| Plan Review Stops For Permit 11030471 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-05-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-02 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-02 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-04-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-14 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-14 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2011-04-14 14:16:14 | 2007 FBC W/2009 REVISIONS | | | DENIED BY BUILDING | | | | | | 1) FBC R 806.1 REQUIRES ENCLOSED RAFTER SPACES FORMED | | | WHEN CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF | | | ROOF RAFTERS TO HAVE CROSS VENTILATION OF EACH SEPARATE | | | SPACE THEREFORE A CONTINUOUS SOFFIT VENT OR OTHER | | | METHOD WILL BE REQUIRED. SEE SECTION B ON SHEET 5. | | | | | | 2) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A | | | BOND BREAK BETWEEN THE STUCCO AND THE WATER RESISTIVE | | | BARRIER. | | | | | | 3) A FOUNDATION WEEP SCREED IS REQUIRED AT THE BOTTOM | | | OF ALL FRAMED EXTERIOR STUCCO WALLS IN ACCORDANCE WITH | | | ASTM C 1063. | | | | | | 4) ASTM C 926 REQUIRES THE STUCCO APPLIED OVER METAL | | | LATH ON VERTICAL WALLS TO BE A MINIMUM OF 7/8 INCH | | | THICK. SECTION B ON SHEET 5 SPECIFIES 5/8 INCH STUCCO. | | | PLEASE CORRECT. | | | | | | 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE | | | ADDITION. | | | | | | 6) PLEASE CLARIFY THE COMPONENT AND CLADDING PRESSURES | | | THAT ARE SPECIFIED ON THE PLANS WERE DETERMINED. THE | | | STRUCTURE IS LOCATED IN 140 MPH 3 SECOND GUST WIND | | | SPEED AND EXPOSURE CATEGORY C. PROVIDE THE MEAN ROOF | | | HEIGHT, WALL ZONE AND EFFECTIVE WIND AREA USED TO | | | DETERMINE THESE PRESSURES. | | | | | | 7) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL WINDOW MULLIONS AND THE STORM PANELS THAT | | | WILL BE INSTALLED. | | | | | | 8) SUBMIT TWO COPIES OF A KEY PLAN AND AN INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. THIS IS THE LINK TO A | | | SAMPLE OF AN INSTALLATION SCHEDULE ON THE CONSTRUCTION | | | SERVICES WEB SITE HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION | | | /PDF/SCHEDULE_FOR_INSTALLATION.PDF | | | | | | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | FRENCH DOORS WITH SIDELITES ARE NOT THE ONES THAT ARE | | | SPECIFIED ON THE PLANS. THE PLANS SPECIFY MASONITE | | | INTERNATIONAL AND THE PRODUCT APPROVALS ARE FOR | | | THERMA-TRU. THE DESIGN PRESSURES FOR THE THERMA-TRU OUT | | | SWING GLAZED DOORS WITH SITELITES ARE +47,-47 PSF WHICH | | | ARE LESS THAN THE REQUIRED COMPONENT AND CLADDING | | | PRESSURES. PLEASE CORRECT. | | | | | | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SINGLE HUNG AND FIXED WINDOWS ARE NOT THE ONES THAT ARE | | | SPECIFIED ON THE PLANS. PLEASE CORRECT. NOTE: THE | | | PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 11) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH | | | COUNTY TO DETERMINE IF IMPACT FEES ARE DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-03-17 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-03-17 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-17 |
Time |
13:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-05-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-05 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-27 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-04-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-15 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-17 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2011-03-17 08:24:58 | INCOMING SENT TO R-2 BOX. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2011-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-09 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-09 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-05-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-02 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-02 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2011-04-14 08:50:39 | NEEDS COUNTY IMPACT FEE REVIEW |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
N |
Date |
2011-04-21 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-04-21 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-04-21 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2011-04-21 16:39:59 | ***LANDSCAPE NOT REQUIRED*** | | | | | | PLEASE REFER TO PERMIT NUMBER 11040362 FOR LANDSCAPE | | | PERMIT AND PLANS--RAK |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-04 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-04-04 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-04-04 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2011-04-04 15:25:24 | ***LANDSCAPE REVEIW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | 2. