Plan Review Details - Permit 11030186
Plan Review Stops For Permit 11030186
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-04-12 Cont ID  
Sent By shill Date 2011-04-12 Time 09:24 Rev Time 0.00
Received By shill Date 2011-04-12 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-08 Cont ID  
Sent By shill Date 2011-03-08 Time 08:56 Rev Time 0.00
Received By shill Date 2011-03-08 Time 08:56 Sent To FIRE
Notes
2011-03-08 09:00:17****CORRECTIONS****
 ****REVISED 3/31****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGN PRESSURES CANNOT BE DETERMINED BASED ON
 INFORMATION PROVIDED, FBC1609. PROVIDE BUILDING HEIGHT
 AND A FLOOR PLAN SHOWING LOCATION OF PROPOSED DOOR.
  
 2. THE FLOOR PLAN SHOWS A 90 MINUTE FIRE RATED DOOR
 PROPOSED.
  
 IT APPEARS THAT A RATED DOOR IS NOT REQUIRED FOR THIS
 LOCATION. IF THIS IS THE CASE, PLEASE REMOVE THIS
 REQUIREMENT FROM THE FLOOR PLAN (IF APPLICABLE) AND
 APPLICATION DESCRIPTION. IF A FIRE RATED DOOR IS
 REQUIRED, PLEASE PROVIDE MORE INFORMATION REGARDING
 DOOR INCLUDING LOCATION CONDITIONS WHICH WOULD REQUIRE
 FIRE RATING (CORRIDOR, EXIT, ETC.), FIRE RATING
 REQUIREMENT, AND DOOR HARDWARE INFORMATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-04-12 Cont ID  
Sent By wjolin Date 2011-04-12 Time 10:55 Rev Time 0.00
Received By wjolin Date 2011-04-12 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-10 Cont ID  
Sent By wjolin Date 2011-03-10 Time 13:50 Rev Time 0.00
Received By wjolin Date 2011-03-10 Time 13:48 Sent To  
Notes
2011-03-10 13:49:553915 SOUTH FLAGLER DRIVE #316
 PERMIT #11030186
  
 REFER TO BUILDING REVIEW COMMENTS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-12 Cont ID  
Sent By wjolin Date 2011-04-12 Time 10:55 Rev Time 0.00
Received By wjolin Date 2011-04-12 Time 09:09 Sent To  
Notes
2011-04-12 09:09:47TO FIRE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-10 Cont ID  
Sent By shill Date 2011-03-10 Time 13:51 Rev Time 0.00
Received By wjolin Date 2011-03-08 Time 09:01 Sent To  
Notes
2011-03-08 09:01:27TO FIRE
  