Plan Review Details - Permit 11030102
Plan Review Stops For Permit 11030102
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-09-01 Cont ID  
Sent By ddaniels Date 2011-09-01 Time 10:52 Rev Time 0.00
Received By ddaniels Date 2011-09-01 Time 10:52 Sent To M
Notes
2011-09-01 10:54:3209/01/2011 AS BUILT PLANS REVIEWED BY FIRE **APPROVED**
 SENT TO MECHANICAL FOR STAMPS AND SIGNATURE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-28 Cont ID  
Sent By ddaniels Date 2011-03-28 Time 10:03 Rev Time 0.00
Received By ddaniels Date 2011-03-28 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-03-15 Cont ID  
Sent By wjolin Date 2011-03-15 Time 17:47 Rev Time 0.00
Received By wjolin Date 2011-03-15 Time 17:27 Sent To M
Notes
2011-03-15 17:47:01306 CLEMATIS STREET
 PERMIT #11030102
 MASTER #11010398
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 SIGNIFICANT FLOOR PLAN CHANGES HAVE OCCURED UNDER THE
 MASTER PERMIT THAT WILL EFFECT THE SPRINKLER DESIGN AND
 HYDRAULIC CALCULATIONS.
  
 PROVIDE LOCKABLE KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGNAGE FOR FIRE
 DEPARTMENT CONNECTION.
  
 VERIFY TAMPER SWITCHES ARE SUPERVISING THE CONTROL
 VALVES ON THE BACKFLOW PREVENTER.
  
 VERIFY EXISTING SPRINKLERS NOT BEING RELOCATED ARE
 QUICK RESPONSE TYPE.
  
 REROUTE EXISTING FOUR INCH CROSS MAIN TO AVOID STAIR
 ENTRY AND EXIT PENETRATIONS.
  
 A CEILING HEIGHT OF 14 FEET CORRESPONDS TO A HYDRAULIC
 AREA OF AT LEAST 990 SQUARE FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-28 Cont ID  
Sent By ddaniels Date 2011-03-28 Time 10:03 Rev Time 0.00
Received By ddaniels Date 2011-03-24 Time 14:40 Sent To  
Notes
2011-03-24 14:41:32IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-21 Cont ID  
Sent By hmoser Date 2011-03-21 Time 10:33 Rev Time 0.00
Received By hmoser Date 2011-03-04 Time 14:59 Sent To  
Notes
2011-03-04 14:59:16IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-03-21 Cont ID  
Sent By hmoser Date 2011-03-21 Time 10:33 Rev Time 0.00
Received By hmoser Date 2011-03-21 Time 09:09 Sent To  
Notes
***NONE***