Plan Review Details - Permit 11030438
Plan Review Stops For Permit 11030438
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-21 Cont ID  
Sent By jwitmer Date 2011-04-21 Time 09:29 Rev Time 0.55
Received By jwitmer Date 2011-04-21 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-03-31 Cont ID  
Sent By jwitmer Date 2011-03-31 Time 12:10 Rev Time 2.00
Received By jwitmer Date 2011-03-29 Time 13:31 Sent To  
Notes
2011-03-31 12:14:37BUILDING PROVISO:
 EXERCISE BATHROOM & SHOWER:
 1) TOILET TO COMPLY WITH HEIGHT REQUIREMENT 11-4.16.3
 17" TO 19" MEASURED FROM THE TOP OF THE SEAT.
  
 2) GRAB RAILS TO COMPLY WITH 11-4.16.4.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-05 Cont ID  
Sent By rlecky Date 2011-04-05 Time 15:04 Rev Time 2.00
Received By rlecky Date 2011-04-05 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-04-19 Cont ID  
Sent By mcarsill Date 2011-04-19 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2011-04-19 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-04 Cont ID  
Sent By mcarsill Date 2011-04-04 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2011-04-04 Time 15:32 Sent To  
Notes
2011-04-04 15:38:41777 SOUTH FLAGLER DRIVE, 12TH FLOOR
 PERMIT NUMBER 11030438
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. DUSTPROOF WALLS SHALL NOT BE CONSTRUCTED OF
 MATERIALS THAT ARE FLAMMABLE OR COMBUSTIBLE.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS REMODELING.
  
 4. EXISTING HORIZONTAL AND VERTICAL FIRE SEPARATIONS
 ARE TO BE MAINTAINED.
  
 5. PLEASE PROVIDE FLAMESPREAD DETAILS FOR FABRIC
 CEILING PANELS DISPLAYED ON SHEET A5.2.
  
 6. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE
 WITH ANY EXITING.
  
 7. PLEASE PROVIDE FLAMESPREAD DETAILS FOR WOOD VENEER
 WALL PANELS.
  
 8. THE INSTALLATION OF SOFFITS SHALL NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 9. ALL NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
 10. CLOSET AND OFFICE NEAR RECEPTION DESK APPEARS TO BE
 ABSENT OF FIRE SPRINKLER HEADS ON SHEET FS2.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-28 Cont ID  
Sent By rregueir Date 2011-04-28 Time 11:48 Rev Time 0.00
Received By rregueir Date 2011-04-12 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-04-07 Time   Rev Time  
Received By   Date 2011-03-15 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-04-28 Cont ID  
Sent By rregueir Date 2011-04-28 Time 11:47 Rev Time 0.00
Received By rregueir Date 2011-04-28 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-04-07 Cont ID  
Sent By rregueir Date 2011-04-07 Time 12:55 Rev Time 0.00
Received By rregueir Date 2011-04-07 Time 12:51 Sent To  
Notes
2011-04-07 12:55:08REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. IF EXHAUST FIRE DAMPER IS NEW, A FIRE AND SMOKE
 DAMPER IS REQUIRED AT THE EXHAUST SHAFT PENETRATION PER
 FBC-M 607.5.5.
  
 2. FIRE DAMPER AND FIRE/SMOKE DAMPER SYMBOLS ON THIS
 PAGE DO NOT CORRESPOND WITH THOSE USED IN THE SYMBOL
 LEGEND ON PAGE M1. PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-04-19 Cont ID  
Sent By lwagner Date 2011-04-19 Time 09:59 Rev Time 0.00
Received By lwagner Date 2011-04-19 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-03-30 Cont ID  
Sent By lwagner Date 2011-03-30 Time 09:51 Rev Time 0.00
Received By lwagner Date 2011-03-30 Time 09:21 Sent To  
Notes
2011-03-30 09:51:12FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-2 & P-3 SHOW A SINK INSIDE THE WET VENT FOR
 THE WATER CLOSET. PLEASE SHOW THE SINK DOWNSTREAM OF
 THE WET VENT.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-05-09 Cont ID  
Sent By rregueir Date 2011-05-09 Time 10:56 Rev Time 0.00
Received By rregueir Date 2011-05-09 Time 10:56 Sent To  
Notes
***NONE***