Plan Review Details - Permit 11020341
Plan Review Stops For Permit 11020341
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-22 Cont ID  
Sent By rlecky Date 2011-02-22 Time 08:33 Rev Time 0.00
Received By rlecky Date 2011-02-22 Time 07:49 Sent To  
Notes
2011-02-22 08:34:32DESCRIPTION OF WORK IS INCOMPLETE AND INADEQUATELY
 DETAILED. PLEASE PROVIDE ADDITIONAL INFORMATION.
  
 INDICATE THE SIZE OF THE EXISTING SERVICE. NEC 230.31
 SPECIFY THE TYPE OF CONDUIT TO BE UTILIZED. NEC 110.8
 INDICATE THE SIZE AND TYPE OF NEW SERVICE FEEDERS. NEC
 310.8, 310.16
 PROVIDE A PLAN SHOWING HOW THE NEW SERVICE WILL BE
 SUPPORTED. NEC 110.13
 SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE) REQUIRED FOR
 THE SERVICE. NEC 110.20
 PROVIDE CLARIFICATION AS TO THE LOCATION AND REQUIRED
 ACCESS TO THE MAIN ELECTRIC DISCONNECT. NEC 230.70
 SHOW HOW THE NEW SERVICE WILL BE GROUNDED. NEC 250.20,
 250.32 (A) AND (B), TABLE 250.66
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC
 250.94
  
 NOTE: THE NEW LOCATION OF THIS SERVICE WILL REQUIRE
 ZONING REVIEW AND APPROVAL.
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-22 Cont ID  
Sent By rlecky Date 2011-02-22 Time 08:36 Rev Time 0.00
Received By rlecky Date 2011-02-15 Time 07:37 Sent To  
Notes
2011-02-15 07:38:27INCOMING SENT TO < $5,000.00 ELECTRIC BOX. JW

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***