Plan Review Details - Permit 11030458
Plan Review Stops For Permit 11030458
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-29 Cont ID  
Sent By rmcdouga Date 2011-06-29 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2011-06-29 Time 11:04 Sent To  
Notes
2011-06-29 11:20:082007 FBC W/2009 REVISIONS
 2ND REVIEW
 DENIED BY BUILDING
  
 1) THE VALUE FOR THE WORK STATED ON THE APPLICATION IS
 TOO LOW. FBC 108.3 CITY AMENDMENTS STATES THAT FOR
 PERMITTING PURPOSES THE VALUATION INCLUDES THE
 STRUCTURAL, ELECTRICAL, INTERIOR FINISH, DESIGN FEES,
 LABOR AND MATERIAL COSTS, OVERHEAD AND PROFIT AS A
 CONTRACTOR WOULD CHARGE. PLEASE CORRECT THE VALUE.
  
 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS
 AND DOORS WILL NEED TO BE INCREASED TO COMPLY WITH
 EXPOSURE CATEGORY C. THE PRESSURES ON THE REVISED PLANS
 ARE INCORRECT.
  
 3) SUBMIT TWO COPIES OF ENERGY CODE COMPLIANCE FORMS
 FOR THE ADDITION. THE FORMS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE PREPARER AND THE OWNER/AGENT.
  
 4) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-28 Cont ID  
Sent By rmcdouga Date 2011-03-28 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2011-03-28 Time 15:39 Sent To  
Notes
2011-03-28 15:53:472007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE VALUE FOR THE WORK STATED ON THE APPLICATION IS
 TOO LOW. FBC 108.3 CITY AMENDMENTS STATES THAT FOR
 PERMITTING PURPOSES THE VALUATION INCLUDES THE
 STRUCTURAL, ELECTRICAL, INTERIOR FINISH, DESIGN FEES,
 LABOR AND MATERIAL COSTS, OVERHEAD AND PROFIT AS A
 CONTRACTOR WOULD CHARGE. PLEASE CORRECT THE VALUE.
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C PER
 FBC R301.2.1.4.3. PLEASE CORRECT.
  
 3) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS
 AND DOORS WILL NEED TO BE INCREASED TO COMPLY WITH
 EXPOSURE CATEGORY C.
  
 4) SUBMIT TWO COPIES OF ENERGY CODE COMPLIANCE FORMS.
 THE FORMS ARE REQUIRED TO BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER/AGENT.
  
 5) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE REQUIRED WATER RESISTIVE BARRIER
 AND THE STUCCO ON THE EXTERIOR WALLS.
  
 6) SHOW COMPLIANCE WITH ASTM C 1063 SECTION 7.11.5
 WHICH REQUIRES A FOUNDATION WEEP SCREED AT THE BOTTOM
 OF ALL FRAMED EXTERIOR STUCCO WALLS.
  
 7) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-07 Cont ID  
Sent By rlecky Date 2011-07-07 Time 12:35 Rev Time 0.00
Received By rlecky Date 2011-07-07 Time 12:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-03-17 Cont ID  
Sent By rlecky Date 2011-03-17 Time 12:41 Rev Time 0.00
Received By rlecky Date 2011-03-17 Time 11:11 Sent To  
Notes
2011-03-17 12:49:46ADDITIONAL RECEPTACLES ARE REQUIRED. THEY SHALL BE
 SPACED SO THAT AT NO POINT ALONG THE FLOOR IN ANY WALL
 IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC
 210.52 (A)(2).
 ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER.
 NEC 210-12 (B)
 ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11
 AN ELECTRICAL PERMIT IS REQUIRED FOR THIS WORK.
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-07 Cont ID  
Sent By rlecky Date 2011-07-07 Time 12:51 Rev Time 0.00
Received By rlecky Date 2011-06-27 Time 17:41 Sent To  
Notes
2011-06-27 17:42:20SENT TO SHELF R1 FOR BUILDING AND ELECTRICAL REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-14 Cont ID  
Sent By lmartine Date 2011-04-01 Time 12:28 Rev Time 0.00
Received By lmartine Date 2011-03-17 Time 08:11 Sent To  
Notes
2011-03-17 08:13:21INCOMING SENT TO R-1 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-06-29 Cont ID  
Sent By rmcdouga Date 2011-06-29 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2011-06-29 Time 10:20 Sent To  
Notes
2011-03-25 15:47:58NEEDS IMPACT FEE REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2011-04-01 Cont ID  
Sent By lfranco Date 2011-04-01 Time 15:23 Rev Time 0.00
Received By lfranco Date 2011-04-01 Time 15:23 Sent To  
Notes
***NONE***