| Plan Review Stops For Permit 11030690 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-05-03 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-03 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-05-03 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-04-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-01 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-30 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2011-04-01 10:41:41 | THE ENTRANCE DOOR TO THE SWITCHGEAR NEEDS TO SWING IN | | | THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC | | | BARS. NEC 110.26 (C)(3). | | | | | | PLEASE PROVIDE ADDITIONAL INFORMATION ON THE EXISTING | | | FEEDER SIZE FOR FLOORS 1, 2, AND 3. INDICATE THE OC | | | PROTECTION PROPOSED FOR PP3 AND PP2. OC PROTECTION FOR | | | THE EXISTING #250 KCMIL ( 255 AMPS) FEEDERS SHOULD BE | | | LIMITED TO 300 AMPS. NEC 240.6, T 310.16 | | | | | | ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-05-03 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-03 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-28 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2011-05-02 17:31:49 | TO ELECTRICAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-04-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-04-01 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-28 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2011-03-28 14:52:43 | IN ELECTRIC BOX |
|
|
|