Plan Review Details - Permit 11030351
Plan Review Stops For Permit 11030351
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-07-20 Cont ID  
Sent By rbrown Date 2011-07-20 Time 11:07 Rev Time 0.00
Received By rbrown Date 2011-07-20 Time 11:07 Sent To  
Notes
2011-07-20 11:08:24REVISION TO REVERSE DOOR SWING AT RADIOLOGY ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-04-27 Cont ID  
Sent By jwitmer Date 2011-04-27 Time 11:35 Rev Time 0.55
Received By jwitmer Date 2011-04-27 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-11 Cont ID  
Sent By jwitmer Date 2011-04-11 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2011-04-11 Time 09:54 Sent To  
Notes
2011-04-11 09:59:39BUILDING PLAN REVIEW
 PERMIT: 11030351
 ADD: 464 FERN ST
 CONT: TO BE DETERMINED
 TEL: (561)644-7416
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 PLANS APPEAR TO BE CODE COMPLIANT!!!
  
 1) PLANS ARE NEITHER SIGNED NOR SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) CONTRACTOR: TO BE DETERMINED, LICENSURE TO BE
 VERIFIED BEFORE ISSUANCE OF PERMIT. F S 489.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-14 Cont ID  
Sent By jwitmer Date 2011-03-14 Time 08:40 Rev Time 0.00
Received By jwitmer Date 2011-03-14 Time 11:00 Sent To  
Notes
2011-03-14 13:00:16BUILDING PLAN REVIEW
 PERMIT: 11030351
 ADD: 464 FERN ST
 CONT: TO BE DETERMINED
 TEL: (561)644-7416
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATOR???S
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIROMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIROMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
  
  
  
  
  
 1) THIS BUILDING APPEARS TO BE A CONVERSION FROM A R-3
 RESIDENCE TO AN OFFICE USE OCCUPANCY OR A CHANGE OF
 OCCUPANCY THAT TRIGGERS THE USE OF CHAPTER 9 OF
 THE2007/ 2009 FBC- EXISTING BUILDING CODE. NO RECORDS
 WERE FOUND IN THE COMPUTER BASE INDICATING A CHANGE IN
 USE PERMIT.
  
 2) 2007 EXST BLDG CODE 906.1 ACCESSIBILITY IN PORTIONS
 OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING . 912.8 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
  
 11-4.1.6 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH
 OF TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
 (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
 (IV) ACCESSIBLE TELEPHONES;
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
 PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE FROM THE PUBLIC WAY. 11-4.1.6(1)(B) .
  
 3) THIS BUILDING IS INDICATED AS A TWO STORY BUILDING
 BY THE COVER SHEET AND INTERNAL WINDER STAIR. THE PLANS
 DO NOT INDICATE ANY 2ND FLOOR INFORMATION,
 11-4.1.6(1)(III) VERTICAL ACCESSIBILITY.
  
 4) 2007/ 2009 EXST BLDG CODE 907.1 GRAVITY LOADS.
 BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED
 ON THE FLORIDA BUILDING CODE, BUILDING TABLE 1607.1
 SHALL COMPLY WITH THE GRAVITY LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 AS A R-3 RESIDENCE THE FLOOR LOAD DESIGN WOULD HAVE
 BEEN 30 PSF FOR SLEEPING AREAS AND 40 PSF FOR OTHER
 HABITABLE AREAS, FOR A BUSINESS OCCUPANCY 50 PSF WILL
 BE THE DESIGN LOAD.
 A GREATER LOAD THAN THE EXCEPTION: STRUCTURAL ELEMENTS
 WHOSE STRESS IS NOT INCREASED BY MORE THAN 5 PER CENT
 WOULD MEET THE EXCEPTION. PLEASE INDICATE COMPLIANCE
 WITH THIS SECTION, ALSO NOTE IN ROOM # 104 THE X-RAY
 EQUIPMENT AND EXTREMELY HEAVIER LOADS.
 SHEET A-102 DETAIL # 1 APPEARS TO TRY TO MEET CODE
 COMPLIANCE FOR GRAVITY LOADS BUT NO
 LIVE LOAD DESIGNS WERE PROVIDED.
  
 5) 435.5.1 SHIELDING. EACH X-RAY FACILITY SHALL HAVE
 PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO
 ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION
 DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF
 CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE . CONTACT:
 TOM TOMCZAK (904) 278-5730
 705 ROSE RD SUITE# 300
 ORANGE PARK, FL 32073
  
 6) BOTH G-101 AND A-101 INDICATE A SLOPED RAMP IN THE
 INTERIOR OF THE BUILDING BUT NO INFORMATION WAS
 PROVIDED.
 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE SHALL
 BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM RISE FOR
 RUN SHALL BE 30" (SEE FIGURE 16).
 11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH OF A
 RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-04-04 Cont ID  
Sent By rlecky Date 2011-04-04 Time 11:25 Rev Time 0.00
Received By rlecky Date 2011-04-04 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-03-18 Cont ID  
Sent By rlecky Date 2011-03-18 Time 10:30 Rev Time 0.00
Received By rlecky Date 2011-03-18 Time 08:35 Sent To  
Notes
2011-03-18 10:30:162ND REVIEW.
  
 THE ELECTRICAL PLANS ARE INCOMPLETE.
  
 INDICATE THE PROPOSED WIRING METHODS. THE PLANS SHOULD
 INCLUDE THE ELECTRICAL RISER, PANEL SCHEDULE, PANEL
 LOCATION, BRANCH CIRCUIT SIZES, SERVICE SIZE, SERVICE
 LOCATION, SERVICE RATING, ELECTRICAL LOAD CALCULATION
 AND FAULT CURRENT CALCULATION. THE EXISTING WIRING
 METHOD MUST COMPLY WITH THE OCCUPANCY TYPE. NEC 110.3
  
 PATIENT CARE AREAS AND EXAMINING ROOMS, # 103, 104,
 113, 112, 111 AND 114 SHALL PROVIDE AN EFFECTIVE
 GROUND-FAULT RETURN PATH USING METAL RACEWAYS, METALLIC
 CABLE ARMOR ASSEMBLY QUALIFIED AND LISTED AS AN
 EQUIPMENT GROUNDING METHOD. RECEPTACLES WITHIN THESE
 ROOMS ARE REQUIRED TO HAVE AN INSULATED GROUNDING
 TERMINAL. NEC 517.13 (A), (B), NEC 517.167
  
 PROVIDE THE ELECTRICAL SPECIFICATIONS, FEEDER SIZE,
 OVERCURRENT SIZE AND LISTING FOR THE X-RAY MACHINE. NEC
 110.3, 517.71
 PROVIDE THE RATING AND LOCATION OF THE X-RAY
 DISCONNECTING MEANS. NEC 517.72
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 IN ACCORDANCE WITH THE FLORIDA ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.1.2.
  
 THE SECOND FLOOR ELECTRICAL LAYOUT WAS NOT PROVIDED
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-03-15 Cont ID  
Sent By rlecky Date 2011-03-15 Time 12:28 Rev Time 0.00
Received By rlecky Date 2011-03-15 Time 12:28 Sent To  
Notes
2011-03-15 12:33:00PLANS ARE INCOMPLETE.
  
 MISSING ELECTRICAL RISER, PANEL SCHEDULE, PANEL
 LOCATION, SERVICE SIZE, SERVICE LOCATION, SERVICE
 RATING, LIGHTING, RECEPTACLES, AUTOMATIC LIGHTING
 CONTROL.
 REQUIRE ELECTRICAL SPECIFICATIONS AND LISTING FOR THE
 X-RAY MACHINE.
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-04-08 Cont ID  
Sent By wjolin Date 2011-04-08 Time 12:42 Rev Time 0.00
Received By wjolin Date 2011-04-07 Time 15:48 Sent To  
Notes
2011-04-07 17:10:46464 FERN STREET
 PERMIT #11030351
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 THE FIXED DOOR LEAF OF THE EAST EXIT SHALL BE BE MADE
 VISIBLY OBVIOUS THAT THE DOOR LEAF IS INOPERABLE AS AN
 EXIT.
  
 POST BUILDING ADDRESS ON SIDE OF BUILDING FACING FERN
 STREET. NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT
 AND SHALL CONTRAST WITH THE BACKGROUND COLOR.
  
 BUILDING SHALL BE LABELED WITH A REFLECTIVE
 WEATHERPROOF MALTESE CROSS INDICATING THE BUILDING IS
 CONSTRUCTED OF LIGHTWEIGHT FRAMING CONSTRUCTION FOR THE
 FLOOR AND ROOF ASSEMBLIES PER FLORIDA STATUTE 633.027.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE 18 INCH DEEP NONCOMBUSTIBLE DRAFTSTOPS FOR NEW
 SPRINKLER WATER CURTAIN. DRAFTSTOPS SHALL BE LOCATED ON
 THE FIRST FLOOR CEILING IMEDIATELY ADJACENT TO THE TWO
 UNENCLOSED VERTICAL OPENINGS PER NFPA 13 SECTION
 8.14.4.
  
 PROVIDE EXIT SIGNAGE ON SECOND FLOOR DIRECTING
 OCCUPANTS TO THE EXTERIOR STAIR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-18 Cont ID  
Sent By wjolin Date 2011-03-18 Time 17:09 Rev Time 0.00
Received By wjolin Date 2011-03-18 Time 16:37 Sent To  
Notes
2011-03-18 17:08:05464 FERN STREET
 PERMIT #11030351
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 241.
  
 NEW WORK SHALL COMPLY WITH THE LIFE SAFETY REQUIREMENTS
 OF THE FLORIDA FIRE PREVENTION CODE 2007 EDITION.
  
 SHEET G101 TITLED LIFE SAFETY PLAN WAS NOT PROVIDED.
  
 CLASSIFICATION OF OCCUPANCY NOT PROVIDED.
  
 NO INFORMATION ON EGRESS PROVIDED, SUCH AS STAIR
 HANDRAILS, STAIR GUARDRAILS, SLOPE OF RAMP, DOOR
 LOCKS/LATCHES, SLIP RESISTANCE ETC.
  
