Plan Review Details - Permit 11020607
Plan Review Stops For Permit 11020607
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-22 Cont ID  
Sent By rmcdouga Date 2011-03-22 Time 11:41 Rev Time 0.00
Received By rmcdouga Date 2011-03-22 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-03-09 Cont ID  
Sent By rmcdouga Date 2011-03-09 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2011-03-09 Time 15:42 Sent To  
Notes
2011-03-09 15:57:152007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE POOL BARRIER ALARMS ARE REQUIRED TO COMPLY WITH
 FBC R4101.17.1.9 AND UL2017. SUBMIT SPECIFICATIONS FOR
 THE ALARMS WITH THE LISTING INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-03-09 Cont ID  
Sent By rmcdouga Date 2011-03-09 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2011-03-09 Time 15:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2011-03-09 Cont ID  
Sent By rmcdouga Date 2011-03-09 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2011-03-09 Time 15:40 Sent To  
Notes
2011-03-09 15:41:19A SEPARATE PERMIT APPLICATION AND ISOMETERIC DRAWINGS
 ARE REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-04-25 Cont ID  
Sent By rmcdouga Date 2011-04-25 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2011-04-21 Time 10:20 Sent To  
Notes
2011-04-21 10:58:51TO RM DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-04-04 Cont ID  
Sent By rmcdouga Date 2011-04-04 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-03-30 Time 15:12 Sent To  
Notes
2011-03-30 15:13:10INCOMING SENT TO ROBERT MCDOUGALS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-23 Cont ID  
Sent By rmcdouga Date 2011-03-23 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2011-03-21 Time 09:52 Sent To  
Notes
2011-03-21 09:52:53SENT TO R. MCDOUGAL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-10 Cont ID  
Sent By rmcdouga Date 2011-03-10 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2011-02-24 Time 09:01 Sent To  
Notes
2011-02-25 09:02:04ZONING

Review Stop P PLUMBING
Rev No 4 Status P Date 2011-04-25 Cont ID  
Sent By rmcdouga Date 2011-04-25 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2011-04-25 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2011-04-04 Cont ID  
Sent By rmcdouga Date 2011-04-04 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2011-04-01 Time 10:34 Sent To  
Notes
2011-04-04 15:43:382007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE WATER VELOCITY SPECIFIED FOR THE FEATURE PUMP IS
 INCORRECT. THE RETURN LINE SIZE IS LISTED AS 1.5 INCHES
 AND THE FLOW IS 80 GPM. THIS PRODUCES A WATER VELOCITY
 OF 12.59 FEET PER SECOND NOT 2.4. FBC R4101.6.3 LIMITS
 THE VELOCITY TO 10 FEET PER SECOND FOR PRESSURE PIPING.
 PLEASE CORRECT.
  
 2) THE WATER VELOCITY IN THE 2 INCH SPA DRAIN TRUNK IS
 GIVEN AS 8.2 FEET/SECOND. THE MAXIMUM VELOCITY ALLOWED
 BY THE CODE IS 8 FEET/SECOND. PLEASE CORRECT.
  
 3) THE WATER VELOCITY SPECIFIED FOR THE SPA PUMP IS
 INCORRECT. THE RETURN LINE SIZE IS LISTED AS 2 INCH AND
 THE FLOW IS 90 GPM. THIS PRODUCES A WATER VELOCITY OF
 9.2 FEET PER SECOND NOT 1.5. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-03-22 Cont ID  
Sent By rmcdouga Date 2011-03-22 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2011-03-22 Time 10:34 Sent To  
Notes
2011-03-22 15:14:572007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR EACH OF THE SYSTEMS OR DESIGN THE
 SYSTEM FOR THE MAXIMUM FLOW RATE OF THE PUMP. THE
 REVISED PLANS SPECIFY A TDH OF 30FT FOR THE 1 HP
 FEATURE PUMP SYSTEM AND 56 FT FOR THE 1.5 HP PUMP
 SYSTEM. SUBMIT SIGNED AND SEALED CALCULATIONS SHOWING
 HOW THESE TWO TDH WERE DETERMINED. THERE WERE NO
 CALCULATIONS SUBMITTED INDICATING HOW THE TOTAL DYNAMIC
 HEAD FOR EACH OF THE SYSTEMS WAS DETERMINED. UNLESS THE
 TDH CALCULATIONS ARE SUBMITTED THE MAXIMUM CAPACITY OF
 THE PUMPS WILL BE USED TO DETERMINE THE WATER VELOCITY
 IN THE PIPES.
  
