Plan Review Details - Permit 11040155
Plan Review Stops For Permit 11040155
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-05-20 Cont ID  
Sent By jwitmer Date 2011-05-20 Time 12:10 Rev Time 0.44
Received By jwitmer Date 2011-05-20 Time 12:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-29 Cont ID  
Sent By jwitmer Date 2011-04-29 Time 15:04 Rev Time 0.70
Received By jwitmer Date 2011-04-29 Time 14:58 Sent To  
Notes
2011-04-29 15:04:44BUILDING PROVISO:
 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-14 Cont ID  
Sent By jwitmer Date 2011-04-14 Time 14:38 Rev Time 2.00
Received By jwitmer Date 2011-04-14 Time 13:08 Sent To  
Notes
2011-04-14 15:30:31BUILDING PLAN REVIEW
 PERMIT: 11040155
 ADD: 1300 N. FLORIDA MANGO RD
 CONT: MALASKY HOMES, INC
 TEL: (561)329-9428
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 DESIGN CRITERIA:
  
 1A) PLANS INDICATE A S-2 STORAGE OCCUPANCY OF
 APPROXIMATELY 2400 SQ FT AND A BUSSINESS OCCUPANCY OF
 APPROXIMATELY 2200 SQ FT PLUS A ASSEMBLY OCCUPANCY OF
 2400 SQ FT WHEN THE OCCUPANCY DATA IS TOTALED UP ADDING
 UP TO 7,000 SQ FT FOR THIS TENANT SPACE. IT APPEARS TO
 BE A DISCREPANCY IN SQUARE FOOTAGE FOR THIS TENANT
 SPACE. 106.1.2 ADDITIONAL INFORMATION REQUIRED?
  
 1B) THE TENANT SPACE DOES NOT INDICATE ANY ASSEMBLY
 OCCUPANCY, THE PLAN DOES INDICATE A FLEX ROOM,
 INSTRUCTIONAL MEETING ROOM IS THIS TO BE CONSIDERED THE
 CONFERENCE ROOM? WHEN CALCULATING THE SQ FOOTAGE OF THE
 CONFERENCE ROOM OF 556 SQ FT / 15 = AN OCCUPANT LOAD OF
 37 OCCUPANTS, PLEASE PROVIDE ADDITIONAL INFORMATION AS
 TO THE LOCATION OF AN ASSEMBLY OCCUPANCY, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 1C) THE PLANS CURRENTLY INDICATE WALLS TO BE REMOVED
 BUT THERE STILL SEAMS TO BE A A BUSINESS SUB-OCCUPANCY
 AND EITHER A WAREHOUSE (STORAGE S-2) OCCUPANCY OR
 MERCANTILE OCCUPANCY IN EITHER CASE THIS IS A MIXED
 OCCUPANCY (508.3). THE PLAN DOES NOT INDICATE IF THE
 DESIGN INCORPORATES SEPERATED ( 508.3.1.3) OR
 NON-SEPERATED OCCUPNCIES AS PER 508.3.2. THE BUSINESS
 OCCUPANCY IS CLEARLY OVER 10% OF THE SQ FT AREA.
  
 2)THE PLANS SHOW ONE OF THE EXIT ROUTES GOING THROUGH A
 ROOM LABELED EXISTING FLEX SP? WHAT IS THE USAGE OF
 THIS ROOM, IS IT CONSIDERED A STORAGE ROOM?
  
 3) IN THE NORTH EAST CORNER OF THE BUILDING THERE IS A
 EXIT TYPE VESTIBULE BOTH THE TENANT SEPERATION WALLS
 AND THE MAIN ELECTRIC ROOM WALLS ARE A 1 HR FIRE RATED
 ASSEMBLY, PLEASE PROVIDE FIRE RATING OF THE TWO DOORS
 WITHIN THE EXIT VESTIBULE FBC-B TABLE 715.4.
  
 4) THE EXIT VESTIBULE MAY REQUIRE EXIT LIGHTING, THE
 PLANS DO NOT SHOW ANY WINDOWS IN THIS ROOM FBC-B
 10062.1(2).
  
 5) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-08 Cont ID  
Sent By rlecky Date 2011-04-08 Time 15:29 Rev Time 0.00
Received By rlecky Date 2011-04-08 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-05-12 Cont ID  
Sent By ddaniels Date 2011-05-12 Time 11:01 Rev Time 0.00
Received By ddaniels Date 2011-05-12 Time 11:01 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-04-27 Cont ID  
Sent By wjolin Date 2011-04-27 Time 10:17 Rev Time 0.00
Received By wjolin Date 2011-04-27 Time 09:55 Sent To  
Notes
2011-04-27 10:00:141300 NORTH FLORIDA MANGO ROAD, SUITES 21 AND 21A
 PERMIT #11040155
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE
 PREVENTION CODE NFPA 101
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 106.3.5 OF THE FLORIDA BUILDING CODE REQUIRES FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEM.
 SEPARATE PLANS AND PERMITS WILL ALSO BE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF FIRE SPRINKLER AND
 FIRE ALARM SYSTEM.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. FIRE PROTECTION SYSTEMS ARE TO REMAIN
 ACTIVE DURING DEMOLITION AND RENOVATION. IF ANY FIRE
 PROTECTION SYSTEM IS INOPERABLE FOR MORE THAN 4 HOURS
 IN A 24 HOUR PERIOD, A FIRE WATCH IS REQUIRED. ALL FIRE
 WATCHES MUST BE REQUESTED IN WRITING AND SUBMITTED TO
 THE FIRE MARSHAL'S OFFICE.
  
