Plan Review Details - Permit 11030471
Plan Review Stops For Permit 11030471
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-14 Cont ID  
Sent By rmcdouga Date 2011-04-14 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2011-04-14 Time 11:25 Sent To  
Notes
2011-04-14 14:16:142007 FBC W/2009 REVISIONS
 DENIED BY BUILDING
  
 1) FBC R 806.1 REQUIRES ENCLOSED RAFTER SPACES FORMED
 WHEN CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF
 ROOF RAFTERS TO HAVE CROSS VENTILATION OF EACH SEPARATE
 SPACE THEREFORE A CONTINUOUS SOFFIT VENT OR OTHER
 METHOD WILL BE REQUIRED. SEE SECTION B ON SHEET 5.
  
 2) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE STUCCO AND THE WATER RESISTIVE
 BARRIER.
  
 3) A FOUNDATION WEEP SCREED IS REQUIRED AT THE BOTTOM
 OF ALL FRAMED EXTERIOR STUCCO WALLS IN ACCORDANCE WITH
 ASTM C 1063.
  
 4) ASTM C 926 REQUIRES THE STUCCO APPLIED OVER METAL
 LATH ON VERTICAL WALLS TO BE A MINIMUM OF 7/8 INCH
 THICK. SECTION B ON SHEET 5 SPECIFIES 5/8 INCH STUCCO.
 PLEASE CORRECT.
  
 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION.
  
 6) PLEASE CLARIFY THE COMPONENT AND CLADDING PRESSURES
 THAT ARE SPECIFIED ON THE PLANS WERE DETERMINED. THE
 STRUCTURE IS LOCATED IN 140 MPH 3 SECOND GUST WIND
 SPEED AND EXPOSURE CATEGORY C. PROVIDE THE MEAN ROOF
 HEIGHT, WALL ZONE AND EFFECTIVE WIND AREA USED TO
 DETERMINE THESE PRESSURES.
  
 7) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AND THE STORM PANELS THAT
 WILL BE INSTALLED.
  
 8) SUBMIT TWO COPIES OF A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THIS IS THE LINK TO A
 SAMPLE OF AN INSTALLATION SCHEDULE ON THE CONSTRUCTION
 SERVICES WEB SITE HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION
 /PDF/SCHEDULE_FOR_INSTALLATION.PDF
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 FRENCH DOORS WITH SIDELITES ARE NOT THE ONES THAT ARE
 SPECIFIED ON THE PLANS. THE PLANS SPECIFY MASONITE
 INTERNATIONAL AND THE PRODUCT APPROVALS ARE FOR
 THERMA-TRU. THE DESIGN PRESSURES FOR THE THERMA-TRU OUT
 SWING GLAZED DOORS WITH SITELITES ARE +47,-47 PSF WHICH
 ARE LESS THAN THE REQUIRED COMPONENT AND CLADDING
 PRESSURES. PLEASE CORRECT.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG AND FIXED WINDOWS ARE NOT THE ONES THAT ARE
 SPECIFIED ON THE PLANS. PLEASE CORRECT. NOTE: THE
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 11) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF IMPACT FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-03-17 Cont ID  
Sent By rlecky Date 2011-03-17 Time 14:45 Rev Time 0.00
Received By rlecky Date 2011-03-17 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 08:34 Sent To  
Notes
2011-04-27 08:36:28R6
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-15 Cont ID  
Sent By rmcdouga Date 2011-04-15 Time 09:40 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 08:24 Sent To  
Notes
2011-03-17 08:24:58INCOMING SENT TO R-2 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-05-09 Cont ID  
Sent By rmcdouga Date 2011-05-09 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2011-05-09 Time 10:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 14:41 Sent To  
Notes
2011-04-14 08:50:39NEEDS COUNTY IMPACT FEE REVIEW

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-04-21 Cont ID  
Sent By rkussner Date 2011-04-21 Time 16:39 Rev Time 0.00
Received By rkussner Date 2011-04-21 Time 16:39 Sent To  
Notes
2011-04-21 16:39:59***LANDSCAPE NOT REQUIRED***
  
 PLEASE REFER TO PERMIT NUMBER 11040362 FOR LANDSCAPE
 PERMIT AND PLANS--RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-04-04 Cont ID  
Sent By rkussner Date 2011-04-04 Time 15:10 Rev Time 0.00
Received By rkussner Date 2011-04-04 Time 15:10 Sent To  
Notes
2011-04-04 15:25:24***LANDSCAPE REVEIW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR.
 A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR SHALL BE INCLUDED
 WITH THE APPLICATION AND TWO SETS OF PLANS.
  
