Plan Review Details - Permit 11030743
Plan Review Stops For Permit 11030743
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-05-04 Cont ID  
Sent By shill Date 2011-05-04 Time 13:51 Rev Time 0.00
Received By shill Date 2011-05-04 Time 13:51 Sent To  
Notes
2011-05-04 13:52:53***PROVISO***
  
 1. PER ARCHITECT, 2 HR OCCUPANCY SEPARATION WALL IS
 EXISTING. PROVIDE SIGNED SEALED LETTER TO INSPECTOR.
  
 2. APPLY FOR CHANGE OF OCCUPANCY FOR ADJACENT TENANT
 (A3, GYM).
  
 3. REVISION REQUIRED FOR FIRE RATED DOORS (SUBMIT
 PRODUCT APPROVAL)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-29 Cont ID  
Sent By shill Date 2011-04-29 Time 10:08 Rev Time 0.00
Received By shill Date 2011-04-29 Time 10:08 Sent To  
Notes
2011-04-29 11:15:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE SEE FBC EXISTING BUILDING, 804.2.2, LEVEL 3
 ALTERATION REQUIRES COMPLIANCE WITH FBC 907.2.2,
 AUTOMATIC FIRE DETECTION SYSTEM REQUIRED FOR BUSINESS
 OCCUPANCY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-07 Cont ID  
Sent By shill Date 2011-04-07 Time 15:21 Rev Time 0.00
Received By shill Date 2011-04-07 Time 15:21 Sent To  
Notes
2011-04-07 15:23:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PREVIOUS OCCUPANCY CLASSIFICATION AND METHOD OF
 COMPLIANCE WITH FBC EXISTING BUILDING CODE IS NOT
 CLEAR. THEREFORE, PLEASE BE ADVISED THAT ALL COMMENTS
 MAKE REFERENCE TO THE FLORIDA BUILDING CODE, BUILDING.
 IT IS POSSIBLE THAT SOME COMMENTS MAY NOT BE APPLICABLE
 BASED ON EXISTING BUILDING CODE COMPLIANCE METHOD
 SELECTED. IF THIS IS THE CASE, PLEASE INCLUDE THIS
 INFORMATION ON THE PLAN.
  
 2. SHOW COMPLIANCE WITH FBC 508, MIXED USE BUILDINGS.
  
 3. PROVIDE INFORMATION ON THE PLAN REGARDING USE OF
 WAREHOUSE AND STORAGE AREAS, FBC CHAPTER 3.
  
 4. THE STAIR/HANDRAIL DETAIL SHOWS A 42? GUARD,
 HANDRAIL IS REQUIRED IN ADDITION TO THE GUARDRAIL, FBC
 1012.2.
  
 5. PLEASE CLARIFY THE RATING OF WALL TYPE K, 1 HOUR
 MINIMUM REQUIRED FBC 1020.
  
 6. THE PLAN AND PERMIT APPLICATION ADDRESS IS FOR 510
 EVERNIA, BUT THE PARCEL ID IS FOR 512 EVERNIA. PLEASE
 CORRELATE.
  
 7. PROVIDE A SITE PLAN SHOWING LOCATION OF EXTERIOR
 WALLS WITH NEW OPENINGS IN RELATION TO THE LOT LINES,
 FBC704.8.
  
 8. PROVIDE MORE INFORMATION REGARDING THE MOVEABLE
 WALLS, FBC 505.
  
 9. THE MEZZANINE NO LONGER MEETS THE DEFINITION OF A
 MEZZANINE AS THE ROOM SIZE HAS BEEN REDUCED, SEE FBC
 505. PLEASE SHOW COMPLIANCE AS A 2ND STORY ON THE PLAN
 OR REVISE PLAN TO COMPLY WITH MEZZANINE REQUIREMENTS.
  
 10. THE PLAN STATES THAT ONE GARAGE DOOR OPENING WILL
 BE CLOSED, THE OTHER DOOR IS TO REMAIN, BUT A GARAGE
 DOOR NOA WAS SUBMITTED. PLEASE SHOW PROPOSED LOCATION.
  
