| Plan Review Stops For Permit 11020301 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2011-04-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-25 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-25 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2011-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-08 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-08 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2011-04-08 07:35:14 | 2009 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON SHEET A-1 | | | OF THE PLANS ARE STILL INCORRECT. THE PRESSURES FOR 140 | | | MPH EXPOSURE C SHOULD BE +42.7 PSF, -57.2 PSF FOR THE | | | WINDOWS (10 SQFT EFFECTIVE WIND AREA) LOCATED IN WALL | | | ZONE 5. THE DOOR IN WALL ZONE 4 SHOULD BE +41.6 PSF, - | | | 45.2 PSF (15 SQFT EFFECTIVE WIND AREA). THE WINDOWS | | | LOCATED IN WALL ZONE 4 (10 SQFT EFFECTIVE WIND AREA) | | | SHOULD HAVE PRESSURES OF +42.7 PSF, -46.3 PSF. SEE FBC | | | TABLES R301.2(2) AND TABLE R301.2(3) AND ASCE 7-05 | | | FIGURE 6-3. IF YOU DO NOT AGREE PLEASE SUBMIT SIGNED | | | AND SEALED CALCULATIONS FROM THE ENGINEER SHOWING HOW | | | THE PRESSURE WERE DETERMINED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2011-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-24 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-23 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2011-03-24 08:06:18 | 2009 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY FORM THAT WAS SUBMITTED (1100B-07) IS NOT | | | THE CORRECT ONE. PLEASE FILL OUT THE CURRENT FORM | | | (1100B-08) AND SUBMIT 2 COPIES. | | | | | | 2) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | FIXED WINDOW IS ONLY TESTED FOR SMALL MISSILE IMPACT. | | | FBC R301.2.1.2 REQUIRES THE WINDOWS TO BE TESTED FOR | | | LARGE MISSILE IMPACT OR HAVE IMPACT PROTECTION DEVICES | | | INSTALLED. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR | | | THE FIXED WINDOWS TESTED FOR LARGE MISSILE IMPACT OR | | | THE IMPACT DEVICES THAT WILL BE USED. | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE PGT | | | SINGLE HUNG WINDOWS HAS THE WRONG NOA NUMBER. THE NOA | | | SPECIFIED FOR FL239-R14 IS 07-0322.06. PLEASE SUBMIT 2 | | | COPIES OF THE COMPLETE CORRECT NOA. | | | | | | 4) THE PRODUCT APPROVALS SUBMITTED FOR THE JELD-WEN | | | GLAZED OUTSWING DOORS DO NOT HAVE ADEQUATE DESIGN | | | PRESSURES. THE PLANS SPECIFY HIGHER PRESSURES. | | | | | | 5) THE WINDOW AND DOOR PRESSURES SPECIFIED ON SHEET A-1 | | | OF THE PLANS ARE INCORRECT. THE SMALL WINDOW LOCATED IN | | | WALL ZONE 5 SHOULD BE HIGHER THAN THE ONES IN ZONE 4 | | | AND FOR THE DOOR AND OTHER WINDOWS THE NEGATIVE | | | PRESSURE IS ALWAYS MORE THAN THE POSITIVE PRESSURE. | | | | | | 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE "REVIEWED" | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2011-02-28 09:57:46 | 2007 FBC W/2009 | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY | | | IMPACT FEES. | | | | | | 2) THE FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE | | | WINDOWS, MULLIONS AND DOORS ARE FOR THE 2004 CODE | | | VERSION. SUBMIT THE ONES FOR THE 2007 CODE VERSION. | | | | | | 3) THE FLORIDA PRODUCT APPROVAL COVERSHEET FOR THE DOOR | | | IS FROM A DIFFERENT MANUFACTURER (BENCHMARK) THAN THE | | | ATTACHED MIAMI-DADE NOA (JELD-WEN). THE FILE STATUS IS | | | CLOSED FOR THE NOA NO. 07-0731.04. SUBMIT CURRENT | | | PRODUCT APPROVAL THAT HAS BEEN REVIEWED AND APPROVED BY | | | THE DESIGNER OF RECORD. | | | | | | 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE FIXED | | | GLASS WINDOW IN THE NEW BEDROOM. | | | | | | 5) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED | | | REQUIRES CEILINGS TO BE INSULATED TO A MINIMUM OF R-30. | | | THE PLANS SPECIFY R-19 INSULATION IN THE CEILINGS AND | | | THE FORM HAS R-19. IN ORDER TO USE THIS METHOD EACH | | | COMPONENT IS REQUIRED TO MEET OR EXCEED THE PERFORMANCE | | | CRITERIA ON THE FORM, OTHERWISE METHOD A MUST BE USED. | | | PLEASE CORRECT. | | | | | | 6) THE OWNER/AGENT IS REQUIRE TO SIGN THE ENERGY | | | CALCULATION FORMS. | | | | | | 7) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED | | | BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE | | | EXTERIOR STUCCO. | | | | | | 8) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 | | | FOR THE FOUNDATION WEEP SCREED AT THE BOTTOM OF ALL | | | FRAMED EXTERIOR WALLS BELOW THE FLOOR LINE WHERE THE | | | WALL IS SUPPORTED BY A FLOOR OR FOUNDATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-04-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-25 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-25 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-28 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-28 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2011-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-04-08 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-04-04 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2011-04-04 11:52:49 | GAVE TO MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-24 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-21 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2011-03-21 10:38:06 | SENT TO R. MCDOUGAL'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-28 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-14 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2011-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-23 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-23 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2011-03-23 14:00:37 | MU2011-2341 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2011-02-28 07:54:50 | PLEASE SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT | | | FEES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-10-31 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-10-31 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-10-31 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2011-10-31 11:41:50 | PASS PROVISO | | | REFER TO SECTION 601.4 BALANCED RETURN AIR EXCEPTION # | | | 1 | | | 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER. | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-28 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2011-02-28 08:05:50 | NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL | | | PERMIT WAS APPLIED FOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-23 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-23 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-28 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-28 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2011-02-28 07:53:53 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) 2007 FBCR P3108.2 NOT MORE THAN ONE WET VENTED | | | FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY | | | VENTED FIXTURE DRAIN. PLEASE CORRECT DRAWING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2011-03-03 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2011-03-03 |
Time |
17:52 |
Rev Time |
1.00 |
| Received By |
lfranco |
Date |
2011-03-03 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|