| Plan Review Stops For Permit 11020284 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-02-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-23 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-02-15 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-15 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2011-02-15 09:05:41 | SPECIFY HOW THE NEW SERVICE WILL BE SUPPORTED. NEC | | | 110.13 | | | SPECIFY THE MINIMUM CLEARANCE REQUIRED FOR THE OVERHEAD | | | CONDUCTORS. NEC 230.24 | | | SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE), VOLTAGE, | | | AND INTERRUPTING RATING REQUIRED FOR THE SERVICE. NEC | | | 110.11, 110.9, 110.20 | | | BUILDING # 1 REQUIRES A SUB PANEL. NEC 225.30 | | | PROVIDE GFCI PROTECTION ON RECEPTACLES. NEC 210.8 | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-02-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-02-22 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-02-22 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2011-02-22 13:55:05 | GAVE TO LECKY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-15 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-15 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-11 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2011-02-11 15:23:06 | TO ELECT UNDER $5K BOX |
|
|
|