAN 1/A1 ON SHEET A1. ** SPECIFY | | | WHICH APPROVED ASSEMBLY IS GOING TO BE USED. *** | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | REQUIRED BY NOA SUBMITTED. | | | | | | D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL | | | FL9108-R0 SUBMITTED IS FOR 2004 CODE. NEED TO PROVIDE | | | ONE FOR 2007 CODE. | | | | | | 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO | | | FBC. | | | | | | 6- SECTION 2/A2 ON SHEET A2: CLARIFY FINISH GRADE | | | ELEVATION TO VERIFY COMPLIANCE WITH WOOD DECAY SEC. | | | R319.1(5). AND HEIGHT ABOVE FINISHED GRADE SEC. | | | R404.1.6. AND, INSPECTION FOR TERMITES SEC. R704.1. | | | DRAWING PROVIDE SHOWS STUCCO FINISH BELOW FINISH | | | GRADE?. | | | | | | 7- SHEET S1: A) COMPONENTS AND CLADDING DESIGN | | | PRESSURES ON THE WIND DESIGN CRITERIA INDICATES WORST | | | CASE +/-64PSF. THIS DOESN'T MATCH THE DESIGN PRESSURES | | | SHOWN ON THE 2 STORY SKETCH. REVISE AS REQUIRED. | | | | | | B) REVISE FLOOR DEAD LOADS SHOWN. 10PSF AT TOP AND | | | 10PSF AT BOTTOM DON'T ADD UP TO 15PSF. | | | | | | C) SPECIFY AL THE LOADS INCLUDING THE ATTIC LIVE LOAD | | | AND THE BALCONY LIVE LOAD AS REQUIRED BY TABLE R301.5. | | | | | | 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC R807. | | | | | | 9- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING. | | | SEC. R312. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-06-13 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-06-13 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-06-13 |
Time |
12:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-04-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-11 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-11 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2011-04-11 11:43:09 | LOCATE EXISTING SERVICE, MAIN DISCONNECTS AND PANELS ON | | | THE FLOOR PLAN. PROVIDE AN ELECTRICAL RISER DIAGRAM FOR | | | THE EXISTING SERVICE. NEC 110.26 | | | RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11 | | | ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE | | | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER. | | | NEC 210-12 (B) | | | SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING | | | CAPACITY IS SUFFICIENT FOR THE NEW BATH AND BEDROOM. | | | NEC 220 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
2012-06-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2012-06-13 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2012-06-13 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2012-06-15 10:54:14 | CONTRACTOR SUBMITTED ELEVATION CERTIFICATE. ELEVATION | | | CERTIFICATE SENT TO KEN'S DESK FOR PROCESSING FINAL | | | INSPECTION. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-06-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-06-15 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-06-02 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2011-06-15 14:19:00 | RECEIVED PLANS FROM ERIC FOR PROCESSING ON THE | | | AFTERNOON OF 6/14/11. | | 2011-06-02 07:41:21 | R-21 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-06-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-07 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-05-13 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-05-13 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2011-05-13 15:42:12 | NO FEES. MU-2011-6091. REVIEW DONE BY PERMIT TECHNICIAN | | | WITH INITIALS DB ON 4/6/11. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
N |
Date |
2011-06-14 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-06-14 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-06-14 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2011-06-14 15:42:19 | ***LANDSCAPE NOT REQUIRED*** | | | | | | VALUE OF WORK DID NOT EXCEED 50% OF IMPROVEMENT.---RAK |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-12 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-04-12 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-04-12 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2011-04-12 13:36:46 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDR. EXISTING TREES AND SHRUBS CAN BE COUNTED | | | TOWARD MEETING THE REQUIREMENTS IF THEY ARE IN A | | | HEALTHY CONDITION AND MEET THE STANDARDS SET IN THE | | | CODE. SUBMIT WITH THE APPLICATION A CERTIFIED COST | | | ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE | | | MATERIALS AND LABOR BROKEN DOWN INTO UNIT COST. A | | | SEPARATE LANDSCAPE PERMIT IS REQUIRED. | | | | | | 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, IINCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 4. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS | | | ENUMERATED IN THIS SECTION SHALL BE PART OF THE | | | LANDSCAPE PLAN. | | | | | | 5. PURSUANT TO SECTION 94-445 (4) G) (3) (II) IN ALL | | | AREAS (NCLUDING THE ADJACENT RIGHT-OF-WAY) THAT ARE TO | | | BE PLANTED IN A CULTIVATED LANDSCAPE, IRRIGATION | | | SYSTEMS SHALL BE DESIGNED TO HAVE 120 PERCENT COVERAGE. | | | A SEPARATE IRRIGATION PERMIT WILL BE REQUIRED IF AN | | | EXISTING SYSTEM NEEDS TO BE MODIFIED OR IF A NEW SYSTEM | | | WILL BE INSTALLED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-06-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-06-13 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-06-13 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-05-13 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-05-13 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2011-05-13 15:37:55 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE HEATING AND COOLING LOAD CALCULATIONS AS | | | REQUIRED BY SEC. N1107 OF CHAPTER 13 OF 2007 FLORIDA | | | RESIDENTIAL CODE. | | | | | | ***NOTE: COORDINATE EQUIPMENT INFORMATION WITH | | | INFORMATION SHOWN ON THE PLANS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-06-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-06-10 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-06-10 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2011-05-13 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2011-05-13 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-06-14 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2011-06-06 |
Time |
08:28 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2011-06-06 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2011-06-14 15:46:39 | VALUE CHANGE ON PERMIT - LESS THAN 50% OF STRUCTURE | | | VALUE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2011-04-26 |
Time |
15:53 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2011-04-26 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2011-04-26 15:57:48 | FAILED | | | | | | 1) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($272,420) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | 2) EXCLUDING THE REQUIREMENT OF 1, ABOVE, THE NEW | | | CONSTRUCTION MEETS ALL ZONING REQUIREMENTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|