 EXISTING FIRE SPRINKLER SYSTEM OR FIRE ALARM SYSTEM
 INFORMATION NOT PROVIDED.
  
 INFORMATION FOR THE SECOND LEVEL FLOOR PLAN NOT
 PROVIDED.
  
 POST BUILDING ADDRESS ON SIDE OF BUILDING FACING FERN
 STREET. NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT
 AND SHALL CONTRAST WITH THE BACKGROUND COLOR.
  
 BUILDING SHALL BE LABELED WITH A REFLECTIVE
 WEATHERPROOF MALTESE CROSS INDICATING THE BUILDING IS
 CONSTRUCTED OF LIGHTWEIGHT FRAMING CONSTRUCTION FOR THE
 FLOOR AND ROOF ASSEMBLIES PER FLORIDA STATUTE 633.027.
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR MODIFICATIONS
 TO FIRE SPRINKLER OR FIRE ALARM SYSTEMS.
  
 A THOROUGH REVIEW OF THE DRAWINGS CANNOT BE COMPLETED
 UNTIL A COMPLETE PLAN SET HAS BEEN PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-03-15 Cont ID  
Sent By jpapa Date 2011-03-15 Time 14:52 Rev Time 0.00
Received By jpapa Date 2011-03-15 Time 14:52 Sent To  
Notes
2011-03-15 14:55:15PERMIT CONSISTS OF INTERIOR WORK ONLY AT THIS TIME.
 FUTURE EXTERIOR WORK WILL BE SUBJECT TO REVIEW BY HP
 PLANNER.
  
 JILLIAN PAPA
 HISTORIC PRESERVATION PLANNER
 561-822-1454

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-13 Cont ID  
Sent By lmartine Date 2011-04-13 Time 15:47 Rev Time 0.00
Received By lmartine Date 2011-04-01 Time 17:19 Sent To  
Notes
2011-04-01 17:20:16EXPEDITED B-14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-01 Cont ID  
Sent By rbrown Date 2011-03-24 Time 17:19 Rev Time 0.00
Received By rbrown Date 2011-03-10 Time 17:18 Sent To  
Notes
2011-04-01 17:19:37B-4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-03-24 Cont ID  
Sent By hmoser Date 2011-03-24 Time 15:16 Rev Time 0.00
Received By hmoser Date 2011-03-24 Time 15:16 Sent To  
Notes
2011-03-24 15:17:47NEW UP DATED PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-03-24 Cont ID  
Sent By hmoser Date 2011-03-24 Time 13:19 Rev Time 0.00
Received By hmoser Date 2011-03-24 Time 13:19 Sent To  
Notes
2011-03-24 13:22:16THERE ARE NO MECHANICAL PLANS ON MECHANICAL PAGE
 ME-102.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2011-07-12 Cont ID  
Sent By lwagner Date 2011-07-12 Time 13:17 Rev Time 0.00
Received By lwagner Date 2011-07-12 Time 13:14 Sent To  
Notes
2011-07-12 13:18:19REVISION OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-04-04 Cont ID  
Sent By lwagner Date 2011-04-04 Time 09:03 Rev Time 0.00
Received By lwagner Date 2011-04-04 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-03-21 Cont ID  
Sent By lwagner Date 2011-03-21 Time 09:55 Rev Time 0.00
Received By lwagner Date 2011-03-21 Time 09:55 Sent To  
Notes
2011-03-21 09:58:37FBC 2007PLUMBING PLAN REVIEW #2
 DENIED:
  
 1.INSTALLATION OF FIXTURES
 405.3.2 PUBLIC LAVATORIES. IN EMPLOYEE AND PUBLIC
 TOILET ROOMS, THE REQUIRED LAVATORY SHALL BE LOCATED IN
 THE SAME ROOM AS THE REQUIRED WATER CLOSET.
  
 2. PLANS ARE NOT SIGNED AND SEALED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-03-14 Cont ID  
Sent By lwagner Date 2011-03-14 Time 14:28 Rev Time 0.00
Received By lwagner Date 2011-03-14 Time 13:29 Sent To  
Notes
2011-03-14 14:28:04FBC 2007PLUMBING PLAN REVIEW #1
 DENIED:
  
 1.INSTALLATION OF FIXTURES
 405.3.2 PUBLIC LAVATORIES. IN EMPLOYEE AND PUBLIC
 TOILET ROOMS, THE REQUIRED LAVATORY SHALL BE LOCATED IN
 THE SAME ROOM AS THE REQUIRED WATER CLOSET.
  
 2. PLANS ARE NOT SIGNED AND SEALED.
  
 3. NO PLUMBING PLANS WERE SUBMITTED FOR REVIEW.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-03-15 Cont ID  
Sent By aaponte Date 2011-03-15 Time 15:18 Rev Time 0.00
Received By aaponte Date 2011-03-15 Time 15:18 Sent To  
Notes
2011-03-15 15:18:30INTERIOR WORK ONLY. ANY EXTERIOR WORK WILL REQUIRE
 ADDITIONAL REVIEW BY ZONING.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved