Plan Review Details - Permit 11030033
Plan Review Stops For Permit 11030033
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-22 Cont ID  
Sent By shill Date 2011-03-22 Time 14:23 Rev Time 0.00
Received By shill Date 2011-03-22 Time 14:23 Sent To  
Notes
2011-03-22 14:49:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE ENGINEERING FOR THE PROPOSED WALL, FS471,
 FBC R 301. RESISTANCE TO WIND LOADS HAS NOT BEEN
 DEMONSTRATED. CALCULATIONS MAY BE REQUIRED.
  
 2. WIND DESIGN CRITERIA SHOULD BE INCLUDED ON THE PLAN.
  
 3. SHOW THE FOOTER IN RELATION TO THE PROPERTY LINE.
 THE PROPOSED IMPROVEMENT CANNOT ENCROACH THE PROPERTY
 LINE.
  
 4. PLANS ARE TO BE ARCHITECTURAL QUALITY TO SCALE, FBC
 106. INCLUDE STRUCTURAL DETAIL FOR REBAR, ONE
 CONTINUOUS PIECE APPEARS TO BE SHOWN, FBC R 301.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-22 Cont ID  
Sent By shill Date 2011-03-22 Time 14:49 Rev Time 0.00
Received By shill Date 2011-03-02 Time 06:49 Sent To  
Notes
2011-03-02 06:49:29SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2011-03-09 Cont ID  
Sent By ajones Date 2011-03-09 Time 09:02 Rev Time 0.00
Received By ajones Date 2011-03-02 Time 14:20 Sent To  
Notes
***NONE***