Plan Review Details - Permit 11040205
Plan Review Stops For Permit 11040205
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-10 Cont ID  
Sent By jgomez Date 2011-06-09 Time 14:14 Rev Time 0.00
Received By jgomez Date 2011-06-09 Time 14:13 Sent To  
Notes
2011-06-09 14:17:41BUILDING REVIEW APPROVED WITH PROVISO
  
 1- A) REVISE SURVEY TO STATE FLOOD ZONE "A".
 B) PROVIDE SURVEY WITH ORIGINAL SIGNATURE. CHAPTER 472
 FLORIDA STATUTES.
  
 2- PROVIDE PRODUCT APPROVAL FOR: A) DECORATIVE SHUTTERS
 SHOWN ON EXTERIOR ELEVATIONS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
 B) SINGLE HUNG WINDOWS THAT MEET THE CALCULATED DESIGN
 PRESSURES. SEE SHEET S1.
  
 ***NOTE: ARCHITECT TO REVIEW ALL PRODUCT APPROVALS.
  
 3- CLEARLY SPECIFY ATTIC LIVE LOAD. SEE TABLE R301.5.
  
 4- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING.
 SEC. R312.
  
 5- ENERGY CALCULATIONS CALL FOR UNVENTED ATTIC. SHEET
 S3 SHOW ATTIC VENTILATION CALCULATIONS. REVISE AS
 REQUIRED TO MATCH AND PROVIDE REQUIRED SPECIFICATIONS.
  
 6- REVISE ELEVATION CERTIFICATES. FLOOD ZONE A NOT B.
 AND NEED ORIGINAL SIGNATURES. GIVE THEM TO INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By jgomez Date 2011-05-13 Time 15:42 Rev Time 0.00
Received By jgomez Date 2011-05-13 Time 15:42 Sent To  
Notes
2011-05-13 16:08:50RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF CHAPTER
 13 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PER CONVERSATION WITH BUILDING OFFICIAL (DOUG WISE)
 THE PROPERTY IS LOCATED IN FLOOD ZONE A5 WITH A FLOOD
 BASE ELEVATION OF 7'-0". PROVIDE SURVEY SHOWING THE
 HOUSE FINISH FLOOR ELEVATION. IF THE HOUSE FINISH FLOOR
 ELEVATION IS LESS THAN 7'-6", THEN THE HOUSE WILL NEED
 TO BE RAISED. SEC. 94-541 CITY FLOOD PLAIN MANAGEMENT
 POLICY.
  
 3- SHEET A1: CLARIFY HOW DO YOU ENTER THE SITTING ROOM.
 THERE ARE NO DOORS. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) DECORATIVE SHUTTERS SHOWN ON EXTERIOR ELEVATIONS.
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 B) COPPER CLADDING OVER ENTRY ROOF. SEE DETAIL 7/A5 ON
 SHEET A5.
  
 C) MODIFIED BITUMEN MEMBRANE ON SECOND FLOOR BALCONY. *
 THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED.
 PROVIDE ONLY ONE PRODUCT APPROVAL AND MAKE SURE PRODUCT
 APPROVAL IS FOR MODIFIED BITUMEN TO RECEIVE TILE AS
 SPECIFIED ON FLOOR PLAN 1/A1 ON SHEET A1. ** SPECIFY
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. ***
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 REQUIRED BY NOA SUBMITTED.
  
 D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL9108-R0 SUBMITTED IS FOR 2004 CODE. NEED TO PROVIDE
 ONE FOR 2007 CODE.
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC.
  
 6- SECTION 2/A2 ON SHEET A2: CLARIFY FINISH GRADE
 ELEVATION TO VERIFY COMPLIANCE WITH WOOD DECAY SEC.
 R319.1(5). AND HEIGHT ABOVE FINISHED GRADE SEC.
 R404.1.6. AND, INSPECTION FOR TERMITES SEC. R704.1.
 DRAWING PROVIDE SHOWS STUCCO FINISH BELOW FINISH
 GRADE?.
  
 7- SHEET S1: A) COMPONENTS AND CLADDING DESIGN
 PRESSURES ON THE WIND DESIGN CRITERIA INDICATES WORST
 CASE +/-64PSF. THIS DOESN'T MATCH THE DESIGN PRESSURES
 SHOWN ON THE 2 STORY SKETCH. REVISE AS REQUIRED.
  
 B) REVISE FLOOR DEAD LOADS SHOWN. 10PSF AT TOP AND
 10PSF AT BOTTOM DON'T ADD UP TO 15PSF.
  
 C) SPECIFY AL THE LOADS INCLUDING THE ATTIC LIVE LOAD
 AND THE BALCONY LIVE LOAD AS REQUIRED BY TABLE R301.5.
  
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC R807.
  