 LIMITED INFORMATION HAS BEEN PROVIDED AND THE INTENDED
 USE IS NOT CLEAR FOR THE AREA LABELED AS "DISPLAY."
 PROVIDE FLOOR PLAN INFORMATION AS TO THE INTENDED
 LAYOUT FOR THE DISPLAY AREA. INDICATE WHAT TYPE OF
 ITEMS OR MATERIALS WILL BE DISPLAYED AND HOW THESE
 ITEMS WILL BE ARRANGED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-07 Cont ID  
Sent By wjolin Date 2011-04-07 Time 12:23 Rev Time 0.00
Received By wjolin Date 2011-04-07 Time 11:27 Sent To  
Notes
2011-04-07 12:23:571300 NORTH FLORIDA MANGO ROAD, SUITES 21 AND 21A
 PERMIT #11040155
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE OCCUPANCIES INDICATED ON SHEET A1 ARE STORAGE AND
 BUSINESS; HOWEVER, THE OCCUPANT LOAD FACTOR OF 15
 SQUARE FEET PER PERSON CORRELATES TO AN ASSEMBLY
 OCCUPANCY. INDICATE THE INTENDED USE OF THE SPACE.
  
 THE PROPOSED OCCUPANCY TYPES REQUIRE A ONE HOUR RATED
 FIRE SEPARATION BETWEEN DIFFERENT OCCUPANCIES.
  
 THE VESTIBULE DOOR SWING HINDERS FREE FLOWING EGRESS AT
 THE NORTHEAST EXIT. THIS UNRATED DOOR IS LOCATED IN A
 FIRE RATED WALL.
  
 PANIC HARDWARE IS REQUIRED ON DOORS IN ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 100
 PERSONS.EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION
 SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE/SMOKE BARRIER PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE
 SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE NFPA
 101
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 106.3.5 OF THE FLORIDA BUILDING CODE REQUIRES FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEM.
 SEPARATE PLANS AND PERMITS WILL ALSO BE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF FIRE SPRINKLER AND
 FIRE ALARM SYSTEM.
  
 PROVIDE TACTILE SIGNAGE AT EXITS UTILITIZING EXIT
 SIGNS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-05-20 Cont ID  
Sent By jwitmer Date 2011-05-20 Time 12:11 Rev Time 0.00
Received By jwitmer Date 2011-05-05 Time 16:18 Sent To  
Notes
2011-05-20 11:25:175/20 ROUTED TO JW DESK FOR BLDG REVIEW & PROCESSING SH
2011-05-05 16:19:13SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 08:44 Sent To  
Notes
2011-04-27 08:44:16B20
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-14 Cont ID  
Sent By shill Date 2011-04-14 Time 08:43 Rev Time 0.00
Received By shill Date 2011-04-06 Time 16:39 Sent To  
Notes
2011-04-06 16:39:39B--5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-14 Cont ID  
Sent By hmoser Date 2011-04-14 Time 10:51 Rev Time 0.00
Received By hmoser Date 2011-04-14 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-04-27 Cont ID  
Sent By lwagner Date 2011-04-27 Time 11:01 Rev Time 0.00
Received By lwagner Date 2011-04-27 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-04-11 Cont ID  
Sent By lwagner Date 2011-04-11 Time 11:31 Rev Time 0.00
Received By lwagner Date 2011-04-11 Time 10:25 Sent To  
Notes
2011-04-11 11:26:37FBC PLUMBING 2007 PLAN REVIEW #1
 DENIED:
  
 1. 106.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW CRITERIA.
 WATER SUPPLY PIPING REQUIRED.
  
 2. SANITARY RISER DOES NOT INCLUDE THE MOP SINK
  
 3. 11-4.19.1 MINIMUM FOR ACCESSIBLE LAV. IS 15" FROM
 SIDE WALL.
  
 NOTE FOR THE FLOOR DRAINS- 1002.4 TRAP SEALS. WHERE A
 TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP
 SEAL PRIMER VALVE SHALL BE INSTALLED. A TRAP SEAL
 PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR ASSE 1044.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-14 Cont ID  
Sent By lfranco Date 2011-04-14 Time 14:23 Rev Time 0.00
Received By lfranco Date 2011-04-14 Time 14:23 Sent To  
Notes
2011-04-21 14:24:32PLANNING AND ZONING: ****ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ***