Plan Review Details - Permit 11040127
Plan Review Stops For Permit 11040127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 09:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 07:10 Sent To  
Notes
2011-04-27 09:42:32DENIED BY BUILDING
  
 1) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION
 THAT WILL BE USED TO INSTALL THE TAMKO MODIFIED BITUMEN
 ROOF SYSTEM. SUBMIT TWO COPIES OF RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING AT THE PERIMETER AND CORNER ROOF
 AREAS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-11 Cont ID  
Sent By rlecky Date 2011-04-11 Time 09:48 Rev Time 0.00
Received By rlecky Date 2011-04-11 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2011-04-05 Time 09:39 Sent To  
Notes
2011-04-06 09:42:48R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 09:35 Sent To  
Notes
2011-05-05 09:36:23MU-2011-7690

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 07:17 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 07:17 Sent To  
Notes
2011-04-27 07:17:36NEEDS COUNTY IMPACT FEE REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 07:06 Sent To  
Notes
2011-04-27 07:10:30A SEPARATE PERMIT APPLICATION AND AN EQUIPMENT SCHEDULE
 IS REQUIRED FOR THE MINI- SPLIT SYSTEM SHOWN ON THE
 PLANS. THE LOCATION OF THE CONDENSING UNIT SHOWN ON THE
 PLANS HAS BEEN APPROVED PROVISIONLY BY ZONING.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 07:02 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 07:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-21 Cont ID  
Sent By lfranco Date 2011-04-21 Time 16:02 Rev Time 0.00
Received By lfranco Date 2011-04-21 Time 16:02 Sent To  
Notes
2011-04-21 16:05:36PLANNING AND ZONING: **** PASSED WITH PROVISO, PURSUANT
 TO SECTION 94-305(B)(4) OF THE ZLDR: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.****
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  