 2) ANSI/APSP-7 2006 SECTION 4.4 LIMITS THE WATER
 VELOCITY IN BRANCH SUCTION PIPING TO A MAXIMUM OF 6
 FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED. THE
 TABLES ON SHEET 3 OF THE REVISED DRAWINGS LIST THE FLOW
 AND VELOCITY WITH BOTH BRANCHES UNBLOCKED. HOWEVER, THE
 WATER VELOCITY IS LESS THAN 6 AT THE FLOW RATES/GPM
 SPECIFIED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-03-10 Cont ID  
Sent By rmcdouga Date 2011-03-10 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2011-03-10 Time 08:09 Sent To  
Notes
2011-03-10 13:46:262007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY A 1.5 HP JANDY STEALTH SERIES
 VARIABLE SPEED PUMP WHICH REQUIRES THE MAXIMUM FLOW
 RATE OF THE PUMP TO BE USED IN CALCULATIONS. THE PIPING
 SCHEMATIC SHOWS 2.5" PIPE ON THE SPA SUCTION LINES AND
 THE MAIN DRAIN DETAIL SPECIFIES 2.5 " BRANCH PIPING
 BETWEEN THE TWO MAIN DRAINS. PLEASE CLARIFY. THE SPA
 MAIN DRAIN BRANCH PIPING BETWEEN THE TWO MAIN DRAINS IS
 LIMITED TO A MAXIMUM OF 6 FEET PER SECOND WHEN ONE OF
 THE PAIR IS BLOCKED PER ANSI/APSP-7. MAXIMUM OUTLET
 SIZE ON THE MANUFACTURED MAIN DRAIN SUMPS IS TYPICALLY
 2-1/2" AND IS CONSIDERED PART OF THE MAIN DRAIN BRANCH
 PIPING PER DEFINITION 3.5 OF ANSI/APSP-7 2006.
 THEREFORE, THE MAXIMUM BRANCH PIPING SIZE IS 2-1/2".
 UNLESS TDH CALCULATIONS ARE SUBMITTED THE MAXIMUM FLOW
 RATE OF THE PUMP WILL BE USED TO DETERMINE THE WATER
 VELOCITY. PLEASE SHOW HOW THE POOL PIPING WILL COMPLY
 WITH ANSI/APSP-7 SECTION 4.4 AND FBC R4101.6.3.
  
 2) THE SIZE OF THE BRANCH PIPING AT THE TWO SIDE DRAINS
 FOR THE SHEER DESCENT FEATURE IS NOT SPECIFIED. PROVIDE
 THE PUMP SPECS. WITH THE PUMP CURVE AND TDH
 CALCULATIONS TO SHOW COMPLIANCE FOR THIS SYSTEM AS
 WELL.
  
 3) SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR THE POOL
 PUMP INCLUDING THE PUMP CURVE.
  
 4) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR THE SYSTEM OR DESIGN THE SYSTEM FOR
 THE MAXIMUM FLOW RATE OF THE PUMP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-03-07 Cont ID  
Sent By lfranco Date 2011-03-07 Time 17:46 Rev Time 0.00
Received By lfranco Date 2011-02-28 Time 17:06 Sent To  
Notes
2011-03-07 17:48:45PASSED WITH PROVISO: **** PASSED WITH PROVISO: PURSUANT
 TO SECTION 94-305(B)(4) OF THE ZLDR: MECHANICAL (POOL)
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK. ****