Plan Review Details - Permit 11030257
Plan Review Stops For Permit 11030257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-17 Cont ID  
Sent By rmcdouga Date 2011-03-17 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 13:54 Sent To  
Notes
2011-03-17 16:06:34DENIED BY BUILDING
  
 1) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS
 OF +35.3 AND -47.2 PSF ARE TOO LOW FOR EXPOSURE C.
 PLEASE CORRECT.
  
 2) THE ENERGY FORM THAT WAS SUBMITTED IS NO LONGER
 ACCEPTABLE. IT WAS CHANGED BY THE 2009 REVISIONS TO THE
 ENERGY CODE. THE NEW FORM IS 1100B-08
  
 3) THE MINIMUM WALL INSULATION FOR A 2 X 6 WALL IS
 REQUIRED TO BE R-13 PER THE PRESCRIPTIVE METHOD AND
 ENERGY FORM 1100B-08.
  
 4) ITEM # 4 ON SHEET 1 SHOULD REFERENCE THE 2008 NEC
 AND NOT THE 2005 EDITION. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-03-18 Cont ID  
Sent By rmcdouga Date 2011-03-18 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2011-03-18 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-09 Cont ID  
Sent By rmcdouga Date 2011-03-09 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2011-03-09 Time 08:24 Sent To  
Notes
2011-03-09 08:37:13R-9

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2011-03-18 06:58:24NEEDS COUNTY IMPACT FEE REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-03-17 Cont ID  
Sent By rmcdouga Date 2011-03-17 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-03-17 Cont ID  
Sent By rmcdouga Date 2011-03-17 Time 12:18 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 12:18 Sent To  
Notes
2011-03-17 12:19:26PLUMBING PERMIT IS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-03-24 Cont ID  
Sent By eschneid Date 2011-03-24 Time 16:03 Rev Time 1.00
Received By eschneid Date 2011-03-24 Time 16:03 Sent To  
Notes
2011-03-24 16:22:47FAILED
  
 1) TABLE XV-6 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS REQUIRE THAT SINGLE FAMILY RESIDENCES HAVE
 TWO (2) PARKING SPACES. SECTION 94-482 OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS REQUIRES THAT THE
 PARKING FOR SINGLE FAMILY RESIDENCES BE LOCATED ON THE
 PROPERTY WITH THE HOUSE. THE ENCLOSURE OF THE CARPORT
 FOR LIVING SPACE WILL REMOVE ONE (1) PARKING SPACE FROM
 THE PROPERTY. TWO (2) COPIES OF A RECENT SURVEY, LESS
 THAN ONE YEAR OLD, ARE REQUIRED TO VERIFY THAT THERE
 ARE CURRENTLY PARKING SPACES ON-SITE.
  
 2) STAFF HAS COMPARED THE 2007 AERIAL OF THE PROPERTY
 AND THE SURVEY PROVIDED WITH THE 2001 FENCE PERMIT WITH
 A CURRENT PICTURE OF THE PROPERTY AND NOTED THAT THE
 DRIVEWAY HAS BEEN EXPANDED ON EITHER SIDE WITH
 CONCRETE. THE CITY HAS NO RECORD OF PERMITS FOR THE
 ADDITIONAL CONCRETE WORK DONE TO THE SITE. BASED ON THE
 2001 SURVEY, THE SITE WAS DEFICIENT IN THE FRONT YARD
 LANDSCAPE REQUIRED BY SECTION 94-482 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS; THEREFORE, THE ADDITIONAL
 CONCRETE INSTALLED WITHOUT A PERMIT IS NOT ALLOWED.
 ADDITIONALLY, NO NEW CONCRETE OR ASPHALT MAY BE
 INSTALLED IN THE FRONT YARD FOR ADDITIONAL PARKING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.