| 2011-02-28 10:03:26 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. REVISE EXPOSURE CATEGORY OR HAVE ENGINEER PROVIDE |
| | CALCULATIONS FOR USE OF EXPOSURE B PRESSURES. FBC1609, |
| | FBC R301.2.1.4. NOTE THAT THE CODE CHANGED EFFECTIVE |
| | MARCH 1, 2009. |
| | |
| | FBC 1609.4 EXPOSURE CATEGORY. FOR EACH WIND DIRECTION |
| | CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY |
| | REFLECTS THE CHARACTERISTICS OF GROUND SURFACE |
| | IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT |
| | WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED. |
| | FOR A SITE LOCATED IN THE TRANSITION ZONE BETWEEN |
| | CATEGORIES, THE CATEGORY RESULTING IN THE LARGEST WIND |
| | FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN OF |
| | VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE FROM |
| | NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM |
| | CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE |
| | EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER |
| | STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF |
| | THE FOLLOWING CATEGORIES: |
| | |
| | EXCEPTION: AN INTERMEDIATE EXPOSURE BETWEEN THE |
| | EXPOSURE CATEGORIES DEFINED IS PERMITTED IN A |
| | TRANSITION ZONE PROVIDED THAT IT IS DETERMINED BY A |
| | RATIONAL ANALYSIS METHOD. |
| | |
| | |
| | |
| | |