Plan Review Details - Permit 11040022
Plan Review Stops For Permit 11040022
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-04-13 Cont ID  
Sent By shill Date 2011-04-13 Time 09:40 Rev Time 0.00
Received By shill Date 2011-04-13 Time 09:40 Sent To  
Notes
2011-04-13 09:40:47PROVISO - 18" PULL SIDE CLEARANCE REQUIRED AT BATHROOMS
 FBC FIGURE 11-25

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-15 Cont ID  
Sent By rlecky Date 2011-04-05 Time 10:46 Rev Time 0.00
Received By rlecky Date 2011-04-05 Time 10:00 Sent To  
Notes
2011-04-05 12:40:45 
  
 PROVISO:
  
 PROVIDE A SINGLE LINE ELECTRIC SERVICE PLAN SHOWING
 EXISTING AND NEW PANEL BOARDS WITH FEEDERS AND CONDUIT
 SIZES. NEC 230.2
 SUMMARIZE THE LOAD CALCULATION TO VERIFY EXISTING
 CAPACITY. NEC 220
 PROVIDE A SCALE DRAWING OF THE ELECTRICAL ROOM LAYOUT
 TO ILLUSTRATE THERE ARE ADEQUATE SAFETY CLEARANCES FOR
 THE EQUIPMENT. NEC 110.26
 SECONDARY PROTECTION IS REQUIRED ON THE TRANSFORMERS
 FEEDING PANELS A, B, AND C. NEC 450.3, TABLE 450.3(B),
 240.21
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
  
 SEPARATE PERMITS ARE REQUIRED FOR THE LOW VOLTAGE
 DATA/PHONE AND FIRE ALARM SYSTEM.
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-04-07 Cont ID  
Sent By wjolin Date 2011-04-07 Time 15:32 Rev Time 0.00
Received By wjolin Date 2011-04-07 Time 13:37 Sent To  
Notes
2011-04-07 15:30:161400 NORTHPOINT PARKWAY SUITE #20
 PERMIT #11040022
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS***** DRAWINGS WILL BE
 STAMPED, INITIALED, AND DATED BY THE FIRE DEPARTMENT
 AFTER ALL BUILDING DEPARTMENT PLAN REVIEW COMMENTS HAVE
 BEEN SATISFIED.
  
 DOORS SHALL OPEN WITH NOT MORE THAN ONE RELEASING
 MECHANISM.
  
 THUMB TURN LOCKS SHALL VISIBLY INDICATE LOCKED/UNLOCKED
 STATUS.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4 INCHES IN HEIGHT AND HALF INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE NFPA
 101.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS ACCOMPANIED BY
 EXIT SIGNAGE.
  
 INDICATE WHAT MATERIALS WILL BE STORED IN STORAGE ROOM,
 HOW MATERIALS WILL BE STORED, AND STORAGE HEIGHT.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-14 Cont ID  
Sent By shill Date 2011-04-14 Time 10:29 Rev Time 0.00
Received By shill Date 2011-04-01 Time 14:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-04-12 Cont ID  
Sent By shill Date 2011-04-12 Time 14:36 Rev Time 0.00
Received By shill Date 2011-04-12 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-14 Cont ID  
Sent By shill Date 2011-04-14 Time 10:30 Rev Time 0.00
Received By shill Date 2011-04-14 Time 10:30 Sent To  
Notes
2011-04-14 10:30:14OK PER HM

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-11 Cont ID  
Sent By lwagner Date 2011-04-11 Time 09:17 Rev Time 0.00
Received By lwagner Date 2011-04-08 Time 14:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-11 Cont ID  
Sent By eschneid Date 2011-04-11 Time 11:59 Rev Time 0.50
Received By eschneid Date 2011-04-11 Time 11:59 Sent To  
Notes
2011-04-11 12:00:46PASSED
  
 1) ONLY EXTERIOR WORK IS DOOR REPLACMENT.
  
 2) DOES NOT TRIGGER 50% VALUE OF STRUCTURE.
  