| 2011-04-13 08:33:26 | BUILDING PLAN REVIEW |
| | PERMIT: 11040079 |
| | ADD: 1601 BELVEDERE RD |
| | CONT: TO BE DETERMINED |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | NOTICE TO OWNER OF A CODE VIOLATION THAT EXIST IN YOUR |
| | BUILDING. THE ELEVATOR LOBBY IS MISSING SEPERATION AS |
| | REQUIRED IN THE 2007/09 FBC-B |
| | SECTION 707.14.1 ELEVATOR LOBBY OR 1 OF THE 6 |
| | EXCEPTIONS. CURRENTLY WE ARE PUTTING YOU ON NOTICE OF |
| | THIS VIOLATION. |
| | |
| | IN THE 2007/09 EXISTING BUILDING CODE SECTION 703.2.2 |
| | SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE |
| | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS |
| | 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE |
| | REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL |
| | OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. THE |
| | WORK WHICH WILL BE COVERED UNDER THIS PERMIT DOES NOT |
| | MEET THIS REQUIREMENT THUS NOT REQUIRING THE ELEVATOR |
| | LOBBIES TO BE INSTALLED AT THIS TIME. |
| | |
| | ACTION :BUILDING PROVISO: |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A2.2, A2.3 PLANS INDICATE ALL HOLES FEFT IN |
| | THE CONCRETE SLAB AFTER PIPE REMOVAL TO BE FIRE RATED- |
| | ANYTHING OVER 2 INCHES IN DIAMETER TO BE SEALED WITH |
| | CONCRETE. PLEASE REVIEW FBC-B 712.4.1 FIRE-RESISTANCE |
| | RATED ASSEMBLIES. PENETRATIONS OF THE FIRE-RESISTANCE |
| | RATED FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING |
| | MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH |
| | SECTIONS 712.4.1.1 THROUGH 712.4.1.4. PLEASE PROVIDE |
| | DOCUMENTATION FOR COMPLIANCE PROVIDE CUT SHEET FOR |
| | PRODUCTS TO BE INSTALLED. |
| | |
| | |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |