Plan Review Details - Permit 11020284
Plan Review Stops For Permit 11020284
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-23 Cont ID  
Sent By rlecky Date 2011-02-23 Time 14:27 Rev Time 0.00
Received By rlecky Date 2011-02-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-15 Cont ID  
Sent By rlecky Date 2011-02-15 Time 09:04 Rev Time 0.00
Received By rlecky Date 2011-02-14 Time 14:32 Sent To  
Notes
2011-02-15 09:05:41SPECIFY HOW THE NEW SERVICE WILL BE SUPPORTED. NEC
 110.13
 SPECIFY THE MINIMUM CLEARANCE REQUIRED FOR THE OVERHEAD
 CONDUCTORS. NEC 230.24
 SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE), VOLTAGE,
 AND INTERRUPTING RATING REQUIRED FOR THE SERVICE. NEC
 110.11, 110.9, 110.20
 BUILDING # 1 REQUIRES A SUB PANEL. NEC 225.30
 PROVIDE GFCI PROTECTION ON RECEPTACLES. NEC 210.8
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-22 Time 13:54 Rev Time 0.00
Received By lmartine Date 2011-02-22 Time 13:54 Sent To  
Notes
2011-02-22 13:55:05GAVE TO LECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-15 Cont ID  
Sent By rlecky Date 2011-02-15 Time 09:05 Rev Time 0.00
Received By rlecky Date 2011-02-11 Time 14:54 Sent To  
Notes
2011-02-11 15:23:06TO ELECT UNDER $5K BOX