Plan Review Details - Permit 11030249
Plan Review Stops For Permit 11030249
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-17 Cont ID  
Sent By jwitmer Date 2011-03-17 Time 15:45 Rev Time 1.30
Received By jwitmer Date 2011-03-17 Time 15:45 Sent To  
Notes
2011-03-17 15:49:18BUILDING PROVISO:
 SHEET A200.5 TYPICAL KIOSK DETAILS INDICATE 5/8 " CDX
 PLYWOOD SHEATHING, DISCREPANCY WITH ROOFING NOA PRODUCT
 APPROVAL 10-0920.06 FOR RIFFE MEGALOC 2.0 24 GA STEEL
 PANEL OVER STEEL DECK , SUBMIT REVISION BEFORE ROOF
 SHEATHING INSPECTION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-21 Cont ID  
Sent By rlecky Date 2011-03-21 Time 08:06 Rev Time 0.00
Received By rlecky Date 2011-03-21 Time 07:54 Sent To  
Notes
2011-03-21 08:06:57PULLED ELECTRIC SHEETS FROM ABANDONED FILE PER
 CONTRACTORS REQUEST AND ADDED THEM TO THE NEW
 SUBMITTAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-03-18 Cont ID  
Sent By rlecky Date 2011-03-18 Time 15:25 Rev Time 0.00
Received By rlecky Date 2011-03-18 Time 11:53 Sent To  
Notes
2011-03-18 15:25:04THE ELECTRICAL PLANS ARE INCOMPLETE.
  
 THE PLANS SHOULD INCLUDE THE ELECTRICAL RISER, PANEL
 SCHEDULE, PANEL LOCATION, BRANCH CIRCUIT SIZES, SERVICE
 SIZE, SERVICE LOCATION, SERVICE RATING, ELECTRICAL LOAD
 CALCULATION AND FAULT CURRENT CALCULATION.
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-05-03 Cont ID  
Sent By lmartine Date 2011-05-02 Time 12:43 Rev Time 0.00
Received By lmartine Date 2011-05-02 Time 12:43 Sent To  
Notes
2011-05-03 12:44:16SEE PLANS FOR MANNY'S SIGNATURE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-03-25 Cont ID  
Sent By wjolin Date 2011-03-25 Time 14:54 Rev Time 0.00
Received By wjolin Date 2011-03-25 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-03 Cont ID  
Sent By lmartine Date 2011-05-02 Time 12:44 Rev Time 0.00
Received By lmartine Date 2011-03-09 Time 14:06 Sent To  
Notes
2011-03-09 14:06:46C-4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-04-29 Cont ID  
Sent By hmoser Date 2011-04-29 Time 07:13 Rev Time 0.00
Received By hmoser Date 2011-04-29 Time 07:13 Sent To  
Notes
2011-04-29 07:17:13MECHANICAL PLANS SUBMITTED UNDER A SEPARATE PERMIT #
 11040591
 PLAN REVIEW BY HAROLD MOSER 546-805-6732
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-04-05 Cont ID  
Sent By hmoser Date 2011-04-05 Time 07:43 Rev Time 0.00
Received By hmoser Date 2011-04-05 Time 07:43 Sent To  
Notes
2011-04-05 07:46:52THERE ARE NO MECHANICAL PLANS SUBMITTED . HAVE
 MECHANICAL CONTRACTOR PROVIDE PLANS AT TIME OF
 APPLICATION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status P Date 2011-03-24 Cont ID  
Sent By eschneid Date 2011-03-24 Time 15:00 Rev Time 0.75
Received By eschneid Date 2011-03-24 Time 15:00 Sent To  
Notes
2011-03-24 15:15:01IF TREES ARE TO BE REMOVED AND/OR RELOCATED THEN A TREE
 ALTERATION PERMIT FROM THE PLANNING & ZONING DEPARTMENT
 IS REQUIRED AND A LANDSCAPE PERMIT IS REQUIRED.
  
  