Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-05-18 Cont ID  
Sent By shill Date 2011-05-18 Time 12:52 Rev Time 0.00
Received By shill Date 2011-05-18 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-18 Cont ID  
Sent By shill Date 2011-04-18 Time 10:51 Rev Time 0.00
Received By shill Date 2011-04-18 Time 10:51 Sent To  
Notes
2011-04-18 10:55:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENINGS 5, 8, 9; CONNECTION TYPE I REQUIRES A
 CONCRETE SUBSTRATE. PLEASE REVISE AND CHECK ALL.
  
 2. OPENING 9 HAS BEEN MARKED "EGRESS" ON THE
 INSTALLATION SCHEDULE. PLEASE REVISE FLOOR PLAN TO GIVE
 ROOM DESIGNATION AND DOOR TYPE AS IT APPEARS THAT YOU
 PROPOSE TO BLOCK THE "EGRESS" WITH AN ACCORDION
 SHUTTER. DOCUMENTS SUBMITTED FOR PERMIT SHOULD PROVIDE
 ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-05 Cont ID  
Sent By shill Date 2011-04-05 Time 09:48 Rev Time 0.00
Received By shill Date 2011-04-05 Time 09:48 Sent To  
Notes
2011-04-05 10:01:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE FLORIDA STATE PRODUCT APPROVAL IS NOT CURRENT,
 R2 (REVISION #2) IS THE CURRENT PRODUCT APPROVAL
 VERSION. SEE WWW.FLORIDABUILDING.ORG. IT IS NOT CLEAR
 HOW THIS AFFECTS THE PROJECT. A REVIEW HAS BEEN
 PERFORMED USING THE DOCUMENTS SUBMITTED BUT WHEN
 RESUBMITTING PLEASE REVIEW CURRENT DOCUMENTS FOR
 COMPLIANCE.
  
 2. CONNECTION TYPE A REQUIRES A CONCRETE SUBSTRATE.
 MOST PROJECTS HAVE A CONCRETE SUBSTRATE AT THE TOP,
 BLOCK SUBSTRATE AT THE BOTTOM (ALTHOUGH THIS MAY NOT BE
 THE CASE DEPENDING ON INSTALLATION METHOD). EITHER
 REVISE THE SHUTTER MOUNTING CONNECTION TYPE OR REVISE
 THE SUBSTRATE.
  
 3. A 2" EDGE DISTANCE FOR TAPCONS REQUIRE A .35 FACTOR,
 SEE SHEET 14. FOR INSTANCE, IF ANCHOR SPACING PER THE
 CHART IS 10" FOR A 3 1/2" EDGE DISTANCE, 3.5" WOULD BE
 REQUIRED FOR 2" EDGE DISTANCE (10" X .35 FACTOR).
  
 4. DESIGN PRESSURES TO MEET MINIMUM REQUIREMENTS OF FBC
 R301. THE DESIGN PRESSURE PROGRAM PRODUCED DESIGN
 PRESSURES WHICH APPEAR TO COMPLY WITH THE CODE
 REQUIREMENTS, BUT THESE NUMBERS WERE NOT USED PROPERLY
 IN THE INSTALLATION SCHEDULE. FOR INSTANCE, SEE OPENING
 6. THE PROGRAM GAVE DP OF 48.88/-53, BUT THE
 INSTALLATION SCHEDULE SPECIFIED 38/-40 (WHICH IS THE
 OPENING SIZE). OTHER OPENINGS WERE ROUNDED DOWN TO THE
 NEAREST WHOLE NUMBER, FOR INSTANCE OPENING 1 REQUIRED
 PRESSURES OF +46.96/-61.49 BUT WAS ROUNDED DOWN TO
 49/-61. IF ROUNDING IS USED, PLEASE ROUND TO THE MORE
 CONSERVATIVE WHOLE NUMBER, WHICH WOULD BE +47/-62.
  
 5. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 ***PLEASE BE ADVISED THAT IN THE FUTURE PERMITS MAY BE
 ISSUED WITH PROVISO THAT DOCUMENTS REQUIRED TO
 DEMONSTRATE CODE COMPLIANCE BUT NOT PROVIDED AT TIME OF
 SUBMITTAL MAY BE ISSUED WITH PROVISO THAT THE REQUIRED
 DOCUMENTS BE SUBMITTED AS A REVISION. ***
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-18 Cont ID  
Sent By shill Date 2011-04-18 Time 10:55 Rev Time 0.00
Received By shill Date 2011-04-12 Time 09:02 Sent To  
Notes
2011-04-13 09:02:28SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-05 Cont ID  
Sent By shill Date 2011-04-05 Time 10:01 Rev Time 0.00
Received By shill Date 2011-03-28 Time 14:23 Sent To  
Notes
2011-03-28 14:23:36SENT TO BUILDING UNDER $5000 BOX.