 11. PLEASE CLARIFY WHETHER THIS TENANT COMPRISES THE
 ENTIRE PARCEL, AND THE WALL IS A ZERO LOT LINE FIRE
 WALL, OR IF THERE ARE MULTIPLE TENANTS ON THIS PARCEL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-02 Cont ID  
Sent By rlecky Date 2011-05-02 Time 11:36 Rev Time 0.00
Received By rlecky Date 2011-05-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-01 Cont ID  
Sent By rlecky Date 2011-04-01 Time 11:16 Rev Time 0.00
Received By rlecky Date 2011-04-01 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-05-04 Cont ID  
Sent By ddaniels Date 2011-05-04 Time 13:15 Rev Time 0.00
Received By ddaniels Date 2011-05-04 Time 13:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-03-31 Cont ID  
Sent By ddaniels Date 2011-03-31 Time 14:30 Rev Time 0.00
Received By ddaniels Date 2011-03-31 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-05 Cont ID  
Sent By shill Date 2011-05-05 Time 14:44 Rev Time 0.00
Received By shill Date 2011-04-19 Time 16:28 Sent To  
Notes
2011-04-19 16:28:59INCOMING SENT TO B14-. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-11 Cont ID  
Sent By jwitmer Date 2011-04-11 Time 16:28 Rev Time 0.00
Received By jwitmer Date 2011-03-30 Time 15:02 Sent To  
Notes
2011-04-12 13:42:26PERMIT FAILED. FILED UNDER "G"
2011-03-30 15:02:41*****************EXPEDITED***************
 B--10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-04-07 Cont ID  
Sent By shill Date 2011-04-07 Time 15:23 Rev Time 0.00
Received By shill Date 2011-04-07 Time 15:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-04-01 Cont ID  
Sent By hmoser Date 2011-04-01 Time 13:45 Rev Time 0.00
Received By hmoser Date 2011-04-01 Time 13:15 Sent To  
Notes
2011-04-01 13:50:28PASS PROVISO
 PROVIDE A LETTER FROM THE ENGINEER ON WHAT SIZE SCREWS
 HOLD CONDENSER TO THE STAND.
 PROVIDE PRODUCT APPROVALS ON THE FAT BOY MOUNTING
 BRACKET. FOR FIRST INSPECTION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-04-20 Cont ID  
Sent By lwagner Date 2011-04-20 Time 12:30 Rev Time 0.00
Received By lwagner Date 2011-04-20 Time 11:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-04-07 Cont ID  
Sent By lwagner Date 2011-04-07 Time 10:05 Rev Time 0.00
Received By lwagner Date 2011-04-04 Time 11:18 Sent To  
Notes
2011-04-04 13:39:08FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. THE WATER CLOSET IN MENS ROOM #107 WILL REQUIRE A
 VENT 901.2.1
  
 2. THE ISOMETRIC DRAWING SHOWS THE TRAPS FOR
 LAVITORIES, SINKS, URINAL, AND EWC APPEAR TO BE
 UNDERGROUND 1002.1
  
 3. THE WATER CLOSETS AND URINAL ARE CONNECTED TO THE
 HOT WATER SYSTEM ON THE ISO.
  
 4. THE 2 LAVITORIES IN WOMENS ROOM #106 HAVE THE HOT
 WATER ON THE RIGHT SIDE.
  
 5. THE WATER SUPPLY TO THE WATER COOLER IS NOT SHOWN.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-05-04 Cont ID  
Sent By aaponte Date 2011-05-04 Time 11:36 Rev Time 0.75
Received By aaponte Date 2011-05-04 Time 11:36 Sent To  
Notes
2011-05-04 11:37:12PROVISO: PARKING LOT SHALL MEET CURRENT CODE
 REQUIREMENT BEFORE FINAL CO IS ISSUED.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-04-11 Cont ID  
Sent By aaponte Date 2011-04-11 Time 13:45 Rev Time 0.30
Received By aaponte Date 2011-04-11 Time 13:44 Sent To  
Notes
2011-04-11 14:39:281. SURVEY OF THE PROPERTY SHALL BE PROVIDED.
 2. PROPOSED IMPROVEMENTS EXCEED THE 50% ASSESSED VALUE
 OF THE STRUCTURES, THEREFORE THE SITE LANDSCAPE SHALL
 BE BROUGHT INTO COMPLIANCE WITH CURRENT CODE. PLEASE
 PROVIDE A SITE PLAN INDICATING EXISTING LANDACAPE
 CONDITIONS AND UPGRADES TO COMPLY WITH CURRENT CODE.
 3. A UNITY OF TITLE SHALL BE RECORDED FOR THE TWO
 PROPERTIES. THEY ARE CURRENTLY SHARING PARKING.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.