Plan Review Details - Permit 11020323
Plan Review Stops For Permit 11020323
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-02-17 Cont ID  
Sent By jwitmer Date 2011-02-17 Time 11:44 Rev Time 0.77
Received By jwitmer Date 2011-02-17 Time 11:43 Sent To  
Notes
2011-02-17 12:50:30BUILDING PLAN REVIEW
 PERMIT: 11020323
 ADD: 225 CLEMATIS ST
 CONT: R BUILDERS, INC
 TEL: (561)531-9079
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PLEASE NOTE THAT A SEPERATE PERMIT REVIEW AND
 ASSOCIATED FEES ARE REQUIRED FOR THE WALK-IN-COOLER,
 PROVIDE THE FOLLOWING INFORMATION FOR CODE COMPLIANCE
 FOR THE NEW MECHANICAL PERMIT : WALK IN COOLER.
  
 2007/ 2009 FBC-BUILDING
 SECTION 2603
 FOAM PLASTIC INSULATION
 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM PLASTIC
 INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES (254 MM)
 IN COOLER AND FREEZER WALLS SHALL:
  
 1.HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
  
 2.HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES OF
 NOT LESS THAN 600'F AND 800'F (316'C AND 427'C),
 RESPECTIVELY.
  
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
  
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-02-22 Cont ID  
Sent By rlecky Date 2011-02-22 Time 16:15 Rev Time 0.00
Received By rlecky Date 2011-02-22 Time 16:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-02-17 Cont ID  
Sent By wjolin Date 2011-02-17 Time 10:29 Rev Time 0.00
Received By wjolin Date 2011-02-17 Time 09:40 Sent To  
Notes
2011-02-17 10:29:40225 CLEMATIS STREET
 PERMIT #11020323
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE DRY PENDENT SPRINKLER COVERAGE IN NEW COOLER.
  
 MODIFY EXISTING SPRINKLERS FOR NEW LAY-IN CEILING.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR THE INSTALLATION
 OR MODIFICATION OF THE FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-15 Cont ID  
Sent By jwitmer Date 2011-02-15 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2011-02-15 Time 08:52 Sent To  
Notes
2011-02-15 08:53:36INCOMING SENT TO C-7 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-03-01 Cont ID  
Sent By hmoser Date 2011-03-01 Time 13:05 Rev Time 0.00
Received By hmoser Date 2011-03-01 Time 13:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-02-22 Cont ID  
Sent By aaponte Date 2011-02-22 Time 11:38 Rev Time 0.00
Received By aaponte Date 2011-02-22 Time 11:38 Sent To  
Notes
***NONE***