 3. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL
 AREAS THAT ARE TO BE PLANTED IN A CULTIVATED LANDSCAPE,
 IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE. A SEPARATE IRRIGATION PERMIT IS
 REQUIRED. PLEASE SUBMIT AN APPLICATION AND TWO SETS OF
 IRRIGATION PLANS IF NO SYSTEM EXISTS OR IF THERE WILL
 BE MODIFICATIONS MADE TO AN EXISTING SYSTEM.
  
 4. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION SHALL BE PART OF THE
 LANDSCAPE PLAN.
  
 5. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 15:44 Sent To  
Notes
2011-05-05 15:45:40NEW HVAC CONTRACTOR APPLICATION AND PLANS WERE
 SUBMITTED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-05-04 Cont ID  
Sent By rmcdouga Date 2011-05-04 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2011-05-03 Time 07:06 Sent To  
Notes
2011-05-04 13:48:342007 FBC W/2009 REVISIONS
 DENIED BY MECHANICAL
  
 1) THE COMPANY NAME THAT THE MECHANICAL CONTRACTOR IS
 DOING BUSINESS AS IS NOT REGISTERED WITH THE STATE. THE
 QUALIFIER WILL NEED TO REGISTER THE COMPANY "TOTAL
 HEATING AND COOLING" WITH THE STATE BEFORE A MECHANICAL
 PERMIT CAN BE ISSUED.
  
 2) THE MECHANICAL DESIGN IS REQUIRED TO BE SIGNED AND
 SEALED BY A FLORIDA LICENSED ENGINEER OR AS ALLOWED BY
 EXEMPTION TO FS 471.003 (H) FOR HVAC SYSTEMS NOT
 EXCEEDING 15 TONS THE AIR-CONDITIONING CONTRACTOR
 LICENSED UNDER FS 489. THE NAME, SIGNATURE AND LICENSE
 NUMBER OF THE MECHANICAL CONTRACTOR OR THE TITLE BLOCK
 SIGNATURE AND SEAL OF THE ENGINEER IS REQUIRED ON THE
 MECHANICAL PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-04-14 Cont ID  
Sent By rmcdouga Date 2011-04-14 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2011-04-14 Time 10:15 Sent To  
Notes
2011-04-14 10:16:28NO MECHANICAL PLANS WERE SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-02 Cont ID  
Sent By rmcdouga Date 2011-05-02 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-04-14 Cont ID  
Sent By rmcdouga Date 2011-04-14 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2011-04-14 Time 09:05 Sent To  
Notes
2011-04-14 09:20:402007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE DWV ISOMETRIC DRAWING DOES NOT CORRESPOND TO THE
 ARCHITECTURAL FLOOR PLAN. A SINGLE LAVATORY AND A WATER
 CLOSET ARE SHOWN BETWEEN THE WASHING MACHINE AND THE
 KITCHEN SINK ON THE PLUMBING RISER PLAN. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-05-06 Cont ID  
Sent By jroach Date 2011-05-06 Time 14:37 Rev Time 0.00
Received By jroach Date 2011-05-06 Time 14:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-04-01 Cont ID  
Sent By jroach Date 2011-04-01 Time 17:17 Rev Time 0.00
Received By jroach Date 2011-04-01 Time 17:17 Sent To  
Notes
2011-04-01 17:17:13ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.01.2011
 PERMIT NO.: 11030471
 ADDRESS: 4507 NORTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: DONALD MURRY
 TELEPHONE NO.: 561.704.3233
 SCOPE OF REVIEW: ENCLOSE CARPORT AND REMODEL INTERIOR
 AS PER PLANS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED SHOWING THE LOCATION OF ALL EXISTING
 IMPROVEMENTS ON THE SITE.
  
 2. AS THE PROPOSED IMPROVEMENT VALUE EXCEEDS 50 PERCENT
 OF THE VALUE OF THE EXISTING STRUCTURE, THE SUBJECT
 PROPERTY SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE
 XIV (LANDSCAPING) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS. A LANDSCAPE PLAN SHALL BE
 PROVIDED INDICATING COMPLIANCE WITH SUCH PROVISIONS AND
 ANY IMPROVEMENTS NECESSARY.
  
 3. ACCORDING TO THE PALM BEACH COUNTY PROPERTY
 APPRAISERS WEBSITE, THE NORTH PROPERTY LINE OF THE
 SUBJECT PROPERTY APPEARS TO BE LOCATED INCORRECTLY. IT
 ACTUALLY SHOWS THE PROPERTY LINE GOING THROUGH THE
 MIDDLE OF THE RESIDENCE TO THE NORTH. THIS SHALL BE
 RECTIFIED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  