Plan Review Details - Permit 11020297
Plan Review Stops For Permit 11020297
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 08:21 Rev Time 0.00
Received By shill Date 2011-03-14 Time 08:21 Sent To  
Notes
2011-03-14 08:36:57****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 REVISE INSTALLATION SCHEDULE AS FOLLOWS:
  
 1. (COMMENT FROM REVIEW #2) - THE ANCHOR SPACING DOES
 NOT COMPLY WITH REQUIREMENTS OF THE PRODUCT APPROVAL.
 FOR INSTANCE, SEE OPENING 1. C2 CONNECTION TYPE, BLOCK
 SUBSTRATE, -70PSF REQUIRES 4" SPACING, SEE CHART ON
 SHEET 10. THIS COMMENT APPLIES TO OTHER OPENINGS.
 PLEASE CHECK ALL AND REVISE INSTALLATION SCHEDULE AS
 REQUIRED.
  
 REVIEW #3 - COMMENT FROM REVIEW #2 PARTIALLY ADDRESSED
 - SOME OPENINGS (SUCH AS OPENING 1) SPECIFY DIFFERENT
 ANCHOR SPACING FOR TOP AND BOTTOM ALTHOUGH BOTH
 CONNECTIONS HAVE THE SAME CONNECTION TYPE, WIND DESIGN
 PRESSURE, AND SPAN. SEE OPENING 1, 12" SPACING DOES NOT
 MEET THE REQUIREMENT OF THE PRODUCT APPROVAL FOR 34"
 SPAN, 2.5" EDGE DISTANCE, BLOCK SUBSTRATE.
  
 PLEASE REVISE. PLEASE HAVE THE QUALIFIER VERIFY
 ACCURACY OF INSTALLATION SCHEDULE PRIOR TO SUBMITTAL.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-01 Cont ID  
Sent By shill Date 2011-03-01 Time 14:42 Rev Time 0.00
Received By shill Date 2011-03-01 Time 14:42 Sent To  
Notes
2011-03-01 14:44:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE ANCHOR SPACING DOES NOT COMPLY WITH REQUIREMENTS
 OF THE PRODUCT APPROVAL. FOR INSTANCE, SEE OPENING 1.
 C2 CONNECTION TYPE, BLOCK SUBSTRATE, -70PSF REQUIRES 4"
 SPACING, SEE CHART ON SHEET 10. THIS COMMENT APPLIES TO
 OTHER OPENINGS. PLEASE CHECK ALL AND REVISE
 INSTALLATION SCHEDULE AS REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-15 Cont ID  
Sent By shill Date 2011-02-15 Time 14:31 Rev Time 0.00
Received By shill Date 2011-02-15 Time 14:31 Sent To  
Notes
2011-02-15 14:35:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE MORE INFORMATION AS TO HOW YOU HAVE
 DETERMINED THAT THE BOTTOM SUBSTRATE IS CONCRETE RATHER
 THAN FILLED CMU. ALTERNATIVELY, PLEASE REVISE
 INSTALLATION SCHEDULE FOR BLOCK ON THE BOTTOM.
  
 2. PLEASE EXPLAIN SPANS; HOW CAN SPAN BE THE SAME SIZE
 AS OPENING WITH A 2.5 INCH EDGE DISTANCE, WALL MOUNT?
 PLEASE REVISE INSTALLATION SCHEDULE.
  
 3. SEE OPENING 2, ANCHOR SPACING DOES NOT COMPLY WITH
 CHART IN PRODUCT APPROVAL FOR THIS SPAN AND CONNECTION
 TYPE. PLEASE REVISE AND CHECK ALL OPENINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 08:37 Rev Time 0.00
Received By shill Date 2011-03-07 Time 14:24 Sent To  
Notes
2011-03-07 14:24:58SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-28 Cont ID  
Sent By jgomez Date 2011-02-28 Time 11:49 Rev Time 0.00
Received By jgomez Date 2011-02-28 Time 11:49 Sent To  
Notes
2011-02-28 11:49:20SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-15 Cont ID  
Sent By shill Date 2011-02-15 Time 14:35 Rev Time 0.00
Received By shill Date 2011-02-11 Time 15:30 Sent To  
Notes
2011-02-11 15:31:17TO MISC 1 BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved