| Plan Review Stops For Permit 11030743 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2011-05-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-05-04 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-05-04 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2011-05-04 13:52:53 | ***PROVISO*** | | | | | | 1. PER ARCHITECT, 2 HR OCCUPANCY SEPARATION WALL IS | | | EXISTING. PROVIDE SIGNED SEALED LETTER TO INSPECTOR. | | | | | | 2. APPLY FOR CHANGE OF OCCUPANCY FOR ADJACENT TENANT | | | (A3, GYM). | | | | | | 3. REVISION REQUIRED FOR FIRE RATED DOORS (SUBMIT | | | PRODUCT APPROVAL) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2011-04-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-04-29 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-04-29 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2011-04-29 11:15:03 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE SEE FBC EXISTING BUILDING, 804.2.2, LEVEL 3 | | | ALTERATION REQUIRES COMPLIANCE WITH FBC 907.2.2, | | | AUTOMATIC FIRE DETECTION SYSTEM REQUIRED FOR BUSINESS | | | OCCUPANCY. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-04-07 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-04-07 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2011-04-07 15:23:44 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. THE PREVIOUS OCCUPANCY CLASSIFICATION AND METHOD OF | | | COMPLIANCE WITH FBC EXISTING BUILDING CODE IS NOT | | | CLEAR. THEREFORE, PLEASE BE ADVISED THAT ALL COMMENTS | | | MAKE REFERENCE TO THE FLORIDA BUILDING CODE, BUILDING. | | | IT IS POSSIBLE THAT SOME COMMENTS MAY NOT BE APPLICABLE | | | BASED ON EXISTING BUILDING CODE COMPLIANCE METHOD | | | SELECTED. IF THIS IS THE CASE, PLEASE INCLUDE THIS | | | INFORMATION ON THE PLAN. | | | | | | 2. SHOW COMPLIANCE WITH FBC 508, MIXED USE BUILDINGS. | | | | | | 3. PROVIDE INFORMATION ON THE PLAN REGARDING USE OF | | | WAREHOUSE AND STORAGE AREAS, FBC CHAPTER 3. | | | | | | 4. THE STAIR/HANDRAIL DETAIL SHOWS A 42? GUARD, | | | HANDRAIL IS REQUIRED IN ADDITION TO THE GUARDRAIL, FBC | | | 1012.2. | | | | | | 5. PLEASE CLARIFY THE RATING OF WALL TYPE K, 1 HOUR | | | MINIMUM REQUIRED FBC 1020. | | | | | | 6. THE PLAN AND PERMIT APPLICATION ADDRESS IS FOR 510 | | | EVERNIA, BUT THE PARCEL ID IS FOR 512 EVERNIA. PLEASE | | | CORRELATE. | | | | | | 7. PROVIDE A SITE PLAN SHOWING LOCATION OF EXTERIOR | | | WALLS WITH NEW OPENINGS IN RELATION TO THE LOT LINES, | | | FBC704.8. | | | | | | 8. PROVIDE MORE INFORMATION REGARDING THE MOVEABLE | | | WALLS, FBC 505. | | | | | | 9. THE MEZZANINE NO LONGER MEETS THE DEFINITION OF A | | | MEZZANINE AS THE ROOM SIZE HAS BEEN REDUCED, SEE FBC | | | 505. PLEASE SHOW COMPLIANCE AS A 2ND STORY ON THE PLAN | | | OR REVISE PLAN TO COMPLY WITH MEZZANINE REQUIREMENTS. | | | | | | 10. THE PLAN STATES THAT ONE GARAGE DOOR OPENING WILL | | | BE CLOSED, THE OTHER DOOR IS TO REMAIN, BUT A GARAGE | | | DOOR NOA WAS SUBMITTED. PLEASE SHOW PROPOSED LOCATION. | | | | | | 11. PLEASE CLARIFY WHETHER THIS TENANT COMPRISES THE | | | ENTIRE PARCEL, AND THE WALL IS A ZERO LOT LINE FIRE | | | WALL, OR IF THERE ARE MULTIPLE TENANTS ON THIS PARCEL. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-05-02 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-02 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-05-02 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-04-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-01 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-04-01 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-05-04 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2011-05-04 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2011-05-04 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2011-03-31 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2011-03-31 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2011-03-31 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-05-05 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-04-19 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2011-04-19 16:28:59 | INCOMING SENT TO B14-. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-04-11 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-03-30 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2011-04-12 13:42:26 | PERMIT FAILED. FILED UNDER "G" | | 2011-03-30 15:02:41 | *****************EXPEDITED*************** | | | B--10 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2011-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-04-07 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-04-07 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2011-04-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-04-01 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-04-01 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2011-04-01 13:50:28 | PASS PROVISO | | | PROVIDE A LETTER FROM THE ENGINEER ON WHAT SIZE SCREWS | | | HOLD CONDENSER TO THE STAND. | | | PROVIDE PRODUCT APPROVALS ON THE FAT BOY MOUNTING | | | BRACKET. FOR FIRST INSPECTION | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-04-20 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-04-20 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-04-20 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-07 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-04-07 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-04-04 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2011-04-04 13:39:08 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. THE WATER CLOSET IN MENS ROOM #107 WILL REQUIRE A | | | VENT 901.2.1 | | | | | | 2. THE ISOMETRIC DRAWING SHOWS THE TRAPS FOR | | | LAVITORIES, SINKS, URINAL, AND EWC APPEAR TO BE | | | UNDERGROUND 1002.1 | | | | | | 3. THE WATER CLOSETS AND URINAL ARE CONNECTED TO THE | | | HOT WATER SYSTEM ON THE ISO. | | | | | | 4. THE 2 LAVITORIES IN WOMENS ROOM #106 HAVE THE HOT | | | WATER ON THE RIGHT SIDE. | | | | | | 5. THE WATER SUPPLY TO THE WATER COOLER IS NOT SHOWN. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-05-04 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2011-05-04 |
Time |
11:36 |
Rev Time |
0.75 |
| Received By |
aaponte |
Date |
2011-05-04 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2011-05-04 11:37:12 | PROVISO: PARKING LOT SHALL MEET CURRENT CODE | | | REQUIREMENT BEFORE FINAL CO IS ISSUED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-11 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2011-04-11 |
Time |
13:45 |
Rev Time |
0.30 |
| Received By |
aaponte |
Date |
2011-04-11 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2011-04-11 14:39:28 | 1. SURVEY OF THE PROPERTY SHALL BE PROVIDED. | | | 2. PROPOSED IMPROVEMENTS EXCEED THE 50% ASSESSED VALUE | | | OF THE STRUCTURES, THEREFORE THE SITE LANDSCAPE SHALL | | | BE BROUGHT INTO COMPLIANCE WITH CURRENT CODE. PLEASE | | | PROVIDE A SITE PLAN INDICATING EXISTING LANDACAPE | | | CONDITIONS AND UPGRADES TO COMPLY WITH CURRENT CODE. | | | 3. A UNITY OF TITLE SHALL BE RECORDED FOR THE TWO | | | PROPERTIES. THEY ARE CURRENTLY SHARING PARKING. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|