Plan Review Details - Permit 11030690
Plan Review Stops For Permit 11030690
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-03 Cont ID  
Sent By rlecky Date 2011-05-03 Time 11:35 Rev Time 0.00
Received By rlecky Date 2011-05-03 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-01 Cont ID  
Sent By rlecky Date 2011-04-01 Time 10:36 Rev Time 0.00
Received By rlecky Date 2011-03-30 Time 12:50 Sent To  
Notes
2011-04-01 10:41:41THE ENTRANCE DOOR TO THE SWITCHGEAR NEEDS TO SWING IN
 THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC
 BARS. NEC 110.26 (C)(3).
  
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE EXISTING
 FEEDER SIZE FOR FLOORS 1, 2, AND 3. INDICATE THE OC
 PROTECTION PROPOSED FOR PP3 AND PP2. OC PROTECTION FOR
 THE EXISTING #250 KCMIL ( 255 AMPS) FEEDERS SHOULD BE
 LIMITED TO 300 AMPS. NEC 240.6, T 310.16
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-03 Cont ID  
Sent By rlecky Date 2011-05-03 Time 11:35 Rev Time 0.00
Received By rlecky Date 2011-03-28 Time 11:35 Sent To  
Notes
2011-05-02 17:31:49TO ELECTRICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-01 Cont ID  
Sent By rlecky Date 2011-04-01 Time 10:36 Rev Time 0.00
Received By rlecky Date 2011-03-28 Time 14:52 Sent To  
Notes
2011-03-28 14:52:43IN ELECTRIC BOX