Plan Review Details - Permit 11030392
Plan Review Stops For Permit 11030392
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-01 Cont ID  
Sent By jwitmer Date 2011-04-01 Time 13:30 Rev Time 0.77
Received By jwitmer Date 2011-04-01 Time 13:30 Sent To  
Notes
2011-04-01 13:31:40BUILDING PLAN REVIEW
 PERMIT: 11030392
 ADD: 1200 7TH ST
 CONT: TBD
 TEL: (561)###-####
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY:
  
 1) 906.1 GENERAL. ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING .
 2007 FBC-B 11-4.1.6(2)
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS
 THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL
 OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD
 CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4,
 EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
 805.3 EXIT SIGNS. MEANS OF EGRESS FROM THE HIGHEST WORK
 AREA FLOOR TO THE FLOOR OF EXIT DISCHARGE SHALL BE
 PROVIDED WITH EXIT SIGNS IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING .
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-03-28 Cont ID  
Sent By rlecky Date 2011-03-28 Time 09:57 Rev Time 0.00
Received By rlecky Date 2011-03-28 Time 09:46 Sent To  
Notes
2011-03-28 09:58:17THE NEW AND EXISTING WIRING METHOD MUST COMPLY WITH THE
 OCCUPANCY TYPE. NEC 110.3

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-24 Cont ID  
Sent By wjolin Date 2011-03-24 Time 16:39 Rev Time 0.00
Received By wjolin Date 2011-03-24 Time 16:23 Sent To  
Notes
2011-03-24 16:39:211200 7TH STREET
 PERMIT #11030392
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM EXISTING
 FAMILY DWELLING TO NEW BUSINESS.
  
  
 EXITING SHALL COMPLY WITH LIFE SAFETY CODE CHAPTER 7 OF
 NFPA 101 FLORIDA EDITION 2007.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE EXIT SIGNS AND TACTILE SIGNAGE AT EXIT DOORS
 READING EXIT.
  
 COOKING EQUIPMENT SHALL BE PROTECTED WITH A FIXED FIRE
 SUPPRESSION SYSTEM.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-04-12 Time 10:34 Rev Time 0.00
Received By shill Date 2011-03-23 Time 16:14 Sent To  
Notes
2011-03-23 16:32:55INCOMING SENT TO B-3. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-04-01 Cont ID  
Sent By jwitmer Date 2011-04-01 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2011-04-01 Time 13:29 Sent To  
Notes
2011-04-01 13:30:27BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-03-28 Cont ID  
Sent By hmoser Date 2011-03-28 Time 14:22 Rev Time 0.00
Received By hmoser Date 2011-03-28 Time 14:22 Sent To  
Notes
2011-03-28 14:25:06PLANS DENIED
 NO MECHANICAL PLANS SUBMITTED . HAVE MECHANICAL
 CONTRACTOR SUBMIT PLANS WITH APPLICATION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2011-04-01 Cont ID  
Sent By lwagner Date 2011-04-01 Time 13:58 Rev Time 0.00
Received By lwagner Date 2011-04-01 Time 13:57 Sent To  
Notes
2011-04-01 13:58:32NO PLUMBING TO REVIEW AT THIS TIME

Review Stop Z ZONING
Rev No 2 Status P Date 2011-04-12 Cont ID  
Sent By jroach Date 2011-04-12 Time 09:29 Rev Time 0.00
Received By jroach Date 2011-04-12 Time 09:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-04-04 Cont ID  
Sent By lmartine Date 2011-04-04 Time 13:51 Rev Time 0.00
Received By lmartine Date 2011-04-04 Time 13:51 Sent To  
Notes
2011-04-04 13:55:25ZONING REVIEW #1 INPUT OF 'N' WAS AN ERROR, ZONING
 REVIEW IS REQUIRED. LM