Plan Review Details - Permit 11020243
Plan Review Stops For Permit 11020243
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-02-28 Cont ID  
Sent By jwitmer Date 2011-02-28 Time 14:48 Rev Time 2.20
Received By jwitmer Date 2011-02-28 Time 13:00 Sent To  
Notes
2011-02-28 15:13:50 
  
 BUILDING PLAN REVIEW
 PERMIT:11020243
 ADD: 500 N CONGRESS AVE. BLDG# C
 CONT: PAUL DAVIS RESTORATION
 TEL: (561)248-7167
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
  
  
  
 BUILDING PROVISO:
  
 SHEET A-4-0 DETAILS 4 & 5. FIRE BLOCKING 717.2.3 FIRE
 BLOCKING CONNECTIONS BETWEEN HORIZONTAL AND VERTICAL
 SPACES.
  
 DRAFTSTOPPING IN FLOORS:
 717.3.2 GROUPS R-1, R-2, R-3 AND R-4. DRAFTSTOPPING
 SHALL BE PROVIDED IN FLOOR/CEILING SPACES IN GROUP R-1
 BUILDINGS, IN GROUP R-2 BUILDINGS WITH THREE OR MORE
 DWELLING UNITS, IN GROUP R-3 BUILDINGS WITH TWO
 DWELLING UNITS AND IN GROUP R-4 BUILDINGS.
 DRAFTSTOPPING SHALL BE LOCATED ABOVE AND IN LINE WITH
 THE DWELLING UNIT AND SLEEPING UNIT SEPARATIONS.
  
 DRAFTSTOPPING IN ATTICS:
 717.4.2 GROUPS R-1 AND R-2. DRAFTSTOPPING SHALL BE
 PROVIDED IN ATTICS, MANSARDS, OVERHANGS OR OTHER
 CONCEALED ROOF SPACES OF GROUP R-2 BUILDINGS WITH THREE
 OR MORE DWELLING UNITS AND IN ALL GROUP R-1 BUILDINGS.
 DRAFTSTOPPING SHALL BE INSTALLED ABOVE, AND IN LINE
 WITH, SLEEPING UNIT AND DWELLING UNIT SEPARATION WALLS
 THAT DO NOT EXTEND TO THE UNDERSIDE OF THE ROOF
 SHEATHING ABOVE. EXCEPTIONS:
 3.IN OCCUPANCIES IN GROUP R-2 THAT DO NOT EXCEED FOUR
 STORIES IN HEIGHT, THE ATTIC SPACE SHALL BE SUBDIVIDED
 BY DRAFTSTOPS INTO AREAS NOT EXCEEDING 3,000 SQUARE
 FEET (279 M2) OR ABOVE EVERY TWO DWELLING UNITS,
 WHICHEVER IS SMALLER.
  
 SHEET A-1.1 UNIT #23 GENERAL NOTE #3, RENOVATION KEY
 NOTE # 14 BOTH INDICATE THAT NEW WINDOWS WILL BE
 INSTALLED AT UNIT # 23. THE MIAMI-DADE PRODUCT APPROVAL
 SUBMITTED 06-1211.07 IS A NON-IMPACT WINDOW THAT WILL
 REQUIRE WINDOW PROTECTION, STORM SHUTTERS UNDER A
 SEPARATE PERMIT, REVIEW AND FEES.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-02-25 Cont ID  
Sent By rlecky Date 2011-02-25 Time 12:19 Rev Time 0.00
Received By rlecky Date 2011-02-25 Time 12:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-02-22 Cont ID  
Sent By wjolin Date 2011-02-22 Time 10:17 Rev Time 0.00
Received By wjolin Date 2011-02-22 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-04 Cont ID  
Sent By lwagner Date 2011-03-04 Time 16:00 Rev Time 0.00
Received By lwagner Date 2011-02-11 Time 17:16 Sent To  
Notes
2011-02-11 17:16:42C40

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-02-28 Cont ID  
Sent By hmoser Date 2011-02-28 Time 10:37 Rev Time 0.00
Received By hmoser Date 2011-02-28 Time 10:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-03-04 Cont ID  
Sent By lwagner Date 2011-03-04 Time 15:59 Rev Time 0.00
Received By lwagner Date 2011-03-04 Time 15:32 Sent To  
Notes
2011-03-04 16:00:43FIXTURE INSTALL ONLY

Review Stop Z ZONING
Rev No 1 Status P Date 2011-02-25 Cont ID  
Sent By lfranco Date 2011-02-25 Time 17:16 Rev Time 0.00
Received By lfranco Date 2011-02-25 Time 17:16 Sent To  
Notes
2011-02-25 17:17:07PLANNING AND ZONING: ***** PASSED, *ZONING REVIEW NOT
 REQUIRED: INTERIOR WORK ONLY AND THE VALUE OF PROPOSED
 WORK DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.
 ******