Plan Review Details - Permit 11030311
Plan Review Stops For Permit 11030311
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-04-21 Cont ID  
Sent By ddaniels Date 2011-04-21 Time 13:25 Rev Time 0.00
Received By ddaniels Date 2011-04-21 Time 13:25 Sent To M
Notes
2011-04-21 13:29:0904/21/11 PLANS REVIEWED BY FIRE **APPROVED**
  
 IN FUTURE ADDRESS COMMENTS TO PLANS REVIEWER. THIS PLAN
 SHALL BE APPROVED DUE TO THE AMOUNT OF SPRINKLER HEADS
 INVOLVED.
  
 CAPTAIN DERRICK DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-03-29 Cont ID  
Sent By ddaniels Date 2011-03-29 Time 15:06 Rev Time 0.00
Received By ddaniels Date 2011-03-29 Time 15:06 Sent To M
Notes
2011-03-29 15:09:0003/29/11 PLANS REVIEWED BY FIRE **DENIED**
  
 ELEVATION SITE ADDED TO PLANS DOES NOT INCLUDE THE PIPE
 SIZE.
  
 DERRICK DANIELS, CAPTAIN
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-15 Cont ID  
Sent By wjolin Date 2011-03-15 Time 13:18 Rev Time 0.00
Received By wjolin Date 2011-03-10 Time 11:27 Sent To  
Notes
2011-03-10 11:31:5103/10/11 PLANS REVIEWED BY FIRE **DENIED**
  
 PROVIDE SIDE ELEVATION
  
 CAPTAIN DERRICK DANIELS
 BUREAU OF FIRE PREVENTION
 561 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-04-22 Cont ID  
Sent By hmoser Date 2011-04-22 Time 14:38 Rev Time 0.00
Received By hmoser Date 2011-04-19 Time 10:26 Sent To  
Notes
2011-04-19 10:26:50TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-31 Cont ID  
Sent By hmoser Date 2011-03-31 Time 13:18 Rev Time 0.00
Received By hmoser Date 2011-03-28 Time 15:39 Sent To  
Notes
2011-03-28 15:40:14SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-15 Cont ID  
Sent By wjolin Date 2011-03-15 Time 13:18 Rev Time 0.00
Received By wjolin Date 2011-03-10 Time 08:11 Sent To  
Notes
2011-03-10 08:12:04IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-04-22 Cont ID  
Sent By hmoser Date 2011-04-22 Time 14:38 Rev Time 0.00
Received By hmoser Date 2011-04-22 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-03-31 Cont ID  
Sent By hmoser Date 2011-03-31 Time 13:15 Rev Time 0.00
Received By hmoser Date 2011-03-31 Time 13:15 Sent To  
Notes
2011-03-31 13:17:25PLAN DENIED
 PLEASE PROVIDE A LARGER PLAN CAN NOT SEE PIPE SIZE OR
 READ GENERAL NOTES .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-03-15 Cont ID  
Sent By hmoser Date 2011-03-15 Time 11:01 Rev Time 0.00
Received By hmoser Date 2011-03-15 Time 10:45 Sent To FIRE
Notes
2011-03-15 11:03:13PLEASE PROVIDE PIPE SIZE ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732