| 2011-04-19 14:23:03 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. VALUE IS TO INCLUDE LABOR AND MATERIALS. PROVIDE AN |
| | INVOICE FROM STORM DEPOT TO PROVIDE EVIDENCE OF |
| | MATERIAL COST. |
| | |
| | 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. |
| | |
| | 3. PROVIDE INFORMATION TO SHOW HOW YOU HAVE DETERMINED |
| | THAT THE SUBSTRATE ON THE BOTTOM IS CONCRETE. TYPICALLY |
| | THE SUBSTRATE IS CONCRETE AT THE TOP, CONCRETE AT THE |
| | BOTTOM. ALTERNATIVELY, REVISE BOTTOM SUBSTRATE TO |
| | CONCRETE BLOCK AND REVISE ANCHOR SPACING ACCORDINGLY. |
| | FBC R301. |
| | |
| | 4. PROVIDE INFORMATION REGARDING THE EMERGENCY MEANS OF |
| | ESCAPE, FBC R310.4. SHOW ROOM DESIGNATIONS AND TYPE OF |
| | OPENING. TWO OPENINGS ARE SHOWN ON THE FLOOR PLAN AS |
| | "EXIT" BUT BOTH ARE TO BE COVERED WITH ACCORDION |
| | SHUTTERS. IT IS NOT CLEAR HOW THE OPENINGS WILL COMPLY |
| | WITH THE REQUIREMENTS OF THE CODE. |
| | |
| | 5. THE "SHUTTER CONNECTION MOUNTING TYPE" ON THE |
| | INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR |
| | CHART, SEE PAGE 6. BASED ON INFORMATION HIGHLIGHTED, IT |
| | APPEARS THAT YOU PROPOSE TO USE MOUNTING TYPE "C2," SEE |
| | PAGE 3 OF PRODUCT APPROVAL. PLEASE NOTE THAT |
| | HIGHLIGHTED INFORMATION DOES NOT APPEAR WHEN SCANNED, |
| | AND CANNOT BE USED TO SHOW CODE COMPLIANCE. PLEASE |
| | REVISE THE INSTALLATION SCHEDULE TO INCLUDE REQUIRED |
| | INFORMATION. |
| | |
| | 6. SHUTTER SPAN FOR AN ACCORDION SHUTTER IS THE BLADE |
| | LENGTH. SEE OPENING 6, 268" IS STATED AS SPAN. THIS |
| | EXCEEDS THE MAXIMUM PERMITTED BY THIS PRODUCT APPROVAL; |
| | HOWEVER, IT APPEARS THAT YOU HAVE USED THE SHUTTER |
| | WIDTH. PLEASE ADDRESS. |
| | |
| | |
| | |
| | 6. |
| | |
| | |
| | |
| | 4. |
| | |