Plan Review Details - Permit 11020678
Plan Review Stops For Permit 11020678
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-04-20 Cont ID  
Sent By jgomez Date 2011-04-20 Time 09:17 Rev Time 0.00
Received By jgomez Date 2011-04-20 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-02 Cont ID  
Sent By jgomez Date 2011-03-02 Time 09:46 Rev Time 0.00
Received By jgomez Date 2011-03-02 Time 09:46 Sent To  
Notes
2011-03-02 09:48:16RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO PERMIT APPLICATION REPAIRS ARE 30% OF
 THE ENTIRE ROOF. 30% OF ROOF AREA IS NOT ALLOWED BY
 SEC. 611.1.1 OF 2007 FLORIDA BUILDING CODE-EXISTING
 BUILDING CODE. NEED TO RE-ROOF ENTIRE ROOF.
  
 2- ADJUST VALUATION TO INCLUDE TOTAL RE-ROOF. SEC.
 108.3 CITY AMENDMENTS TO FBC.
  
 3- ACCORDING TO MIAMI-DADE WEBSITE NOA 09-0331.10
 SUBMITTED FOR THE CONCRETE ROOF TILE WAS SUPERSEDED.
 VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-01 Cont ID  
Sent By jgomez Date 2011-03-01 Time 09:28 Rev Time 0.00
Received By jgomez Date 2011-03-01 Time 09:28 Sent To  
Notes
2011-03-01 10:09:07RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO CONTRACTOR'S MESSAGE LEFT ON MY VOICE
 MAIL, THERE WAS A MISTAKE ON THE PERMIT APPLICATION.
 REPAIRS SHALL BE 30% NOT 30 SQUARES. 30% OF ROOF AREA
 IS NOT ALLOWED BY SEC. 611.1.1 OF 2007 FLORIDA BUILDING
 CODE-EXISTING BUILDING CODE. NEED TO RE-ROOF ENTIRE
 ROOF.
  
 ***NOTE: CONTRACTOR TO REVISE PERMIT APPLICATION AS
 REQUIRED TO STATE 30% ROOF REPAIRS.
  
  
 2- ADJUST VALUATION TO INCLUDE TOTAL RE-ROOF. SEC.
 108.3 CITY AMENDMENTS TO FBC.
  
 3- ACCORDING TO MIAMI-DADE WEBSITE NOA 09-0331.10
 SUBMITTED FOR THE CONCRETE ROOF TILE WAS SUPERSEDED.
 VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-20 Cont ID  
Sent By jgomez Date 2011-04-20 Time 09:17 Rev Time 0.00
Received By jgomez Date 2011-04-20 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-01 Cont ID  
Sent By jgomez Date 2011-03-01 Time 09:28 Rev Time 0.00
Received By jgomez Date 2011-03-01 Time 09:28 Sent To  
Notes
***NONE***