Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-28 Cont ID  
Sent By rmcdouga Date 2011-04-28 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2011-04-28 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-12 Cont ID  
Sent By rmcdouga Date 2011-04-12 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2011-04-12 Time 07:26 Sent To  
Notes
2011-04-12 11:11:372007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) PROVIDE THE DESIGN CRITERIA ON THE PLANS. THE
 WIND-SPEED IS 140 MPH AND THE EXPOSURE CATEGORY IS C.
 FBC R301
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS ON THE PLANS. FBC R301.2.1
  
 3) SPECIFY THE SQUARE FOOTAGE OF THE ENCLOSED PORCH
 ADDITION ON THE PLANS.
  
 4) THE FINISH FLOOR ELEVATION IS REQUIRED TO BE A
 MINIMUM OF 4 INCHES ABOVE FINISH GRADE FOR MASONRY
 WALLS. PLEASE SPECIFY ON THE PLANS. FBC R 404.1.6
  
 5) THE SOIL IS TO BE COMPACTED AND TREATED FOR TERMITES
 AT THE NEW FOOTERS. FBC R401.2 AND R320
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 IMPACT WINDOWS THAT WILL BE INSTALLED. SPECIFY THE
 WINDOW TYPES AND SIZES ON THE PLANS. DCA RULE 9B-72
  
 7) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED IS
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT.
  
 8) THE ENERGY FORM THAT WAS SUBMITTED REQUIRES A
 MINIMUM INSULATION VALUE OF R-6 FOR THE EXTERIOR MASS
 WALLS. THE PLANS SPECIFY R-5 INSULATION. PLEASE REVISE
 PLANS.
  
 9) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-04-08 Cont ID  
Sent By rlecky Date 2011-04-08 Time 11:07 Rev Time 0.00
Received By rlecky Date 2011-04-08 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-05 Cont ID  
Sent By rlecky Date 2011-04-05 Time 08:27 Rev Time 0.00
Received By rlecky Date 2011-04-05 Time 08:27 Sent To  
Notes
2011-04-05 09:03:31PLEASE SUBMIT AN ELECTRICAL FLOOR PLAN SHOWING THE NEW
 RECEPTACLES WITH AFCI PROTECTION, GFCI PROTECTION AND
 TAMPER RESISTANT AS APPROPRIATE FOR THE INTENDED USE.
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A
 SWITCHED RECEPTACLE OR LIGHT AND A SWITCHED OUTSIDE
 LIGHT. AT LEAST ONE GFCI PROTECTED RECEPTACLE IS
 REQUIRED OUTSIDE.
  
 PROVIDE A ONE LINE ELECTRICAL SERVICE RISER DIAGRAM
 SHOWING THE SIZE OF THE EXISTING ELECTRIC SERVICE. SHOW
 LOCATION OF ELECTRICAL PANEL.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES OR A FIRE PLACE A CARBON MONOXIDE
 DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED
 FOR SLEEPING.
  
 2008 NATIONAL ELECTRIC CODE REFERENCES:
 SECTIONS 210.8, 210.12, 210.52, 210.70, 406.11
  
 2007 FLORIDA RESIDENTIAL BUILDING CODE REFERENCE:
 SECTION R313
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-28 Cont ID  
Sent By rmcdouga Date 2011-04-28 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2011-04-25 Time 15:53 Sent To  
Notes
2011-04-27 15:54:27TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-12 Cont ID  
Sent By rmcdouga Date 2011-04-12 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2011-03-21 Time 09:25 Sent To  
Notes
2011-04-05 09:09:12IN R9
2011-03-21 09:25:36SENT TO ZONING BOX.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 15:57 Sent To  
Notes
2011-04-27 15:58:05MU-2011-007187-0000
2011-04-12 07:47:01COUNTY IMPACT FEE REVIEW REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-01 Cont ID  
Sent By astelly Date 2011-04-01 Time 10:50 Rev Time 0.00
Received By astelly Date 2011-04-01 Time 10:50 Sent To  
Notes
***NONE***