Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-04 Cont ID  
Sent By jgomez Date 2011-03-04 Time 09:54 Rev Time 0.00
Received By jgomez Date 2011-03-04 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-23 Cont ID  
Sent By rmcdouga Date 2011-02-23 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2011-02-23 Time 15:54 Sent To  
Notes
2011-02-23 16:18:472007 FBC W/2009 REVISIONS
 RE-ROOF
  
 1) THE BUR SYSTEM THAT WAS SELECTED FROM NOA #
 08-0729.07 HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF
 WHICH IS TOO LOW AT THE CORNER AND PERIMETER AREAS FOR
 A WIND SPEED OF 140 MPH IN EXPOSURE C. GENERAL
 LIMITATION #9 DOES IS SPECIFIED FOR THIS SYSTEM AND
 DOES NOT ALLOW ENHANCED FASTENING FOR INCREASING
 UPLIFT. PLEASE SELECT AN APPROPRIATE SYSTEM.
  
 2) LIMITATION #7 ALLOWS ENHANCED FASTENING WITH RAS 117
 CALCULATIONS FROM A FLORIDA REGISTERED ARCHITECT,
 ENGINEER OR REGISTERED ROOF CONSULTANT.
  
 3) IF THE BUR IS BEING INSTALLED ON AN INSULATED DECK
 SELECT THE APPROPRIATE SYSTEM FROM THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW