Plan Review Details - Permit 11030620
Plan Review Stops For Permit 11030620
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-06-28 Cont ID  
Sent By rmcdouga Date 2011-06-28 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2011-06-28 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-05-31 Cont ID  
Sent By rmcdouga Date 2011-05-31 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2011-05-31 Time 09:48 Sent To  
Notes
2011-05-31 10:01:232007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE MIAMI-DADE ONE-TIME APPROVAL NO.11-0411 FOR THE
 HORIZONTAL ROLLING WINDOW, HAS THE WRONG ADDRESS AND
 OWNERS NAME. BECAUSE THIS IS A "ONE-TIME" PRODUCT
 APPROVAL THE INFORMATION NEEDS TO BE CORRECT. DCA RULE
 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-04-05 Cont ID  
Sent By rmcdouga Date 2011-04-05 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2011-04-05 Time 16:47 Sent To  
Notes
2011-04-05 16:54:292007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT
 COVER THE 73-1/2" X 80 " OR THE 111" X 50 " HORIZONTAL
 SLIDING WINDOWS SPECIFIED ON THE FLOOR PLAN. SUBMIT
 PRODUCT APPROVALS FOR THESE SIZE WINDOWS. THE LOCAL
 PRODUCT APPROVAL WAS DENIED.
  
 2) THE STRUCTURE IS LOCATED IN 140 MPH WIND SPEED AND
 EXPOSURE CATEGORY C. HIGHLITE THE WINDOW SIZES AND
 GLASS TYPE IN THE TABLES IN THE PRODUCT APPROVALS. MAKE
 SURE THAT THE POSITIVE AND NEGATIVE PRESSURES FROM THE
 TABLES ARE HIGHER THAN THE REQUIRED DESIGN LOADS FOR
 COMPONENTS AND CLADDING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-05 Cont ID  
Sent By rbrown Date 2011-04-05 Time 12:07 Rev Time 0.00
Received By rbrown Date 2011-04-05 Time 12:07 Sent To  
Notes
2011-04-05 12:30:35THESE COMMENTS APPLY TO THE LOCAL PRODUCT APPROVAL
 APPLICATION ONLY. PLAN REVIEW COMMENTS FROM 3/31/11
 MUST ALSO BE ADDRESSED.
  
  
 LOCAL PRODUCT APPROVAL APPLICATION FOR LAWSON
 INDUSTRIES INC. ALUMINUM HORIZONTAL SLIDING WINDOW:
  
 1) APPROVED THIRD PARTY QUALITY ASSURANCE ENTITY - ITEM
 7 ON THE LOCAL PRODUCT APPROVAL APPLICATION FORM STATES
 THAT HURRICANE ENGINEERING AND TESTING INC. IS THE
 APPROVED THIRD PARTY QUALITY ASSURANCE ENTITY FOR THIS
 PRODUCT. THAT COMPANY IS NOT AN APPROVED THIRD PARTY
 QUALITY ASSURANCE ENTITY. THE COMPANY DOES NOT APPEAR
 IN THE SEARCH RESULTS FOR APPROVED THIRD PARTY QUALITY
 ASSURANCE ENTITIES ON THE FLORIDA DEPARTMENT OF
 CONSUMER AFFAIRS SEARCH WEBPAGE
 WWW.FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX
 IT IS NOTED THAT LAWSON INDUSTRIES INC. HAS MIAMI-DADE
 NOA'S FOR OTHER PRODUCTS AND HENCE HAS MIAMI-DADE
 QUALITY ASSURANCE LISTING FOR THOSE OTHER PRODUCTS. IF
 THE INTENTION IS TO SHOW MIAMI-DADE QUALITY ASSURANCE
 LISTING FOR THE HS-8700 ALUMINUM HORIZONTAL SLIDING
 WINDOW THAT IS THE SUBJECT OF THIS LOCAL PRODUCT
 APPROVAL APPLICATION THEN DOCUMENTATION STATING THAT IS
 REQUIRED FROM MIAMI-DADE BUILDING CODE COMPLIANCE
 OFFICE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF LOCAL PRODUCT APPROVAL APPLICATION REVIEW
 COMMENTS
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-31 Cont ID  
Sent By rmcdouga Date 2011-03-31 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2011-03-31 Time 09:35 Sent To  
Notes
2011-03-31 09:59:122007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE FLOOR PLAN THAT WAS SUBMITTED PROVIDES THE
 OPENING SIZES BUT DOES NOT SPECIFY THE TYPE OF WINDOW
 AT EACH LOCATION. PLEASE CORRECT.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT
 COVER THE 73-1/2" X 80 " OR THE 111" X 50 " WINDOWS
 SPECIFIED ON THE FLOOR PLAN. SUBMIT PRODUCT APPROVALS
 FOR THESE SIZE WINDOWS. IF THESE ARE WINDOWS THAT ARE
 MULLED TOGETHER, LIST THE INDIVIDUAL WINDOW SIZES AND
 SPECIFY THE NUMBER OF THEM THAT ARE MULLED TOGETHER AND
 SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS.
  
 3) THE STRUCTURE IS LOCATED IN 140 MPH WIND SPEED AND
 EXPOSURE CATEGORY C. HIGHLITE THE WINDOW SIZES AND
 GLASS TYPE IN THE TABLES IN THE PRODUCT APPROVALS. MAKE
 SURE THAT THE POSITIVE AND NEGATIVE PRESSURES FROM THE
 TABLES ARE HIGHER THAN THE REQUIRED DESIGN LOADS FOR
 COMPONENTS AND CLADDING.
  
 4) SPECIFY THE ROOM TYPES IN WHICH THE WINDOWS ARE
 LOCATED ON THE FLOOR PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-31 Cont ID  
Sent By rmcdouga Date 2011-05-31 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2011-05-20 Time 16:02 Sent To  
Notes
2011-05-20 16:02:30SENT TO MCDOUGALS'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-31 Cont ID  
Sent By rmcdouga Date 2011-03-31 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2011-03-23 Time 16:04 Sent To  
Notes
2011-03-23 16:05:17INCOMING SENT TO MISC BOX # 1. JW