| 2011-03-22 16:15:13 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. CLARIFY SCOPE. APPLICATION IS FOR DOORS AND |
| | SHUTTERS, PLAN SHOWS DUMPSTER ENCLOSURE AND CANOPY, AND |
| | CANOPY PRODUCT APPROVAL WAS SUBMITTED. REMOVE |
| | UNNECESSARY DETAILS FROM THE PLAN OR REVISE THE |
| | APPLICATION. |
| | |
| | 2. DETAIL FOR "EXISTING STOREFRONT TO BE PROVIDED WITH |
| | ACCORDION SHUTTERS" DOES NOT CORRELATE WITH THE SITE |
| | PLAN. |
| | |
| | 3. PLAN SHOWS THAT A 4' DOOR WILL REPLACE A 3' EXISTING |
| | DOOR, PROVIDE A STRUCTURAL DETAIL FOR THE ENLARGED |
| | OPENING. |
| | |
| | 4. PROVIDE THE PRODUCT APPROVAL COVER SHEET FOR THE |
| | ACCORDION SHUTTERS. |
| | |
| | 5. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 6. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL |
| | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE |
| | INSTALLATION SCHEDULE, ITEM 5 ABOVE. FBC R301, FBC1609, |
| | FBC*106. |
| | |
| | 7. IT APPEARS THAT THIS APPLICATION PROPOSES COVERING |
| | EXIT DOORS WITH ACCORDION SHUTTERS. SEE FBC 1003.6, |
| | MEANS OF EGRESS CONTINUITY. THE PATH OF EGRESS TRAVEL |
| | ALONG A MEANS OF EGRESS SHALL NOT BE INTERRUPTED BY ANY |
| | BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT |
| | AS SPECIFIED IN THIS CHAPTER. |
| | |
| | |
| | |