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE | | | SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING | | | COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR. | | | A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST | | | OF ALL LANDSCAPE MATERIALS AND LABOR SHALL BE INCLUDED | | | WITH THE APPLICATION AND TWO SETS OF PLANS. | | | | | | 3. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL | | | AREAS THAT ARE TO BE PLANTED IN A CULTIVATED LANDSCAPE, | | | IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120 | | | PERCENT COVERAGE. A SEPARATE IRRIGATION PERMIT IS | | | REQUIRED. PLEASE SUBMIT AN APPLICATION AND TWO SETS OF | | | IRRIGATION PLANS IF NO SYSTEM EXISTS OR IF THERE WILL | | | BE MODIFICATIONS MADE TO AN EXISTING SYSTEM. | | | | | | 4. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS | | | ENUMERATED IN THIS SECTION SHALL BE PART OF THE | | | LANDSCAPE PLAN. | | | | | | 5. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2011-05-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-05 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-05 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2011-05-05 15:45:40 | NEW HVAC CONTRACTOR APPLICATION AND PLANS WERE | | | SUBMITTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2011-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-04 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-03 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2011-05-04 13:48:34 | 2007 FBC W/2009 REVISIONS | | | DENIED BY MECHANICAL | | | | | | 1) THE COMPANY NAME THAT THE MECHANICAL CONTRACTOR IS | | | DOING BUSINESS AS IS NOT REGISTERED WITH THE STATE. THE | | | QUALIFIER WILL NEED TO REGISTER THE COMPANY "TOTAL | | | HEATING AND COOLING" WITH THE STATE BEFORE A MECHANICAL | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE MECHANICAL DESIGN IS REQUIRED TO BE SIGNED AND | | | SEALED BY A FLORIDA LICENSED ENGINEER OR AS ALLOWED BY | | | EXEMPTION TO FS 471.003 (H) FOR HVAC SYSTEMS NOT | | | EXCEEDING 15 TONS THE AIR-CONDITIONING CONTRACTOR | | | LICENSED UNDER FS 489. THE NAME, SIGNATURE AND LICENSE | | | NUMBER OF THE MECHANICAL CONTRACTOR OR THE TITLE BLOCK | | | SIGNATURE AND SEAL OF THE ENGINEER IS REQUIRED ON THE | | | MECHANICAL PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2011-04-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-14 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-14 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2011-04-14 10:16:28 | NO MECHANICAL PLANS WERE SUBMITTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-05-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-02 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-02 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-14 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-14 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2011-04-14 09:20:40 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE DWV ISOMETRIC DRAWING DOES NOT CORRESPOND TO THE | | | ARCHITECTURAL FLOOR PLAN. A SINGLE LAVATORY AND A WATER | | | CLOSET ARE SHOWN BETWEEN THE WASHING MACHINE AND THE | | | KITCHEN SINK ON THE PLUMBING RISER PLAN. PLEASE | | | CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-05-06 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2011-05-06 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2011-05-06 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-04-01 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2011-04-01 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2011-04-01 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2011-04-01 17:17:13 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 04.01.2011 | | | PERMIT NO.: 11030471 | | | ADDRESS: 4507 NORTH FLAGLER DRIVE | | | CONTRACTOR/CONTACT: DONALD MURRY | | | TELEPHONE NO.: 561.704.3233 | | | SCOPE OF REVIEW: ENCLOSE CARPORT AND REMODEL INTERIOR | | | AS PER PLANS. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | | SHALL BE PROVIDED SHOWING THE LOCATION OF ALL EXISTING | | | IMPROVEMENTS ON THE SITE. | | | | | | 2. AS THE PROPOSED IMPROVEMENT VALUE EXCEEDS 50 PERCENT | | | OF THE VALUE OF THE EXISTING STRUCTURE, THE SUBJECT | | | PROPERTY SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE | | | XIV (LANDSCAPING) OF THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS. A LANDSCAPE PLAN SHALL BE | | | PROVIDED INDICATING COMPLIANCE WITH SUCH PROVISIONS AND | | | ANY IMPROVEMENTS NECESSARY. | | | | | | 3. ACCORDING TO THE PALM BEACH COUNTY PROPERTY | | | APPRAISERS WEBSITE, THE NORTH PROPERTY LINE OF THE | | | SUBJECT PROPERTY APPEARS TO BE LOCATED INCORRECTLY. IT | | | ACTUALLY SHOWS THE PROPERTY LINE GOING THROUGH THE | | | MIDDLE OF THE RESIDENCE TO THE NORTH. THIS SHALL BE | | | RECTIFIED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | PLANNING AND ZONING DEPARTMENT | | | 401 CLEMATIS STREET - P.O. BOX 3366 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.CITYOFWPB.COM | | | |
|
|