 9- PROVIDE COMPLETE INFORMATION FOR BALCONY RAILING.
 SEC. R312.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-06-13 Cont ID  
Sent By rlecky Date 2011-06-13 Time 12:45 Rev Time 0.00
Received By rlecky Date 2011-06-13 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-11 Cont ID  
Sent By rlecky Date 2011-04-11 Time 11:41 Rev Time 0.00
Received By rlecky Date 2011-04-11 Time 11:05 Sent To  
Notes
2011-04-11 11:43:09LOCATE EXISTING SERVICE, MAIN DISCONNECTS AND PANELS ON
 THE FLOOR PLAN. PROVIDE AN ELECTRICAL RISER DIAGRAM FOR
 THE EXISTING SERVICE. NEC 110.26
 RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER.
 NEC 210-12 (B)
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING
 CAPACITY IS SUFFICIENT FOR THE NEW BATH AND BEDROOM.
 NEC 220
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2012-06-15 Cont ID  
Sent By jgomez Date 2012-06-13 Time 10:54 Rev Time 0.00
Received By jgomez Date 2012-06-13 Time 10:54 Sent To  
Notes
2012-06-15 10:54:14CONTRACTOR SUBMITTED ELEVATION CERTIFICATE. ELEVATION
 CERTIFICATE SENT TO KEN'S DESK FOR PROCESSING FINAL
 INSPECTION. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-15 Cont ID  
Sent By jgomez Date 2011-06-15 Time 14:17 Rev Time 0.00
Received By jgomez Date 2011-06-02 Time 07:41 Sent To  
Notes
2011-06-15 14:19:00RECEIVED PLANS FROM ERIC FOR PROCESSING ON THE
 AFTERNOON OF 6/14/11.
2011-06-02 07:41:21R-21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-02 Cont ID  
Sent By rmcdouga Date 2011-05-13 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2011-04-07 Time 16:58 Sent To  
Notes
2011-04-07 17:10:46R--10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-05-13 Cont ID  
Sent By jgomez Date 2011-05-13 Time 15:39 Rev Time 0.00
Received By jgomez Date 2011-05-13 Time 15:39 Sent To  
Notes
2011-05-13 15:42:12NO FEES. MU-2011-6091. REVIEW DONE BY PERMIT TECHNICIAN
 WITH INITIALS DB ON 4/6/11.

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-06-14 Cont ID  
Sent By rkussner Date 2011-06-14 Time 15:40 Rev Time 0.00
Received By rkussner Date 2011-06-14 Time 15:40 Sent To  
Notes
2011-06-14 15:42:19***LANDSCAPE NOT REQUIRED***
  
 VALUE OF WORK DID NOT EXCEED 50% OF IMPROVEMENT.---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-04-12 Cont ID  
Sent By rkussner Date 2011-04-12 Time 10:57 Rev Time 0.00
Received By rkussner Date 2011-04-12 Time 10:57 Sent To  
Notes
2011-04-12 13:36:46***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. EXISTING TREES AND SHRUBS CAN BE COUNTED
 TOWARD MEETING THE REQUIREMENTS IF THEY ARE IN A
 HEALTHY CONDITION AND MEET THE STANDARDS SET IN THE
 CODE. SUBMIT WITH THE APPLICATION A CERTIFIED COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR BROKEN DOWN INTO UNIT COST. A
 SEPARATE LANDSCAPE PERMIT IS REQUIRED.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, IINCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 4. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION SHALL BE PART OF THE
 LANDSCAPE PLAN.
  
 5. PURSUANT TO SECTION 94-445 (4) G) (3) (II) IN ALL
 AREAS (NCLUDING THE ADJACENT RIGHT-OF-WAY) THAT ARE TO
 BE PLANTED IN A CULTIVATED LANDSCAPE, IRRIGATION
 SYSTEMS SHALL BE DESIGNED TO HAVE 120 PERCENT COVERAGE.
 A SEPARATE IRRIGATION PERMIT WILL BE REQUIRED IF AN
 EXISTING SYSTEM NEEDS TO BE MODIFIED OR IF A NEW SYSTEM
 WILL BE INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-06-13 Cont ID  
Sent By jgomez Date 2011-06-13 Time 10:08 Rev Time 0.00
Received By jgomez Date 2011-06-13 Time 09:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By jgomez Date 2011-05-13 Time 15:32 Rev Time 0.00
Received By jgomez Date 2011-05-13 Time 15:32 Sent To  
Notes
2011-05-13 15:37:55RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE HEATING AND COOLING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107 OF CHAPTER 13 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 ***NOTE: COORDINATE EQUIPMENT INFORMATION WITH
 INFORMATION SHOWN ON THE PLANS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-06-10 Cont ID  
Sent By jgomez Date 2011-06-10 Time 16:37 Rev Time 0.00
Received By jgomez Date 2011-06-10 Time 16:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-13 Cont ID  
Sent By jgomez Date 2011-05-13 Time 15:39 Rev Time 0.00
Received By jgomez Date 2011-05-13 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-06-14 Cont ID  
Sent By eschneid Date 2011-06-06 Time 08:28 Rev Time 0.50
Received By eschneid Date 2011-06-06 Time 08:28 Sent To  
Notes
2011-06-14 15:46:39VALUE CHANGE ON PERMIT - LESS THAN 50% OF STRUCTURE
 VALUE.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-04-26 Cont ID  
Sent By eschneid Date 2011-04-26 Time 15:53 Rev Time 0.50
Received By eschneid Date 2011-04-26 Time 15:53 Sent To  
Notes
2011-04-26 15:57:48FAILED
  
 1) THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($272,420) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2) EXCLUDING THE REQUIREMENT OF 1, ABOVE, THE NEW
 CONSTRUCTION MEETS ALL ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.