| Plan Review Stops For Permit 11040166 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-06-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-13 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-13 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-19 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-19 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2011-05-19 10:36:23 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A | | | MINIMUM ELEVATION REQUIREMENT OF 7'-6" PER THE CITY OF | | | WEST PALM BEACH CITY FLOOD PLAIN ORDINANCE ARTICLE | | | XVII. THE GARAGE FLOOR ELEVATION IS REQUIRED TO BE A | | | MINIMUM OF 7'-6" OR BE CONSTRUCTED WITH FLOOD DAMAGE | | | RESISTANT MATERIALS AND FLOOD VENTS. FBC R323 | | | | | | 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | AND DATED BY THE OWNER/AGENT. THERE ARE ALSO MISTAKES | | | IN THE CALCULATIONS. SEE MECHANICAL REVIEW COMMENTS. | | | FBC 13-103 | | | | | | 3) SUBMIT TWO COPIES OF THE SPECIFICATIONS FOR THE | | | ICYNENE SPRAY FOAM INSULATION AND SPECIFY THE IGNITION | | | BARRIER THAT WILL BE USED. FBC R314 | | | | | | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT PER CITY AMENDMENTS 106.3.3. | | | | | | 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE CLAY ROOF TILE AND SUBMIT THE PRODUCT | | | APPROVALS FOR IT. DCA RULE 9B-72 | | | | | | 6) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING OF THE BASE SHEET | | | FOR THE GAF MODIFIED ROOFING MATERIAL AS REQUIRED BY | | | LIMITATION # 7 OF THE PRODUCT APPROVAL. | | | | | | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | OUT-SWING SERVICE DOOR AT THE GARAGE AS REQUIRED BY DCA | | | RULE 9B-72. | | | | | | 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SERIES "450" ALUMINUM DOOR HAS BEEN SUPERSEDED. PLEASE | | | SUBMIT THE CURRENT NOA NO. 09-0723.04. | | | | | | 9) THE TRUSS DRAWINGS AND LAYOUT ARE REQUIRED TO BE | | | REVIEWED BY THE DESIGNER OF RECORD FOR THE STRUCTURE. | | | THE D.O.R. SHOULD STAMP THE LAYOUT WITH A SHOP DRAWING | | | REVIEW STAMP. NOTE: THE TRUSS DRAWINGS AND LAYOUT FOR | | | SINGLE FAMILY HOMES CAN BE GIVEN TO THE FIELD INSPECTOR | | | AT THE TRUSS INSPECTION. | | | | | | 10) PROVIDE ROOF DRAIN AND OVERFLOW SCUPPER SIZING | | | CALCULATIONS FOR THE BALCONY AS REQUIRED BY FBC R903.4 | | | AND FBC 1106 & 1107. | | | | | | 11) TWO SETS OF SHOP DRAWINGS APPROVED BY THE DESIGNER | | | OF RECORD FOR THE STRUCTURE FOR THE PRECAST HOLLOW CORE | | | SLAB SYSTEM WILL BE REQUIRED TO BE SUBMITTED PRIOR TO | | | INSTALLATION. | | | | | | 12) SUBMIT TWO SETS OF SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE BUILT-IN BBQ ON THE COVERED PORCH. | | | FBCR M1306.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-04-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-28 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-27 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2011-04-28 10:01:04 | PLANS REDLINED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2011-05-13 |
Time |
|
Rev Time |
0.25 |
| Received By |
mgonzale |
Date |
2011-05-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2011-05-13 16:23:05 | CALL 811 FOR LOCATES AS CITY UTILITIES ARE IN THE | | | VICINITY, WATERMAIN IN THE EASEMENT IN PROXIMITY TO | | | DRIVEWAY. | | | | | | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-6 | | | .PDF | | | | | | | | | MANNY GONZALEZ | | | CSD ENG REVIEW | | | (561) 494-1085 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2011-05-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-17 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-17 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2011-05-17 08:14:58 | A SEPARATE PERMIT, APPLICATION AND PLANS ARE REQUIRED | | | FOR THE GAS PERMIT. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-04-13 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2011-04-13 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2011-04-13 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2011-04-13 14:57:45 | 4-13-11 FHM APPROVED FOR HSITORIC WITH THE FOLLOWING | | | PROVISOS (SPOKE TO ARCHITECT WHO WILL ADDRESS THESE AND | | | RESUBMIT): | | | - MUNTINS ON WINDOWS TO HAVE OGEE PROFILE NOT | | | RECTANGULAR | | | - ADDITION OF TWO AWNINGS ON GREENWOOD SIDE OVER | | | RECTANGULAR WINDOWS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-06-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-14 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-03 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2011-06-03 10:50:36 | INCOMING SENT TOR MC DOUGAL DESK. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-19 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-14 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2011-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-10 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-10 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2011-06-10 15:26:12 | MU-2011-009167 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-05-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-16 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-16 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2011-05-16 08:57:50 | IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. (561-233-5025) |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2011-06-14 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2011-06-13 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2011-06-13 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2011-06-13 17:01:01 | PRIOR TO THE ISSUANCE OF A CO A LANDSCAPE PERMIT MUST | | | BE APPLIED FOR, ISSUED AND INSTALLED. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2011-04-20 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2011-04-20 17:02:31 | MUST SUBMIT SEPARATE LANDSCAPE AND IRRIGATION PERMIT. | | | CONTACT ROBERT KUSSNER AT 822-1462 FOR MORE DETAILS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-06-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-13 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-13 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-05-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-16 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-16 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2011-05-16 15:57:39 | 2009 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE TITLE BLOCK HAS THE NAME AND LICENSE NUMBER OF | | | THE ARCHITECT, THEREFORE THE MECHANICAL PLANS ARE | | | REQUIRED TO BE SIGNED AND SEALED BY HIM PER FLORIDA | | | STATUTES 481. IF THERE IS NO ACHITECT OR ENGINEERS | | | TITLE BLOCK, SYSTEMS LESS THAN 15-TONS AND DESIGNED TO | | | ACCOMMODATE 100 OR FEWER PERSONS CAN BE DESIGNED BY AN | | | A/C OR MECHANICAL CONTRACTOR PER FS471.003(H). THE | | | NAME, SIGNATURE AND LICENSE NUMBER OF THE CONTRACTOR IS | | | REQUIRED ON THE PLANS. | | | | | | 2) THE ENERGY CALCULATIONS CONTAINS THE FOLLOWING | | | ERRORS: 1) THE ENERGY CALC. FORM SPECIFIES A VENTED | | | ATTIC WITH R-30 INSULATION AND THE PLAN SHEET A11 | | | SPECIFIES ICYNENE SPRAY FOAM INSULATION IN A NON-VENTED | | | ATTIC. 2) THE PLANS SPECIFY CLAY TILE AND NOT | | | COMPOSITION SHINGLES. 3) THE (2) WATER HEATERS ARE GAS | | | AND NOT ELECTRIC. PLEASE REVIEW AND CORRECT THE ENERGY | | | CALCULATIONS. SEE FBC 13-101.2 | | | | | | 3) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | AND DATED BY THE OWNER/AGENT. FBC 13-103.1.2 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-05-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-17 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-17 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2011-04-13 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2011-04-13 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2011-04-13 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2011-04-13 14:59:05 | 4-13-11 FHM APPROVED. POOL LOCATION REQUIRES CLASS B | | | SPECIAL USE PERMIT (SCHEDULED FOR 4-26-11 HPB MTG). |
|
|